
IAEI
News>Issue Listing>September/October 2000>Proposed Changes for the 2002 NEC, Part 2
| Proposed Changes for the 2002 NEC, Part 2 |
Part 2 on the proposed changes to articles of the Code within the scope of 20 NEC code-making panels. |
|

This is the second part of a summary of
proposed changes for the 2002 National Electrical Code® acted
on by NEC Code Making Panels in January 2000. Proposals
submitted to change the 2002 Code are included in the NEC Report on Proposals. That document is available from the
National Fire Protection Association. Those who wish to make
comments on actions taken by the code making panels must
submit them to NFPA. They must be received by NFPA no later
than 5:00 p.m. EDST, Friday, October 27, 2000. Blank forms for
those comments are available from NFPA. They are also included
in the ROP and can be downloaded from the NFPA web site. The
address is www.nfpa.org. Action will be taken in December 2000
by the 20 NEC Code Making Panels on public comments
submitted and the results of panel actions will be published
by NFPA in the NEC Report on Comments.
210-52(c)(5).
Receptacle Outlet Location.
Proposal No. 2-172: The term "appliance garages"
has been added to the last sentence. This change clarifies
that a receptacle installed inside an "appliance
garage" does not count as the required outlet. An
"appliance garage" is understood to be an enclosed
area on the countertop where an appliance can be stored and
hidden from view when not in use.
210-52(c)(5).
Exception.
Proposal No. 2-175: The second sentence of the Exception
has been revised to read, "Receptacles mounted below a
countertop that extends more than 6 in. (153 mm) beyond its
support base, shall be located so that they are not more than
6 in. (153 mm) from the outside edge of the countertop."
This change will permit the mounting of
receptacles to the underside of extended countertops, provided
the receptacles are within 6 inches of the outside edge of the
countertop.
210-52(g). Basements
and Garages.
Proposal No. 2-196: The last sentence has been changed to
read, "Where a portion of the basement is finished into
one or more habitable rooms, each separate unfinished portion
shall have a receptacle outlet installed in accordance with
this section."
This makes it clear that any unfinished
portion of the basement, when separated by a finished portion,
will have to have a receptacle outlet installed.
210-70(a)(2).
Additional Locations.
Proposal No. 2-226(a): 210-70(a)(2) has been restructured
for clarity and the last sentence has been revised to become
210-70(a)(2)c and reads, "c. Where one or more
lighting outlet(s) are installed for interior stairways, there
shall be a wall switch at each floor level, and landing level
that includes an entry way, to control the lighting outlet(s)
where the stairway between floor levels has six risers or
more."
This change in 210-70(a)(2)c will require a
switch at an intermediate landing that has an entry way as
well as at each floor level. In addition, the word
"step" was changed to "riser" to conform
with the accepted terms for the elements of a stairway.
Table 220-36.
Optional Method—Permitted Load Calculations for Service and
Feeder Conductors for New Restaurants.
Proposals Nos.2-304 and 2-305: Table 220-36 on the
optional method for calculation of service and feeder
conductors for new restaurants has been changed to reduce the
break points from six to four and avoids the problem of adding
load and reducing switch sizes, which the existing table would
allow in isolated cases.
Article 225 – Outside Branch Circuits and Feeders:
225-26: Vegetation as
Support.
Proposal No. 4-16: This section was revised to read:
"225.26. Vegetation as Support. Vegetation, such
as trees, shall be permitted only for the support of temporary
wiring, as covered in Article 305." The title was
expanded by adding the words "as support." The
wording "overhead conductor spans" at the end of the
sentence was replaced with "temporary wiring, as covered
in Article 305." The exception was deleted as the concept
of temporary wiring is included in the revised section.
225-30: Number of
Supplies.
Proposal No. 4-17a: The first sentence of the section was
modified by adding the wording "additional" and
"that is on the load side of the service disconnecting
means." It will now read: "Where more than one
building or other structure is on the same property and under
single management, each additional building or other structure
served, that is on the load side of the service disconnecting
means, shall be supplied by one feeder or branch circuit
unless permitted in (a) through (e)." The revised wording
adds clarity to the general rule covering the number of
supplies permitted for multiple buildings or structures. The
additional building or structure covered by this section are
those supplied by conductors on the load side of the service
disconnecting means.
225-30(a)(4).
Proposal No. 4-18a: The word "optional" was
deleted from 225-30(a)(4) and will now read: "(4) Standby
systems." This change should eliminate any potential
confusion regarding standby systems being permitted under this
section.
225-50. Supervised
Installations. Proposal No. 4-39: A new section was
added to describe conditions under which over 600 volt
installations can be considered as supervised installations.
