Rule 10-812 — Grounding Conductor Size

[ 2 ] Published: July 2010 | Author: Leslie Stoch

Rule 10-812 specifies minimum grounding conductor sizes for low-voltage electrical systems up to 750 volts. This article discusses the complexities of this rule, which as you know, was revised in the 2009 Canadian Electrical Code.

Sub-rule 1 tells us that, when the electrical system grounding electrode is a continuous metallic public water system or other interconnected electrode systems that may provide multiple ground-fault current paths back to the source, the minimum grounding conductor size must be selected from Table 17. Sub-rule 2 continues on to say that the minimum grounding conductor size for other types of grounding electrodes must not be smaller than 6 AWG.

Appendix B explains that the minimum grounding conductor size for a solidly grounded electrical system need not be larger than 6 AWG, since most of the ground-fault current will be carried back to the source by the grounded circuit conductor (service neutral).

Appendix B further makes clear that when a continuous underground public metallic water system or other low impedance system is used as the grounding electrode, or that the source and electrical service grounding electrodes are interconnected, the minimum grounding conductor size must be selected from Table 17, since a sizable portion of the ground-fault current will be carried by the grounding conductor.

How to interpret Rule 10-812?

If your electrical system grounding electrode is a metallic water system, use Table 17.

If the electrical utility’s transformer and your electrical service are grounded to the same grounding electrode or separate interconnected grounding electrodes, use Table 17.

If the electrical utility’s transformer and your electrical service are grounded to separate grounding electrodes (other than a metallic water system), the system grounding conductor need not be larger than 6 AWG.

But a note of caution — if the building is supplied by a metallic water system and it’s not being used as the electrical system grounding electrode, the water system will need to be bonded to your electrical system grounding electrode (ground rods, ground plate, and so forth). Therefore a low impedance return path is established and you will still need to use Table 17.

All well and good, but this rule is also a bit of a head scratcher. What if your building has 5000-ampere electrical service equipment? Will the minimum 6 AWG grounding conductor size be heavy enough to safely carry the available ground-fault current? For an electrical service of this size, even though most ground-fault current is expected to return along the system neutral, the portion flowing back along other paths may be sufficient to burn off the system grounding conductor.

And I’m also struggling with the technical justification for the revised rule. We know that the impedance of the ground fault path consists of resistance and inductive reactance. Previously, testing has provided conclusive proof that the lowest impedance fault paths are always closest to the current-carrying conductors. Magnetic fields produced by the circuit conductors will force fault current along the path closest to the circuit conductors (the system neutral). Other paths further from the circuit conductors (such as a metallic water system or interconnected grounding electrodes), even though they may have low resistances, will usually have higher total impedances and therefore will only be expected to carry a much smaller portion of the fault current.

Play it safe. Always use Table 17. As with previous articles, you should always consult with the electrical inspection authority in each province or territory for a more accurate interpretation of any of the above.

Tags: , ,

Category: Canadian Code

About Leslie Stoch: Leslie Stoch, P.E. is principal of L. Stoch & Associates, providing electrical engineering and ISO 9000 quality systems consulting. Prior to that, he spent over 20 years with Ontario Hydro as an electrical inspection manager and engineer. Les holds a B.S. in electrical engineering from Concordia University in Montreal. .

Comments (2)

Trackback URL | Comments RSS Feed

  1. Mike Shea Mike Shea says:

    Les
    Always enjoy your articles. I am struggling with this rule and am a dissenting voice on a code interpretation to part 1 of which I am a new member, regarding this rule and when is a Larger than #6 required for grounding.
    In your article you mention a bonding conductor to a water main if an artificial electrode is used and I am not sure if you think the requirement for the bonding conductor is table 17. I do not think it is, nor do I think it is a problem.
    The city of Victoria has a network downtown which allows pretty high fault levels often considered to be 100 KA. We have old buildings with grounding on the water main and grounding via a station electrode. All are bonded to the water with a little #6. Never any damaged bonding conductors after a fault including faults on the mains of 2000 and 3000 amp services.
    FYI I believe the Continuous water mains must be interconnected with both the utility and consumer electrodes before the larger wire size is required but that is to be debated at the part 1 meeting in November in Vancouver. So standby there is more to come.
    I expect that at some point all low voltage grounding and bonding will not be required to exceed a #6 or some smaller than T17 ground and as you alluded the real fault path is the grounded circuit conductors. If anything, it might eliminate the possibility of reduced neutrals which I think would be the bigger safety improvement. From the information I have read, no more than %10 of fault current ever goes down the ground. From that perspective a 100ka fault would need a wire large enough to carry 10 KA for 8 cycles. That might be bigger than #6 and would be technically a more accurate way to size a ground or bond wire to a water mains.

  2. Leslie Stoch Leslie Stoch says:

    Hello Mike:

    Many thanks for your note and well thought out comments on my article on 10-812. Your points are well taken.

    In answer to your question on whether I believe that artificial electrode bonding conductor sizes are based on Table 17 – no, I believe the code only requires minimum #6 AWG copper wire. Your point on eliminating reduced size neutrals is a great one, as this would also address a number of other problems. But I still believe we should tread carefully when considering reducing grounding conductor sizes. Electrical loads and supply equipment are increasing in size and transformer impedances are minimized to reduce transformer load losses, creating higher fault currents. Although there may be some room for reducing ground wire sizes, we still need to draw a line in the sand.

    Again, many thanks for your great comments on my article. I’m happy someone actually reads them. Many people have struggled with this rule.

    Best wishes with your code deliberations, Les