|
|
Sign In | Register Now Why Register? |
||
|
|
|||
|
|
|||
|
IAEI News>Issue Listing>March/April 2000 >Wire Temperature Ratings and Terminations
Many electrical inspectors can tell you that confusion about wire temperature ratings and equipment termination temperature requirements results in their rejecting installations. Information about this topic can be found in the National Electrical Code (NEC), testing agency directories, product testing standards, and manufacturers’ literature, but many people do not consult these sources until it is too late. Why are
temperature ratings important? The ampacity of the 1/0 Cu conductor depends on the temperature rating of the insulation. At the same ampacity, a smaller conductor with higher-rated insulation can be used instead of a larger conductor with lower-rated insulation. As a result, the amount of copper and even the number of conduit runs needed for the job may be reduced. One of the most common misapplications of conductor temperature ratings occurs when the established temperature rating of the equipment termination is ignored. This is particularly true for equipment rated for 600 V and less since the equipment is tested as a complete system using conductors sized by the NEC rules. Reduced conductor sizes result in the system having less ability to dissipate heat and therefore increase the operating temperature of the equipment terminations. Conductors must be sized by considering where they will terminate and how that termination is rated. If a termination is rated for 75°C, the maximum temperature at that termination is 75°C when the equipment is loaded to its ampacity. If 60°C insulated conductors are used in this example, the additional heat at the connection above 60°C could result in conductor insulation failure. When a conductor is selected to carry a specific load, the user/installer or designer must know the termination ratings for the equipment in the circuit. For example, consider a circuit breaker with 75°C terminations and a 150A load. If a THHN (90°C) conductor is chosen for the job, review Table 310-16 in the NEC and look for a conductor that will carry the 150A. Although a 90°C conductor is being used, ampacity must be chosen from the 75°C column because the circuit breaker termination is rated at 75°C. Based on the table, a 1/0 copper conductor is acceptable. The installation would be as shown in Figure 1, with proper heat dissipation at the termination as well as along the conductor length. Had the temperature rating of the termination not been a consideration, a No.1 AWG conductor might have been chosen, based on the 90°C ampacity. This may have led to overheating at the termination or premature opening of the overcurrent device due to the smaller conductor size (see Figure 2). In this same example, a conductor with a 75°C insulation type (THW, RHW, USE, etc.) also would be acceptable since the termination is rated at 75°C. A 60°C insulation type (TW) is not acceptable since the temperature at the termination could rise to a value greater than the insulation rating. The NEC Rules Equipment Rated for 100A or Less— NEC 110-14(c)(1)(a) through (d) NOTE: The equipment sizes and ampacities shown in the figures are arbitrary. The rules apply to any equipment rated 100A or less. For equipment with termination provisions for circuits rated 100A or less or marked for No. 14 AWG through No. 1 AWG conductors, the NEC allows conductors to be used based on the following four conditions:
Equipment Rated Above 100A—NEC 110-14(c)(2)(a) and (b) For equipment with termination provisions for circuits rated above 100A or marked for conductors larger than No. 1 AWG, the NEC 110-14(c)(2)(a) and (b) allows conductors to be used based on the following conditions:
The equipment termination ratings versus conductor insulation ratings are summarized in Table 2. Caution on using
lug ratings Review the labeling of all devices and equipment for installation guidelines and possible restrictions. Available
Equipment Terminations For electrical equipment rated for 600V and less, terminations are typically rated to 60°C, 75°C, or 60/75°C. No distributions or utilization equipment is listed and identified for the use of 90°C wire at its 90°C ampacity. This includes distribution equipment, wiring devices, and even utilization equipment such as HVAC, motors, and light fixtures. Installers and designers who have not realized this fact have equipment that does not comply with the National Electrical Code and that has been turned down by the electrical inspector. In equipment rated over 600V, the effect of the conductor as a heat sink is minimized, and ratings higher than 75°C are available. NEC 110-40 recognizes that conductors with sizes based on the 90°C ampacity can be used in installations over 600V. An example of how 90°C wire might be used at its 90°C ampacity is shown in Figure 9. Note that the conductor does not terminate directly in the distribution equipment, but in a terminal or tap box using 90°C-rated terminations. Frequently, manufacturers are asked when distribution equipment will be available with terminations that will permit 90°C conductors at the 90°C ampacity. This would require not only significant equipment redesign (to handle the additional heat), but also coordination of the downstream equipment where the other end of the conductor terminates. Significant changes in the product testing/listing standards also would have to occur. A final note about equipment—some equipment requires the conductors that are terminated in the equipment to have an insulation rating of 90°C, but an ampacity based on 75°C or 60°C. This type of equipment might include 100 percent rated circuit breakers, fluorescent lighting fixtures, etc., and is marked to indicate such a requirement. Check with the manufacturer of the equipment to see if you need to take into account any special considerations. What about
higher-rated conductors and derating factors? Remember these points while studying the derating process example:
Example of the
derating process Additional information to consider from the NEC:
Calculate, using a 75°C conductor such as THWN:
201A is now the allowable ampacity of the 300 kcmil copper conductor for this circuit. Had the derating factors for conduit fill and ambient not been required, a 3/0 copper conductor would have met the needs for this application. Calculate, using a 90°C conductor such as THHN:
Therefore, when using 90°C wire for derating purposes, you can begin derating at the 90°C ampacity. You must compare the result of the calculation to the ampacity of the conductor based on the termination rating (60°C or 75°C). The smaller of the two numbers then becomes the allowable ampacity of the conductor. Summary Jim Pauley is a registered professional engineer in the state of Kentucky and is manager, Global Standards Strategy for Square D Company. He serves on NEC Code-Making Panel No. 2, the NEC Technical Correlating Committee and the NFPA Standards Council. He is also active with UL, NEMA and the American National Standards Institute and serves on the Kentucky Chapter IAEI Executive Committee as well as the IAEI Western Section Board of Directors.
|
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||