The proposal was submitted as a new 225-48, but was renumbered
by action on Proposal 4-40b.
225-51. Sizing of
Outdoor Circuits.
Proposal No. 4-40b: This new section has been added to
include general rules for sizing of outdoor branch circuit and
feeder conductors in over 600 volt installations. It also
includes provisions for the sizing of conductors rated over
600 volt in supervised installations described in new 225-50.
Conductors in supervised installations are permitted to be
determined by qualified persons under engineering supervision.
Article 230 –
Services
230-70(a). Location.
Proposal No. 4-107a: This section was restructured and
revised to better describe the required location of a building
service disconnecting means and to clarify that a remote
control actuator is not recognized as the required
disconnecting means.
Article 240 – Overcurrent Protection
240-21(c). Transformer Secondary
Conductors.
Proposal No. 10-34: The title of subdivision (3) was
revised to read "Industrial Installation" and a new
subdivision (6) entitled "Secondary Conductors Not Over
25 ft Long" was added. The change more clearly identified
the title of (3) to reflect the restriction to industrial
installation and the new (6) provides a general 25 ft tap rule
for transformers.
240-33. Vertical
Position.
Proposal No. 10-46: The wording "unless that is shown
to be impracticable" was added to the end of the first
sentence. This change addresses the conditions where circuit
breaker enclosures cannot be mounted in the vertical position.
240-83(d). Used as
Switches.
Proposal No. 10-63: New wording has been added to this
section to require circuit breakers used as switches for high
intensity discharge lighting to be marked "HID."
240-86. Series
Ratings.
Proposal No. 10-67: This section has been revised to add a
provision for a line-side current-limiting device to be
selected under engineering supervision to protect load side
circuit breakers that have a lower interrupting rating than
the available fault current on the circuit.
240-100(a).
Proposal No. 10-77: The main rule covering overcurrent
protection for over 600 volt feeders and branch circuits has
been revised to provide examples of items to consider when
designing the overcurrent protection to be at a location other
than at the point where the conductor receives its supply. The
design for overcurrent protection to be at an alternate
location is required to be done under engineering supervision.
Article 250 –
Grounding:
250-2(a). Grounding of Electrical
Systems.
Proposal No. 5-60: The wording "required to be"
was deleted from 250-2(a). This action should clarify that
grounding rules must be followed whether systems are grounded
because they are required to be, or if they are grounded by
choice.
250-30(a)(2).
Proposal No. 5-101: A new paragraph has been added to
250-30(a)(2) to permit a grounding electrode conductor of a
separately derived system to be connected to a grounding
electrode conductor that extends through a building. This
change permits an alternate method of grounding separately
derived systems where effectively grounded building steel or
grounded metal water pipe is not near the separately derived
system.
250-32(f). Grounding Electrode
Conductor.
Proposal No. 5-123: The title of 250-32(f) was amended by
adding the word "electrode" and the reference to the
table has been changed from Table 250-122 to read Table
250-66. This modification changes the sizing requirement for
the grounding conductor at the second building or structure to
that based on Section 250-66. In addition, the term for this
conductor is no longer a "grounding conductor," but
is a "grounding electrode conductor."
250-36(g). Equipment
Bonding Jumper Size.
Proposal No. 5-134: A new 250-36(g) has been added to
provide equipment bonding sizing requirements for
high-impedance grounded neutral systems.
250-50. Grounding
Electrode System. Proposal No. 5-134a: This section
has been revised to read: "Grounding Electrode System. If available on the premise at each building or structure
served, each item in 250-52(a)(1) through (a)(6) shall be
bonded together to form the grounding electrode system. Where
none of these electrodes is available, one or more of the
electrodes specified in 250-52(a)(4) through (a)(7) shall be
used."
This revised section includes requirements
related to the grounding electrode system and correlates with
the revised 250-52 and the new 250-53. The reference to
"made electrodes" was deleted from this section.
250-52. Grounding
Electrodes. Proposal No. 5-162(a): This section was
revised by changing the title to "Grounding
Electrodes" and was restructured to include two
subheadings, "(a) Electrodes Permitted for
Grounding" and "(b) Electrodes not Permitted for
Grounding." This section describes electrodes that are
permitted for grounding and includes those that were
previously described as "made and other electrodes."
The reference to made electrodes has been deleted. The change
in this section, the amended 250-50, and the new 250-53 should
help make it easier to understand the application of those
respective rules.
250-53. Grounding Electrode System
Installation.
Proposal No. 5-171a: A new section has been added to cover
installation requirements for grounding electrode systems.
