Subscribe via RSS Feed

Focus on the Code

Question: When installing a supply-side bonding jumper, what are the requirements for installing such a conductor both inside and outside a raceway? What type of conductive material is suitable for a supply-side bonding jumper and how is it sized?

[ 0 ] By  |  January 23, 2012  |  IAEI January-February 2012

The term supply-side bonding jumper first appeared in the 2011 National Electrical Code as a result of a CMP-5 Task Group regarding the proposed revisions to Section 250.30 for grounding separately derived systems.

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Question: Where branch-circuit conductors pass through a panelboard and do not originate or terminate in that panelboard, is there any requirement for identifying where the overcurrent devices are located for these pass-through conductors?

[ 0 ] By  |  January 23, 2012  |  IAEI January-February 2012

In this instance, the panelboard is serving the function of a pull box for these pass-through conductors.

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Question: Both dc and ac photovoltaic systems in a common enclosure?

[ 0 ] By  |  November 21, 2011  |  IAEI November-December 2011

Question Where conductors from both dc and ac photovoltaic systems utilize a common junction box or other enclosure, are there any special identification requirements for these conductors? Also, where photovoltaic circuits are run inside a building (whether in conduit or not), can these circuits be run embedded within insulation, and if so, is there any [...]

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Question: Single receptacle for a refrigerator?

[ 0 ] By  |  November 21, 2011  |  IAEI November-December 2011

A single or duplex receptacle is acceptable in this situation. Section 210.52 addresses the requirements for dwelling unit receptacle outlets.

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Question: Protect grounding electrode conductor in crawl?

[ 0 ] By  |  January 1, 2009  |  IAEI January-February 2009

Section 250.64(B) states where exposed and on a surface, a grounding electrode conductor should be protected. If I sleeve an 8 AWG GEC in rigid nonmetallic conduct from the service panel to the crawl, do I have to protect the GEC in the crawl, or is it ok to run the GEC on the bottom [...]

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Question: Breakers not listed on panelboard data sheet

[ 0 ] By  |  January 1, 2009  |  IAEI January-February 2009

I would like some advice and general guidance regarding the use of breakers that are not listed on the panelboard data sheet. Some of these panels have not been made in twenty years and the company is out of business. I generally recommend finding surplus breakers on the internet. Most electricians try to get by [...]

1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)

Question: Exhaust Fans on Pitched Roofs

[ 0 ] By  |  January 1, 2009  |  IAEI January-February 2009

The question I have is spread over several sections of the NEC (or so I think). I am inspecting a surgery center that has a 14-in-12 or, possibly, 16-in-12 pitch roof. The engineer wants to place an exhaust fan on this roof. I am finding nothing specifically in the NEC that would preclude the placement [...]

1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)

Question: Is an additional bare copper bonding wire jumper required?

[ 0 ] By  |  September 1, 2008  |  IAEI September-October 2008

Article 250.92(A)(2) of NEC-2005 requires bonding between service enclosures. I have a meter base can with the grounding electrode conductor connected to the neutral lug going to the grounding electrode. I have a single-phase three-wire service conductor system feeding from the meter can to the service-disconnect panel. The meter base can and the service-disconnect panel [...]

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Question: Size of bonding wire for 200-amp load center

[ 0 ] By  |  September 1, 2008  |  IAEI September-October 2008

For a 200-amp load center used for feeding charging equipment that is approximately 400 ft from main switchboard, what size of bonding wire is required? — T. C.

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Question: Sunlight, Conductors and Raceways on Rooftops

[ 0 ] By  |  September 1, 2008  |  IAEI September-October 2008

When using a 90°C single conductor in an ambient temperature of 81°C – 89°C, what is the correction factor for this application? It is presumed once the temperature reaches 90°C the conductor has met or exceeded its rating. Is there ampacity present in this conductor at 85°C, however minimal it may be? There is no [...]

1 Star2 Stars3 Stars4 Stars5 Stars (No Ratings Yet)

Bad Behavior has blocked 2656 access attempts in the last 7 days.