|
| |
 |
| Photo
1 |
| Typical "Spider box" supplies GFCI protected
receptacles for use on construction sites. |
|
| Diagram
1 |
| GFCI protection required for 15, 20, and 30 ampere, 125-volt receptacles on construction sites. |
|
| Diagram 2 |
| Principles of operation of GFCI protective devices |
|
| Diagram
3 |
| Typical protective GFCI devices |
|
| Diagram 4 |
| GFCI tripping curves showing time and milliampere values |
| |
|
|
|

IAEI
News>Issue Listing>November/December 2000 >NEC & OSHA: Protecting Workers from Electrical Shock
| NEC & OSHA: Protecting Workers from Electrical Shock |
An exploration of both the NEC and OSHA's electrical protection requirements as it relates to GFCI protection for temporary wiring as required by Article 305 of the NEC and OSHA's 1926, Subpart K, Electrical Standards. |
|

Perhaps the greatest advancement in worker
safety over the past 30 years has been the development and
implementation of ground-fault circuit-interrupter (GFCI)
protection. Both the National Electrical Code (NEC) and
the Occupational Safety and Health Administration (OSHA) have
initiated requirements designed to afford a superior level of
protection for both employees and the general public who may
be exposed to the hazards of electricity. The purpose of this
article will be to explore this development as it relates to
GFCI protection for temporary wiring as required by Article
305 of the NEC and OSHA’s 1926, Subpart K, Electrical
Standards.
Background
Both the NEC and OSHA recognize that workers
performing construction, demolition and maintenance activities
are especially vulnerable to the hazards of electricity.
Frequently, workers have environmental and physical conditions
which directly impact their ability to work safely around the
hazards associated with the use of electrical tools and
equipment. Essentially, the NEC developed and OSHA
adopted a two-prong approach to affording protection to
workers. Until recently, (1996 NEC) Article 305 and
OSHA 1926.404(b) have both permitted either the use of the
Assured Equipment Grounding Conductor Program (AEGCP) or the
use of GFCI protection for all 125-volt, single-phase, 15- and
20-ampere receptacle outlets on construction sites. The
concept of the AEGCP is that frequent and regular inspection
and testing of all equipment grounding conductors, receptacles
and attachment plugs, will "assure" that the
continuity of the EGC is maintained and that a low-impedance
grounding path will protect workers sufficiently against the
hazards of electrical shock by facilitating the operation of
the overcurrent device. GFCI devices, on the other hand, sense
an unbalance or leakage current in the area of 4-6 mA and open
the circuit in a 1/40 of a second to provide protection
against electrocution.
The 1996 NEC
Two significant changes occurred in Section 305-6,
Ground-Fault Protection for Personnel, in the 1996 NEC.
First, the scope of the GFCI requirements was greatly expanded
by removing the limitation to construction sites only. Prior
to the 1996 NEC, the GFCI requirements for 15- and 20-
ampere, 125-volt receptacle outlets, only applied to personnel
on construction sites. The 1996 NEC removed this
limitation and expanded the scope of the provision to include
all "temporary wiring installations utilized to supply
temporary power to equipment used by personnel during
construction, remolding, maintenance, repair, or demolition of
buildings, structures, equipment or similar activities."
This was a dramatic expansion of the scope and resulted in a
significant advancement for worker safety.
The second significant change was the
restrictions placed on the use of the AEGCP. Prior to the 1996 NEC, either the GFCI or the AEGCP could be utilized to
meet the requirements of this section. In the 1996 NEC,
the use of the AEGCP was strictly limited to "other
receptacles not covered in (a)." This meant that, for
other than industrial establishments (see exception) all 15-
and 20-ampere, 125-volt, single-phase receptacle outlets had
to be provided with GFCI protection.
Interestingly, CMP-3 also clarified that
when providing GFCI protection, cord sets incorporating listed
GFCI protection for personnel are permissible.
Photo
1. Typical "Spider box" supplies GFCI protected
receptacles for use on construction sites.
Analysis
The changes in the 1996 NEC were a great step, a
leap, towards enhancing worker safety. Subsequent revisions
have continued to expand the scope of the protection to
include 30-ampere, 125-volt, single-phase receptacle outlets
and to clarify that where GFCI protection is required, such
protection is required, regardless if the receptacle exists or
is considered to be part of the permanent wiring of the
building. In other words, if personnel are performing any of
the covered activities, (construction, demolition,
maintenance, etc.), they must be provided some form of GFCI
protection, regardless if the outlet exists or is part of the
permanent wiring of the building.
Often this is accomplished by the use of
listed cord sets which incorporate the GFCI protection into
the cord set. Notice that the wording of Section 305-6(a)
currently permits "cord sets or devices incorporating
listed ground-fault circuit interrupter protection for
personnel identified for portable use." Two points
relevant to this provision. First, note that the cord set must
utilize listed GFCI protection, not that the cord set must be
listed. This sentence structure is intentionally different
from other NEC sections mandating similar requirements.
That is because OSHA does permit employers to construct their
own extension cord sets. There are several conditions that
must be met but the practice is acceptable. Requiring the cord
sets to be listed would severely limit this provision.
Secondly, the cord sets must utilize GFCI protection which is
identified for portable use. Such protection includes
"open neutral" protection which enhances personnel
safety where such devices are subject to the possibility of
losing a neutral connection. For this reason, it is not
permissible to utilize standard GFCI receptacles, intended for
permanent installation only, as part of a
"shop-made" cord set.
OSHA Construction
Standards
Since the early 1970’s, OSHA Construction Electrical
Standards have been driven by the NEC. Current
requirements parallel the 1984 edition of the NEC. In
fact, Section 1926. 404(a) Note, states, "If the
electrical installation is made in accordance with the National
Electrical Code ANSI/NFPA 70-1984, exclusive of Formal
Interpretations and Tentative Interim Amendments, it will be
deemed to be in compliance with 1926.403 through 1926.408,
except for 1926.404(b)(1) and 1926.405(a)(2)(ii)(E), (F), (G),
and (J)." Unfortunately, as we have just discussed,
significant changes in the NEC have occurred which are
not currently enforceable by OSHA. The restriction on the
AEGCP for example, does not exist within the OSHA regulations.
The addition of the 30-ampere, 125-volt receptacle outlet is
not included as well. The scope of application for GFCI
requirements for OSHA is still limited to construction sites
only.
Diagram
1, Diagram 2, Diagram
3, and Diagram 4
Summary
Needless to say, there exists great differences between
the NEC requirements and the OSHA regulations. From an
enforcement point of view and from a safety point of view this
is troublesome. Section 6(b) of the OSHA Act mandates steps
that must be taken before OSHA can promulgate a new rule.
Logistically, OSHA is simply not capable of keeping up with
the latest developments in the NEC.
This fact, however, ought not change
employer strategies for protecting personnel from electrical
shock. The use of GFCI protection provides a level of safety
superior to that of the AEGCP and it can be implemented in an
easier and more cost-efficient manner for the employer. OSHA
regulations are a minimum safety standard for protecting
workers. Particularly when it comes to GFCI requirements,
employers should follow the provisions of Article 305 and
strive to enhance personnel protection by adhering to the
stronger of the two standards.
Michael I. Callanan
serves on the National Joint Apprenticeship &
Training Committee. He is director of Safety, Codes
& Standards and is principal member of the National
Electrical Code Technical Correlating Committee.
Callanan also serves on NFPA 70E, NFPA 70B, and is
chairman, NFPA 79.
|
|
|