This section includes much of the material in Sections 250-50
and 250-52 of the 1999 NEC. Placing installation
requirements for all grounding electrodes in one location will
make it much easier for Code users to follow.
250-102(e).
Installation.
Proposal No. 5-212: A new sentence was added to permit an
equipment bonding jumper to be longer than 6 feet where used
to bond or ground metal raceways and elbows at utility poles.
250-104(a). General.
Proposal Nos. 5-219, 5-220, and 5-221: The word
"interior" has been deleted and the word
"installed in or attached to a building or
structure" were added in 250-104(e) (1), (2), and (3).
This change clarifies the fact that piping installed inside or
outside and attached to the building or structure is required
to be bonded.
250-104(b). Metal Gas
Piping.
Proposal No. 5-229: The text in 250-104(b), which was
extracted material from NFPA 54 for bonding metal gas piping
systems, was deleted.
250-104(c). Other
Metal Piping Systems. Proposal No. 5-238: The term
"interior" was deleted and the wording
"installed in or attached to a building or
structure" was added. Other piping located inside or on
the exterior and attached to the building or structure is now
required to be bonded.
250-104(d).
Structural Steel.
Proposal No. 5-240: The term "interior" in the
first sentence was deleted. This change clarifies that
structural steel whether interior or exterior that is not
intentionally grounded and interconnected to form a building
frame must be bonded where it is likely to become energized.
250-118(11).
Proposal No. 5-254: The wording "the smooth or
corrugated" was added before "Type MC cable to
clarify that only the sheaths of smooth or corrugated
tube-type MC cable assemblies are suitable for grounding.
250-146(a). Surface
Mounted Box.
Proposal No. 5-282: The wording "or at" in the
first sentence was deleted. This change will permit only
surface mounted boxes to be used for direct metal to metal
contact between the receptacle yoke and the box as a means of
grounding receptacles. This reverses the allowance granted for
boxes mounted "at the surface" in the 1999 NEC to be acceptable for grounding receptacles.
250-184(d).
Proposal No. 5-302: A new 250-184(d) has been added to
cover rules on the size and grounding of the neutral and
limits the maximum distance permitted between adjacent
grounding electrodes on solidly grounded neutral systems to
400 meters.
Article 285 –
Transient Voltage Surge Suppressors (TVSS)
Article 285.
Proposal No. 5-316: A new Article 285 was added to
requirements for installations of Transient Voltage Surge
Suppressors (TVSS). Transient voltage surge suppressors are
widely used as part of electrical systems in areas covered by
the National Electrical Code but are not directly
addressed by the Code.
Chapter 3 Articles
General Changes in
Chapter 3:
Considerable work has been done by task groups to continue
improving the Code and to make it even more user
friendly. Chapter Three of the NEC was included in the
task group work and several recommendations were made. The NEC Technical Correlating Committee and Code Making Panels
affected by this work took action on task group
recommendations and some of those actions are as follows:
Reformatting: Many Chapter 3 articles
have been rewritten and reformatted to have similar structure
and to comply with the NEC Style Manual. A more uniform
method of numbering sections within each article will be used.
As an example, the first section in each article is designated
for the scope of that article (318-1, 336-1, etc). The second
section is for definitions used in that article. "Uses
Permitted" will have the same extension or section
identifier in each applicable article (336-10, 345-10, etc).
Renumbering: Many Chapter 3 articles
will be renumbered at the end of the processing of the 2002 NEC.
This change includes a grouping of cable and raceway articles
in a more logical manner.
Relocation: Some Chapter 3 articles are
being relocated to other chapters because the content and
scope of those articles are more appropriate for those
chapters. As an example of relocation, Article 384,
Switchboards and Panelboards, will be moved to Chapter 4 and
renumbered.
Article 300 - Wiring
Methods and Materials
300-4(d),
Exception No. 3.
Proposal No. 3-30: Exception No. 3 which provides that
steel plates, sleeves, and similar protection of cables and
raceways installed parallel to framing members are not
required in mobile homes and recreational vehicles has been
deleted. Mobile homes and RVs will be required to comply with
the same rules on spacing in this section as applied to other
types of buildings.
300-7(a). Sealing.
Proposal No. 3-61: The wording in 300-7(a) requiring a
seal for raceways and sleeving for cables against the flow of
warm air within the raceway or sleeving to a colder section of
the raceway or cable to prevent condensation has been revised.
Wording has been added to specifically identify the passing of
a raceway or cable from the interior to the exterior of a
building and the wording "and where there is a known
condensation problem" has been added.
300-11(c). Cables
Not Used as Means of Support.
