|
|
Sign In | Register Now Why Register? |
||
|
|
|||
|
|
|||
|
IAEI News>Issue Listing>September/October 2000>1+1=Independent Grounding for Patient Areas of Health Care Facilities
The purpose of the grounding portions of Article 517 of the National Electrical Code (NEC) is to reduce low voltage potential differences between electrically conductive surfaces that may be reached by a patient or care provider in the patient vicinity. Two independent means of grounding are required for the patient care areas and are connected in parallel. This limits the voltage and, thus, the electrical currents that the patient is exposed to and will reduce or eliminate the electrical shock hazard. The NEC defines these patient care areas:1
All branch circuits serving the patient care area must be installed in a metallic raceway system or cable assembly. A metallic raceway system used for equipment grounding must comply with the requirements of Section 250-1181. Type MC, AC & MI cable must have a metallic outer covering that is identified as acceptable for grounding. (See Figure 1) All grounding terminals of all receptacles and all non-current carrying electrically conductive surfaces of fixed electric equipment in the patient care area, operating at more than 100 volts, must be grounded using an insulated copper conductor. This grounding conductor must be sized per Section 250-1221, Table 250-122 and installed in the branch circuit metallic raceway or identified cable assembly. (See Figure 2) Metal faceplates can be grounded by means of a metal mounting screw(s) securing the faceplate to a grounded outlet box or grounded wiring device. Light fixtures more than 7½ ft above the floor and switches located outside of the patient vicinity shall not be required to be grounded by an insulated grounding conductor. Patient bed location receptacles must be listed as hospital grade and grounded to the reference grounding point using an insulated copper equipment grounding conductor sized per Section 250-1221, Table 250-122. A patient equipment grounding point (PEGP) is permitted in critical care areas and must be furnished with listed connectors. An equipment bonding jumper No. 10 or larger must be used to bond the PEGP to the grounding terminal of all grounding type receptacles. (See Figure 3) A grounded electrical system feeder that is used to feed a panelboard for critical care area branch circuits must have the metal feeder raceway or type MC or MI cable grounded at each termination or junction point as follows1:
Summary 1 NFPA 70 National Electrical Code 1999 Edition Gaylen D. Rogers is employed with DFCM, Utah. He graduated from the University of Utah in electrical engineering, holds a master electrician license and is a certified electrical inspector for the state of Utah. Rogers is certified with ICBO, as well as IAEI, where he has been active since 1971, and is an alternate member of Code-Making Panel 17.
|
| |||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
|||||||||||||||||||||||||||||||||||||||||||||||||||