|
|
||
|
IAEI News>Focus on the Code >CMP-17
Question
1. I seem to be frequently involved in
discussions over the use of cable ties as a supporting
means for metal-clad cable. Section 330.30 doesn’t
clearly state that cable ties can be used as a support
method. I am aware that cable ties are clearly defined
as an approved method in the following Code locations: 320.30, 334.30, 338.10(B)(b), and 340.10(4).
Could you give us your take on this subject? — G.C. Answer 1. Article
330.30 of NEC 2002 requires Type MC cable to be supported and secured
at intervals not exceeding 1.8 m (6 ft). Article 300.11 also applies and
requires cable assemblies to be securely fastened in place. Article 320.30
allows cable ties to be used to secure type AC cable and does
not allow cable ties to be used to support type AC cable.
Articles 334.30, 338.10(B)(4)(b), and 340.10(4) also reference cable ties
for securing but not for supporting cables. Cable ties are specifically
mentioned in 2002 Code articles for securing cable type wiring
methods but not as the supporting means. — Gaylen Rogers, CMP-17 | Return
to top | Question
2. I was under the impression that the number 8 bond wire did not have to go to
the electrical panel, but only from the tub motor to the piping systems and
any associated electrical equipment. — W. H. Answer 2. Hydromassage
tub installations are covered by Section 680.70 in NEC 2002. Since
there appears to be confusion about the difference between grounding and
bonding, let’s go back to the basics. The requirements for the bonding of
a hydromassage tub are found in Section 680.74, Bonding. In order to answer
this question let’s review the following sections that apply to this type
of installation: "680.74 Bonding. All metal piping systems, metal
parts of electrical equipment, and pump motors associated with the
hydromassage tub shall be bonded together using a copper bonding
jumper, insulated, covered, or bare, not smaller than 8 AWG solid. Metal
parts of listed equipment incorporating an approved system of double
insulation and providing a means for grounding internal nonaccessible,
non-current-carrying metal parts shall not be bonded." Let’s examine what bonding really is. Since there is
not a definition of bonding that is specific to Article 680, we must refer
to the definition of bonding found in Article 100. "Bonding (Bonded): The permanent joining of metallic
parts to form an electrically conductive path that ensures electrical
continuity and capacity to conduct safely any current likely to be
imposed." In this case we are discussing bonding as it pertains to
"the permanent joining of the metallic parts" of a hydromassage
tub as required by Section 680.74. This requirement is to tie all metal
parts together to insure that they are at the same potential. This
requirement for bonding just requires you to bond the metal parts together,
even though in reality, in most instances it will be tied back to the
grounding electrode system through the equipment grounding conductor that is
run to the pool equipment with the branch -circuit wiring. This requirement
for bonding should not be confused with the requirement for grounding as
provided to the pump motor by the equipment grounding conductor which is
usually required to be a 12 AWG wire for a 20-amp circuit. The bonding
requirement of Section 680.74 does not require you to run the required 8 AWG
conductor back to the panelboard feeding the circuit that runs to the pump
motor. There was a new fine print note added to Section 680.26(A) in the
2002 NEC that clarifies the intent of this requirement and should
probably be added to Section 680.74 also. "680.26(A), Performance. The bonding required by
this section shall be installed to eliminate voltage gradients in the pool
area as prescribed. "FPN: This section does not require that the 8 AWG
or larger solid copper bonding conductor be extended or attached to any
remote panelboard, service equipment, or any electrode." — Jim Maldonado, CMP-17 | Return
to top | Question 3.An
outdoor spa has an approved cover. The cover has a metal railing that is
mounted to the spa at the bottom rear and extends up and around the cover
top when the cover is closed. Does this metal railing have to be bonded? The
cover may be removed while this metal railing remains attached to the spa.
Also the spa has a metal railing for entering the spa. This metal railing
rotates up and over the water in the spa (about 1-1/2') and then rotates in
the opposite direction away from the spa. The railing is mounted to the spa
wall with nonmetallic brackets. The railing is approximately four feet long.