Proposal No. 3-73: A new 300-11(c), entitled "Cables
Not Used as Means of Support" has been added to clarify
that cable wiring methods are not to be used as support for
other materials and equipment. The present Code covers
restrictions on the use of raceways for support of cables,
other raceways, or other equipment, but does not specifically
prohibit cable from being used in that fashion. It is not
uncommon to find one cable installed and supported and others
attached to it rather than having individual supports. This
new subsection clearly prohibits the use of cable wiring
methods as a means of support for other items.
300-22(c)(1)
Exception.
Proposal No. 3-99: The exception that permitted
liquidtight flexible metal conduit in lengths not exceeding
six feet in spaces used for environmental air has been
deleted. The reference to "single lengths not exceeding 6
ft (1.83 m)" could have been misinterpreted to permit
multiple runs of liquidtight flexible metal conduit in
"other space used for environmental air" which does
not appear to be the intent of the exception.
Article 305 -
Temporary Wiring
Article 305.
Temporary Wiring.
Proposal No. 3-141: Article 305 has been re-located to
Chapter 5 and will be renumbered accordingly. This article is
more appropriate for Chapter 5 - Special Occupancies. CMP-3
will retain the responsibility of the relocated article.
305-3(b).
Proposal No. 3-124: The provision that allows holiday
decorative and similar lighting to be used for a period not
longer than 90 days has been amended to provide for such use
for more than 90 days where it is provided with arc-fault
circuit-interrupter protection. It is extremely difficult to
enforce the 90-day rule on this type of installation. Those
installations may be de-energized for periods of time and/or
redesigned and it is claimed that it constitutes a new 90 day
period. The use of AFCIs with those circuits will provide
another level of protection for those installations.
305-6(a) Exception
No. 2. Proposal No. 3-138a:
The exception that permitted an assured equipment grounding
conductor program to be used instead of using ground fault
circuit interrupters for personnel in industrial
establishments under certain conditions has been deleted. The
record of performance of GFCIs in the protection of personnel
justifies the use of those devices in the areas exempted by
the exception.
Article 310 - Conductors for General Wiring
310-8(d). Locations Exposed to Direct
Sunlight. Proposal 6-14a:
The text has been revised to clarify that conductors and
cables are required to be "listed for sunlight
resistance" or "listed and marked for sunlight
resistant" where they are exposed to the direct rays of
the sun.
310-15(b)(2)(a), Exception No. 5. Proposal
6-67:
A new exception has been added that will permit Type AC
cable and MC cable without an overall outer jacket to be
bundled without having to apply adjustment factors. Certain
conditions must be met in order to apply the new exception.
Table 310-22.
Ampacities of Two or Three Insulated Conductors, Rated 0
through 2000 Volts, Within an Overall Covering (Multiconductor
Cable), in Raceway in Free Air Based on Ambient Air
Temperature of 30EC (86EF). Proposal 6-6:
Table B-310-1 in Appendix B to Article 310 has been
relocated as Table 310-21. This change locates the table
within the requirements of the Code, enabling it to be used
without engineering supervision
Article 318 - Cable Trays
318-3. Uses
Permitted. Proposal No. 8-15:
A new sentence has been added to read, "Cable tray
installations shall be permitted to be used for feeder
circuits, branch circuits, communications circuits, control
circuits and signaling circuits." This additional wording
provides a better description of permitted uses of cable
trays.
318-3. Uses
Permitted. Proposal No. 8-31:
A new sentence has been added to read, "Cable trays
and their associated fittings shall be identified for the
intended use." This action provides an important focus on
the consideration of cable trays as to their design and
intended use so that they are installed and used properly.
318-3(e). Nonmetallic
Cable Tray. Proposal
No. 8-25a:
The wording in 318-3(e) has been revised by adding
"In addition to the uses permitted elsewhere in Article
318," at the beginning of the section. This change is to
clarify that nonmetallic cable tray is permitted for purposes
other than voltage isolation and corrosive areas.
318-6(c). Supports. Proposal
No. 8-56:
A new second paragraph has been added to this section to
read, "Cable trays shall be supported at intervals in
accordance with the installation instructions." Support
requirements have not previously been specified in this
section.
318-6(j). Raceway,
Cables, and Boxes Supported from Cable Trays. Proposal
No. 8-34:
The term "outlet" has been deleted from the
title of 318-6(j) and the wording "and conduit
bodies" added following the word "boxes". The
first sentence has been revised by deleting the word
"outlet" and rewording it to read "boxes and
conduit bodies as covered in Section 370-1." The word
"outlet" was deleted from the last sentence of the
section and changed to "boxes and conduit bodies..."
The reference to Article 370 was changed to Section 370-23.
This action will permit other boxes than just outlet boxes to
be supported beside or under the cable tray.
