|
|
||
|
IAEI News>Focus on the Code >CMP-19
Question
1. Does Article 555 NEC specifically require the use of
marine power (listed marine power outlets), or can shore
power receptacles be installed in individual enclosures
in accordance with 555.19(A)(1) and 555.11? For example,
an individual meter base nippled to a 6-circuit sub
panel then nippled to a weatherproof FS box for
the shore power receptacle with a weatherproof cover. — J.P. Answer 1. Article 555 of the 2002 NEC does not specifically require the use of marine power outlets. That is one
of several options that are found in 555.19(A)(1). A locking- and
grounding-type receptacle rated not less than 30 amperes or more than 50
amperes may also be installed in a listed weatherproof enclosure or in a
listed enclosure that is protected from the weather. Your example mentions
an FS box with a weatherproof cover, so you need to make sure that the
assembly also complies with the last sentence of 555.19(A)(1). | Return
to top | Answer
2. Section 550-23(b) allows the service
equipment for a manufactured home to be located in or on
the unit where all of the conditions (1) through (4) are
met. As such, there is nothing in 550-6 that would
prohibit this installation. The specific grounding rules
found in 550-11 are applicable to an installation where
the service equipment is located away from the unit and
a distribution panelboard is installed within the unit.
This would be the case for a mobile home, as the service
equipment is not permitted to be located in or on the
unit. Much of the confusion in
applying these rules stems from the fact that many
people tend to interchange the terms mobile home and manufactured home. The definitions in 550-2
tell us that the two are treated the same unless
specifically indicated otherwise. When it comes to the
service equipment, we find a case where the distinction
is indicated. Section 550-23(a) is specifically titled
Mobile Home Service Equipment, and 550-23(b) is titled
Manufactured Home Service Equipment. For the 2002 edition,
550-23 has been renumbered 550.32, and 550.32(B) has
added language that states where the service equipment
is not installed in or on the unit, the installation
shall comply with the other provisions of this section.
This would then trigger in the grounding requirements
which are now found at 550.16. It is important to
understand that the NEC is not the
primary document used for the construction of
manufactured housing. The construction requirements are
found in the HUD Part 3280 rules. These rules reference
the NEC where the HUD rules do not
specifically state a requirement. As part of an ongoing
project, NFPA 501, Standard on Manufactured Housing, has
been rewritten with the intent of becoming the primary
referenced rules in the HUD document. The changes you
see in the 2002 NEC were developed from NFPA 501.
To see where all this leads us, 501 section 9.3.11(3)
contains the identical provisions as section 550.32(B)
of the NEC. In addition, NFPA 501, 9.4.10 and
9.4.11, specifically allow for the service equipment to
be installed on the manufactured home. In summary, the answer to
your question is yes, provided all the conditions in
550-23(b) are met and the unit is, in fact, a
manufactured home bearing the HUD label. Dealing with
different units that are seemingly identical can be a
challenge, and I hope this answer is useful to you. — Robert
McCullough, CMP-19 | Return
to top | Question
3. A journeyman industrial electrician with ten years of
experience in the food industry, I recently switched from a
vegetable processing operation to a milk processing plant.
While the use of rigid aluminum raceway is familiar to me,
along with effects of high pressure wash down including high
strength cleaning chemicals, I was surprised to find that the
milk processing plant uses stainless steel tubing as the
preferred raceway for electrical conductors. The tubing is
purged and welded to additional lengths of stainless steel
tubing as well as elbows and boxes. While this makes an impressive looking
raceway, I am curious as to how this is allowed seeing that no
such wiring method appears in the NEC. The plant
engineer assures me that this is the preferred method among
dairies and is perfectly acceptable. Would you send me any information about the
use of this method? Is another set of code rules involved with
the dairy industry? Is this method an NEC violation?
The small community has no electrical inspector. In that case
who is considered to be the authority having jurisdiction? —J.
E. Answer 3. The first part of your question deals with a wiring method in
a milk processing plant. This may or may not fall under the
scope of Article 547. If this plant is a part of or an area
adjacent to the milking operation or confinement area, then
this would be covered in 547.1 and the wiring methods set
forth in 547.5 would be applicable. Section 547.5(A) permits,
in addition to the specific wiring methods listed, other
cables or raceways suitable for the location. Since you
indicate that the area is subject to high-pressure wash down
and high strength cleaning chemicals are used, you would refer
to 300.6 in general for protection against corrosion. That
section states that the materials used must be suitable for
the environment encountered. Sections 110.2 and 110.3(A)
provide guidance to the AHJ regarding suitability. If the plant is a separate building where
animals are not present and the product is brought in for
final processing, Article 547 would not apply and the general
rules of the Code would apply subject to any
installation restrictions for the particular environment
encountered. You specifically mention the use of stainless
steel tubing as the wiring method used in your facility and
express concern that this wiring method does not appear in the NEC. In order to address this concern it is necessary
to differentiate between tubing and conduit. If
in fact conduit has been used, stainless steel is an
acceptable material. Refer to the definition of rigid metal
conduit (RMC) contained in 344.2 where the last sentence
states, "Special use types are silicon bronze and
stainless steel." Stainless steel conduit is covered by
UL Standard 6A; and 344.6 requires the conduit to be listed.
Another point of concern would be your comment that the
stainless steel is welded to additional lengths. Section
300.18(B) does not permit metal raceways to be welded unless
specifically designed for this so the UL standard should be
reviewed to see if this application is permitted. If stainless
steel tubing rather than conduit has been used, I would be
concerned about the suitability of this for use as a raceway
based on the listing requirements as well as the effectiveness
as an equipment grounding conductor. Now to "milk" this answer
further, I will try to address your other questions. You ask
if there is another set of rules involved with the dairy
industry. The rules that govern any electrical installation
depend on how your particular state or jurisdiction regulates
such installations. If the political jurisdiction has adopted
requirements for installation codes, you would have to look at
that adoption and see what rules are in place. There are some
areas in the country that specifically exempt agricultural
industries from any regulation. Others may adopt codes without
a mechanism for enforcement; in which case, the onus for
compliance is on the building owner. Since you state the small
community has no electrical inspector, that may be the case.
This brings us to your last question — who is considered to
be the AHJ? As I stated previously, you have to find out if
the political jurisdiction has adopted any regulations
covering electrical installations and, if it has, has an
entity been designated to enforce the regulations. In looking
at the definition of authority having jurisdiction in
Article 100, the AHJ could be an organization, office or
individual. The FPN for this definition contains examples of
who could possibly be considered the AHJ and it is worth
noting that in some cases this could be the building owner. So
to "herd" all this together and head back to the
barn, can this wiring method be used? Following the guidelines
of 110.2, the definition of approved in Article 100,
and 90.4, the AHJ could choose to accept this installation. I
would hope that the AHJ would not take this approval process
lightly. — Robert McCullough, CMP-19 | Return
to top | The views of the authors of Focus on
the Code and the editor are provided solely as a public service. |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||