Does this have to be bonded? — R. H. Answer 3. An outdoor
spa is covered in the 2002 NEC under Section 680.40. From the
description given, let’s assume that there are metallic pipe railings
attached to the spa structure that will remain in place while the spa is in
use. Let’s also assume that these rails are attached to the pool structure
without a direct metal- to-metal connection to the metal frame of the spa
assembly and that the length of these rails exceed 100 mm (4 in.) in any
dimension. In order to answer this question let’s review the
following sections that apply to this installation: 680.42 Outdoor Installations. "A spa or hot tub
installed outdoors shall comply with the provisions of Parts I and II of
this article, except as permitted in 680.42(A) and (B), that would otherwise
apply to pools installed outdoors." 680.42(B) Bonding. "Bonding by metal-to-metal
mounting on a common frame or base shall be permitted. The metal bands or
hoops used to secure wooden staves shall not be required to be bonded as
required in 680.26." 680.26(B)(3) Metal Fittings. "All metal fittings
within or attached to the pool structure shall be bonded. Isolated parts
that are over 100 mm (4 in.) in any dimension and do not penetrate into the
pool structure more than 25 mm (1 in.) shall not require bonding." The installation as described, would require that these
railings be bonded, as required in Section 680.42, since the metallic parts
exceed 4" in any dimension, there is no metal-to-metal mounting, and
they will be within 1.5 m (5 ft) of the spa. — Jim Maldonado, CMP-17 | Return
to top | Question 4. As
a new electrical inspector I have been asked to show where in the Code it
is required to have a disconnect (not cord-and-plug) for a water heater. The
cord–and-plug is the issue. It has been a practice in the past to use
dryer receptacles and cords for the disconnecting means. The previous
inspector changed this to using an a/c disconnect as being acceptable. The Code sections I have used to prove this are 422.16, 400.7, 422.13, 422.30 and
427.55(B). Are there better references to use and where can I find listed
appliances? —T Answer 4. You are correct that water heaters are defined as an appliance,
by the definition of appliance in Article 100. The article that
covers appliances in the 2002 NEC is 422. Water heaters are
specifically mentioned in 422.13. Section 422.30 requires a disconnecting
means for appliances in accordance with Part III of Article 422. According
to 422.31(B) "the branch-circuit switch or circuit breaker shall be
permitted to serve as the disconnecting means where the switch or circuit
breaker is within sight from the appliance or is capable of being locked in
the open position." The past practice of using cords and plugs is
covered in 422.16(A), which limits the use of flexible cords to connect
appliances to those applications that meet certain conditions. Condition (1)
is "to facilitate their frequent interchange or to prevent the
transmission of noise or vibration." Water heaters do not require
frequent interchange nor do they usually transmit vibration or noise through
the wiring methods. Condition (2) is where "the appliance is intended
or identified for flexible cord connection." Usually in order for
the AHJ to determine if an appliance is intended to be cord-and-plug
connected, the appliance would come with the cord attached from the factory,
or "identified for flexible cord connection" it would be listed
and labeled for cord-and-plug connection. See the definition of identified in Article 100 and the fine print note (FPN). In most water heater
installations a disconnect switch is located adjacent to the water heater to
meet the disconnect requirements of 422.30. You also quoted 427.55(B) as an
applicable code requirement. This section covers "fixed electrical
pipeline or vessel heating equipment" and does not cover water heaters;
therefore, this section would not be applicable to this installation. —Jim
Maldonado, CMP-17, alternate | Return
to top | Question 5. I have inspected an installation of a heated floor in a bathroom at a home where the installer had roughed in a low-voltage (35-volt AC) floor tile heater mat. I asked about the compliance with NEC 424.44(G) and the answer that I received from a NRTL was that GFCI protection was not required because the low voltage was equal to GFCI protection. The primary of the transformer is 240V / 30A, with non GFCI protection. Please give me your comments. Thank you in advance. — G.L. Answer 5. In reviewing the NEC-2005, Section 424.44(G), I cannot find an exception for a low-voltage system that would allow for low-voltage systems to not be protected with GFCI protection. During the NEC-2005 ROP process, there were code change submittals to this section. Under proposal 17-34, it was proposed to change the requirement for GFCI protection to GFP protection, this proposal was rejected since the intent of the section is for personnel protection, not for equipment protection. Under proposal 17-37, it was proposed that “Listed Equipment provided with an isolation transformer including a grounded shield between primary and secondary windings does not need to be additionally protected by Ground-fault Circuit interrupter protection.” This proposal was rejected in the ROP stage. Under the NEC-2005, I do not see where being a low-voltage system equals GFCI protection as required by 424.44(G). The views of the authors of Focus on
the Code and the editor are provided solely as a public service. |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||