318-11(a). Multiconductor Cables. Proposal
No. 8-52:
A reference to Section 310-15(a)(2) has been added to this
section to provide guidance on the determination of allowable
ampacity of multiconductor cables. Where cables are run out of
the tray, consideration must be given to the rules for
allowable ampacity for conductors in those locations.
318-11(b). Single
Conductor Cables. Proposal No. 8-54:
A new first sentence has been added to read, "The
allowable ampacity of single conductor cables, shall be as
permitted by Section 310-15(a)(2)." This action is
intended to address the condition where single conductor
cables that leave the cable tray and are run in raceways or
locations where the lower ampacity should apply. In those
cases, the lower ampacity should be assigned to the cable to
better assure that the entire length of the circuit will
operate within safe limits.
Article 321 - Messenger Supported Wiring
321-4. Uses Not
Permitted. Proposal
No. 7-26:
The term "severe damage" was changed to
"damage." The distinction between "damage"
and "severe damage" is not clearly defined. It is
not desirable that this type of wiring be subject to damage,
much less to whatever severe damage might be.
Article 330 - Mineral-Insulated,
Metal-Sheathed Cable
330-80. Ampacity. Proposal No. 7-88:
A new Section 330-80 covering rules on the ampacity of
Type MI cable has been added.
Article 333 - Armored Cable
333-7(b). Proposal No. 7-101:
This change permits up to 6' of AC cable supplying
lighting fixtures or other equipment in accessible ceilings to
be unsupported. In the 1999 Code, this permission was
limited to runs directly from an outlet box to the fixture or
equipment.
Article 334 - Metal-Clad Cable
334-10(b).
Unsupported Cables. Proposal 7-122:
This section was amended by deleting the wording "from an
outlet." The resulting wording is "...or where used
in lengths not more than 1.8m (6 ft.) for connections within
an accessible ceiling to lighting fixtures or equipment."
334-22. Metallic
Sheath. Proposal 7-126a:
A new second paragraph has been added to read, "A
non-magnetic sheath or armor shall be used on single conductor
Type MC." The existing second paragraph is to become
paragraph three.
Article 336 - Nonmetallic-Sheathed Cable:
Types NM, NMC, and NMS
336-6(f). (To be
336-17). Grommets in Metal Studs. Proposal 7-158:
New text was added to make the language similar to that in
300-4(b)(1) for the protection of nonmetallic sheathed cable
run through metal studs and to require that grommets used for
cable protection in such studs be listed for that purpose.
This text will become a new second paragraph 336-17 in the
rewritten Article 336.
336-18, Exception No. 3. Proposal
No. 7-169:
This exception was amended by deleting the wording
"from an outlet" and the wording "shall be
permitted without a support within 300 mm (12 in.) of
termination." This change to Article 336 permits up to 4
1/2' of NM cable to be unsupported with accessible ceilings in
the same manner as AC and MC.
Article 338 - Service-Entrance Cable: Types
SE and USE
338-3(b). Grounded
Conductor Not Insulated. Proposal No. 7-203:
This provision was revised to prohibit the use of bare
grounded conductors, except as permitted by Section 250-140
for existing installations to ranges and clothes dryers. This
eliminates the practice of using SE cable with a bare grounded
conductor as the feeder to a second building.
338-4(a). Interior Installations. Proposal
No. 7-205:
This change clarifies that type SE cable used for interior
wiring must comply with the installation requirements of Parts
A & B of Article 336, except Section 336-26 which deals
with the ampacity of NM cable.
Article 340 - Power and Control Tray Cable:
Type TC
340-8. Bends.
Proposal No. 7-252a:
The wording in this section has been modified and expanded
to read, "340-8. Bending Radius. Bends in Type TC
cable shall be made so as not to damage the cable. For Type TC
cable without metal shielding, the minimum bending radius
shall be:
(1) Cables with an outside diameter of
1.000 inches or less- 4 times the overall diameter
(2) Cables with diameter of 1.001 to 2.000
inch - 5 times the overall diameter
(3) Cables with diameters of 2.001 inch and
larger - 6 times the overall diameter
Type TC cables with metallic shielding
shall have a minimum bending radius of not less than 12 times
the cable overall diameter."
This change in the minimum bending radius
of Type TC cable reflects accepted industry standards.
Article 343 - Nonmetallic Underground
Conduit with Conductors
343-1. Description. Proposal
No. 8-77:
A provision has been added to this section to require the
nonmetallic conduit used in this assembly to be listed.
Conductors and cables used in this assembly are required by
343-14 to be listed.
