Are there any other such receptacle replacement requirements?

Posted By Keith Lofland, Tuesday, May 01, 2012
Updated: Friday, September 07, 2012
Question

I know the Code requires GFCI protection for replacement receptacles in existing dwellings where receptacles are replaced in areas that would require GFCI protection under today’s Code. Are there any other such replacement requirements for other things such as AFCI protection elsewhere in the Code? DP

Answer

The GFCI requirement for replacement receptacles is located at 406.4(D)(3) in the 2011 NEC. An example of this would be at a non-GFCI protected kitchen countertop receptacle or a bathroom receptacle being replaced. New for the 2011 NEC are replacement receptacle outlets requirements for such things as AFCI protection, tamper-resistant receptacles and weather-resistant receptacles. Section 406.4(D)(4) requires AFCI protection for replacement receptacle outlets supplied by branch circuits that require AFCI protection elsewhere in the Code. The language in this new AFCI requirement will allow AFCI protection to be provided to the replacement receptacle by either an AFCI circuit breaker or by an outlet branch-circuit type AFCI device located at the replaced outlet or upstream on the supplying branch circuit. Both the receptacle and circuit-breaker type AFCI will provide protection for all receptacles and other outlets that are downstream on the branch circuit. It should be noted that this new receptacle replacement AFCI requirement for the 2011 NEC has a future effective date of January 1, 2014 for enforcement of this new requirement.

Section 406.4(D)(5) now requires listed tamper-resistant receptacles to be provided where replacement receptacles are installed at receptacle outlets that are now required to be tamper-resistant receptacles under today’s Code requirements. An example of this would be replacing existing receptacle outlets in the den or bedroom of an older existing dwelling unit as 406.12 requires tamper-resistant receptacles in all areas specified in 210.52. Section 406.4(D)(6) now requires weather-resistant receptacles to be provided where replacement receptacles are installed at receptacle outlets that are now required to be weather-resistant receptacles under today’s Code requirements. A good example of this would be replacing existing receptacle outlets in a damp or wet location such as an outdoor receptacle outlet at a dwelling unit or a commercial building as 406.9(A) and (B) requires listed weather-resistant receptacles at receptacles located in damp and wet locations. — Keith Lofland, IAEI Director of Education
About Keith Lofland: L. Keith Lofland is director of education, codes and standards for IAEI International. Previously, he was education, codes and standards coordinator and served a seminar specialist. Prior to his position with IAEI International, Keith spent nineteen years with the city of Garland, Texas, serving as their chief electrical inspector. He served as chair of the Texas Chapter in 1989. He served as secretary/treasurer for the Texas Chapter for ten years. Keith has taught seminars for IAEI since 2000. 

Tags:  Focus on the Code  May-June 2012 

Share |
Permalink | Comments (0)