Article 345 - Intermediate Metal Conduit
345-9(a). Threadless. Proposal No. 8-217:
A new sentence has been added to read, "Threadless
couplings and connectors shall not be used on threaded conduit
ends unless listed for the purpose." This new provision
will aid in the selection and use of threadless couplings on
threaded ends of conduit as they will be required to be
"listed for the purpose."
345-12(b)(3). Proposal
No. 8-222:
The wording "industrial machinery" has been
replaced with "fixed equipment." This clarifies that
IMC can be dropped to fixed equipment where certain conditions
are met and that it can be so used in more than just
industrial locations.
Article 346 - Rigid Metal Conduit
346-1. Definition. Proposal No. 8-235:
The definition of rigid metal conduit has been revised to
read, "Rigid Metal Conduit (RMC) is a threadable raceway
of circular cross section designed for the physical protection
and routing of conductors and cables and for use as an
equipment grounding conductor when installed with its integral
or associated coupling and appropriate fittings. RMC is
generally made of steel (ferrous) with protective coatings or
aluminum (nonferrous). Special use types are silicone bronze
and stainless steel."
346-17. Listing
Requirements. Proposal No. 8-253:
A new section under construction specifications has been
added to read, "Listing Requirements. Rigid Metal Conduit
(RMC), factory elbows and couplings, and associated fittings
shall be listed."
The addition of this new provision is
associated with the change made in the definition of RMC.
Wording in the former definition in 346-1 that specified that
RMC is a "...listed metal raceway..." was deleted.
This new section not only specifies that the raceway be
listed, but also other components used with it.
346-9(a). Threadless. Proposal No. 8-217:
A new sentence has been added to read, "Threadless
couplings and connectors shall not be used on threaded conduit
ends unless listed for the purpose." This new provision
will aid in the selection and use of threadless couplings on
threaded ends of conduit as they will be required to be
"listed for the purpose."
346-10 and Table 346-10. Minimum Radius of
Bends to Centerline of Conduit. Proposal No. 8-245:
The title of the table has been changed
from "Radius of Conduit Bends" to "Minimum
Radius of Bends to Centerline of Conduit." The second
sentence of the main paragraph has been changed to read,
"The radius of the curve of any field bend to the
centerline of the conduit shall not be less than indicated in
Table 346-10." This change shifts the focus of the radius
from the inner edge of a field bend to the centerline of the
conduit. It was pointed out that the measurement for conduit
bending equipment for use in the field is based on the conduit
centerline and not on the inner edge of the bend.
346-12(b)(3). Proposal No. 8-249:
The wording "stationary equipment or
fixtures" has been replaced with "fixed
equipment." This clarifies that rigid metal conduit can
be dropped to fixed equipment under certain conditions, but
that it is not permitted for that use with stationary
equipment or fixtures.
Article 347 - Rigid Nonmetallic Conduit
Table 347-9(A). Expansion Characteristics
of PVC Rigid Nonmetallic Conduit Coefficient of Thermal
Expansion... Proposal No. 8-267:
A new note has been added to this table to
read, "Note: Add 30EF to the estimated temperature range
when conduit is installed in direct sunlight to allow for
radiant heating." Rigid nonmetallic conduit exposed to
direct sunlight is affected by the heating caused by that
exposure and must be considered in the design for the
expansion and contraction of this type of conduit.
Table 347-9(B). Proposal No. 8-269:
A new note has been added to this table to
read, "Note: Add 30EF to the estimated temperature range
when conduit is installed in direct sunlight to allow for
radiant heating." This new wording is the same as that
added to Table 347-9(A).
Article 348 - Electrical Metallic Tubing
348-11. Bends - How Made. Proposal No.
8-292:
The section has been amended to read,
"The radius of the curve of any field bend to the
centerline of the conduit shall not be less than shown in
Table 346-10 for one-shot and full shoe benders." The
exception has been deleted. This point of measurement was
changed from "the inner edge of any field bend" to
"the centerline of the conduit." This change
includes specific reference to the types of benders intended
for use in field bends to be "one-shop and full shoe
benders."
Article 350 - Flexible Metal Conduit
350-14. Grounding. Proposal No. 8-323:
The title of this section was revised by
adding the words "and Bonding" to read
"Grounding and Bonding." The text has been revised
to read:
"Where used to connect equipment where
flexibility is required, an equipment grounding conductor
shall be installed.
"Where required or installed,
equipment grounding conductors shall be installed in
accordance with 250-134(b).
"Where required or installed,
equipment bonding jumpers shall be installed in accordance
with 250-102."
This action addresses the grounding and
bonding requirements of flexible metal conduit and clarifies
that the bonding jumpers are permitted to be installed either
inside or outside of the conduit.
Article 351 - Liquidtight Flexible Metal
Conduit and Liquidtight Flexible Nonmetallic Conduit
Article 351. Proposal No. 8-327:
The existing Article 351 will be divided
into two separate articles and renumbered accordingly. One
article will cover liquidtight flexible metal conduit and the
other article will cover liquidtight flexible nonmetallic
conduit. This action is part of the overall effort to arrange
raceway articles into a more user friendly format. The
renumbering of these and other articles will be done at the
end of this Code cycle.
Article 352 - Surface Metal Raceways and Surface
Nonmetallic Raceways
352-26. Combination Raceways. Proposal No.
8-374:
The wording "and the same relative position of
compartments shall be maintained throughout the premise"
at the end of the sentence has been deleted. Accessories that
permit a crossover of the different types of circuits while
maintaining the separation of the different systems are
available. With the use of these accessories that provide the
required separation, the deleted wording is not needed.
Article 362 - Metal Wireways and Nonmetallic Wireways
Article 362. Proposal No. 8-398:
Article has been divided into two separate
articles. Part A of Article 362 as revised will become a new
article entitled "Metal Wireways." Part B will
become a separate article entitled "Nonmetallic
Wireways" through action on Proposal 8-414. This action
is the result of the work done by the NEC Technical
Correlating Committee Task Group on Usability.
362-6. Deflected Insulated Conductors. Proposal 8-410:
The wording in this section has been amended and restructured
to include two subheadings. The title of the first subheading
is "(a) Insulated Conductors" and the second is
"(b) Metallic Wireways Used as Pullboxes." This
revision makes the section easier to read, is more specific in
the reference to the applicable rule in 373-6, and addresses
the use of wireways as pull boxes.
362-6 revise to read:
362 Part B. Nonmetallic Wireways. Proposal
No. 8-414:
Part B of existing Article 362 will be
designated as a new article entitled "Nonmetallic
Wireways." Action on this proposal and that taken on
Proposal No. 8-398 separate the two types of wireways into
articles that will fit into the standard formatting of article
structure for usability purposes.
Article 363 - Flat Cable Assemblies
363-3 Proposal No. 7-273:
The term "severe" has been
deleted from this section. This type of assembly should not be
subject to damage, much less to "severe" damage.
363-19. Identification. Proposal No. 7-281:
The term "natural" has been
deleted from the identification requirement for grounding
conductors in flat cable assemblies. Grounded conductors in
Type FC cable are to be either be white or gray. The term
"natural gray" is not defined and does not exist as
a specified color for wire insulation.
Article 370 - Outlet, Device, Pull and
Junction Boxes, Conduit Bodies and Fittings.
370-20. In Walls or Ceiling. Proposal No.
9-20:
This section has been revised to read,
"In walls or ceilings with a surface of concrete, tile,
gypsum, plaster or other noncombustible material, boxes shall
be installed so that the front edge of the box will not be set
back of the finished surface more than 6 mm (1/4 in.). In
walls and ceilings constructed or wood or other combustible
surface material, boxes shall be flush with the finished
surface or project therefrom."
This change provides a better understanding
of which wall covering materials are considered as combustible
and those that are considered by this section to be
noncombustible.
370-27. Outlet Boxes. Proposal No. 9-36:
A new subsection has been added to read,
"Maximum Fixture Weight. Outlet boxes or fittings
installed as required by Section 370-23 shall be permitted to
support luminaries weighing 23 kg (50 lb.) or less. A
luminarie that weighs more than 23 kg (50 lb.) shall be
supported independently of the outlet box unless the outlet
box is listed for the weight to be supported." This new
subsection is a modified form of the wording located in
410-16(a). Rules covering the use of outlet boxes for the
support of equipment, such as lighting fixtures, is more
appropriately located in Article 370.
370-27(a) Exception. Proposal No. 9-39:
This exception has been revised by deleting
the term "wall mounted," changing the fixture weight
from "6 lb (2.72 kg)" to "7kg (15 lb),"
and adding wording to cover plaster rings. It was concluded
that the boxes under consideration are capable of supporting
fixtures having greater weight than previously permitted.
Article 373 - Cabinets, Cutout Boxes, and Meter Socket
Enclosures
Table 373-6(b). Minimum Wire-Bending Space
at Terminals in Inches. Proposal No. 9-66:
A new column for compact stranded AA-8000
aluminum alloy conductors has been added.
The conductor sizes covered range from 12 AWG to 1000 kcmil.
The bending space for compact stranded aluminum conductors of
the AA-8000 series electrical grade aluminum alloy is
different for the equivalent wire size of other types of
conductors.
Article 380 -Switches
380-6(c). Connection of Switches. Proposal
No. 9-75:
The term "bolted pressure contact
switches" has been added to this provision covering the
requirement that blades of these types of switches be
de-energized when in the open position. The same term was also
added to the second sentence of the section to include bolted
pressure contacts in the requirement that the terminals
supplying the load are de-energized when the switch is in the
open position.
380-9(b). Grounding. Proposal No. 9-83:
The wording "and similar control
switches" has been added to 380-9(b). It will now read,
"(b) Grounding. Snap switches, including dimmer
switches and similar control switches, shall be effectively
grounded..." This change makes it clearer that devices,
such as fan control switches, should be included in the
grounding rules in this section.
380-14(e). Dimmer Switches. Proposal No.
9-88:
A new 380-14(e) has been added to read:
"(e) Dimmer Switches. General use dimmer switches
shall only be used to control permanently installed
incandescent lighting fixtures unless otherwise listed for
control of other loads, and installed accordingly." This
new subsection places a general limitation on the use of
dimmers to that of incandescent luminaire loads but recognizes
that dimmers designed and listed for other types of loads can
be used for those purposes.
380-15. Marking. Proposal No. 9-88a:
The existing wording in 380-15 has been
designated as "(a) Ratings" in this section
and a new subsection (b) has been added to read: "(b)
Off Indication. Where in the off position, a switching
device with a marked OFF position shall completely disconnect
all ungrounded conductors of the load it controls." This
new wording impacts these switching devices by requiring that
they truly disconnect power to a load when the device is in
the "OFF" position.
Article 384 - Switchboards and Panelboards
384-4. Circuit Directory. Proposal 9-94:
The Fine Print Note has been deleted and a
new section added to read: "384-4. Circuit Directory. All circuits and circuit modifications shall be legibly
identified as to purpose or use on a circuit directory located
on the face or inside of the panel door in the case of a
panelboard, and at each switch on a switchboard." This
change provides clearer instructions as to the identification
of circuits.
384-16(b). Power Panelboard Protection. Proposal No. 9-106:
A new sentence has been added to this
section to read: "The overcurrent protective device shall
be located within, or at any point on the supply side of the
panelboard." This new wording adds clarity as to the
permitted location of the overcurrent device protecting the
panelboard.
384-16(d). Continuous Load. Proposal No.
9-107:
The wording in this subsection has been
deleted. This action includes the deletion of the main rule
limiting the total load on any overcurrent device to 80
percent of its rating where the load is continuous as defined
by the Code. The exception to that rule was also
deleted. It was contended that rules in 210-19(a), 210-20(a),
and 215-3 cover this issue.
384-21. Grounded Conductor Terminations. Proposal No. 9-113:
A new section has been added to read:
"Grounded Conductor Terminations. Each grounded
conductor shall terminate within the panelboard in an
individual terminal that is not also used for another
conductor.
"Exception: Grounded conductors of
circuits with parallel conductors shall be permitted to
terminate in a single terminal if the terminal is identified
for connection of more than one conductor."
This new section brings a product standards
rule into the Code and will be helpful for users of the NEC to better understand the issue of terminating
grounded conductors in panelboard busbars.
384-34. Knife Switches. Proposal 9-114:
This section which contained a rule
requiring exposed blades of knife switches to be de-energized
when open and the associated fine print note have been
deleted. It was contended that this requirement is already
covered in 380-6(c).
IAEI Executive
Director and Editor-in-Chief for the IAEI
News, Phil Cox was formerly employed with the
National Electrical Manufacturers Association as a field
representative covering a 17-state area. He is a member
of NFPA NEC® Technical Correlating Committee. He served
on Code-Making Panel No. 6, representing IAEI during the
Code cycles for the 1984 and 1987 editions of the NEC.
He served as chairman of CMP-1, representing the
National Electrical Manufacturers Association during the
1996 Code cycle. He served as acting chairman of CMP-1,
representing IAEI for the 1999 cycle. He is a member of
NFPA Electrical Section; Board of Governors; UL
Electrical Council; ITS Technical Advisory Council; and
former member of The Chauncey Group International,
National Certification Program for Construction Code
Inspectors.
He also served as
secretary for the city of Little Rock Electrical
Examining Board, developing and administering
examinations for master, journeyman and specialty
electricians. During this time, he worked with members
of the Arkansas Chapter IAEI in conducting seminars on
the National Electrical Code for
the purpose of familiarizing electricians with the Code.
Cox participated as a
lead instructor in conducting IAEI-developed Code Change
Seminars. Phil is a past section president and past
member of the IAEI board of directors.
|