
IAEI
News>Issue Listing>July/August 2001 >The Electrical Inspector & Fire Alarm Systems
| The Electrical Inspector & Fire Alarm Systems |
A review on the proper type of location for various fire alarm system components that helps pinpoint potential problems and solutions. |
|

Sitting around the morning coffee table
waiting for shift change, a
group of us discussed the previous night’s calls and the
recurring
false alarms became the main topic. My captain made a
statement that has stuck with me ever since: "Fire
codes have been written with the blood of peoples lives!" These ten simple words hold a truism I hope becomes a part of
our daily thought processes.
It is incumbent upon all of us, whether
electrical, mechanical, or fire inspectors, to make every
inspection truly proactive. Inspections provide a valuable
service to the contractor, the building owner and the people
we serve.
Smoke detectors are designed and installed
to provide reliable early warning smoke detection systems for
the protection of life and property. 1999 NFPA 72, 2-3.1.1.
Heat detectors do not provide early warning and therefore are
not considered life safety. 1999 NFPA 72 has prescribed the
installation requirements for smoke and heat detectors.
Section 2-2 covers heat detector requirements and Section 2-3
covers smoke detectors. Proper smoke and heat detector
locations become paramount when fire safety control functions
are required.
This article will provide an awareness of
the proper type and location for various fire alarm system
components. The information will help you recognize problems
or potential problems and in some cases allow you to offer
solutions. The 1999 NFPA 701 and 1999 NFPA 722 are the sources
of information and should be consulted for definitive answers.
As with any codes or standards, local requirements and
amendments shall always prevail.
Definitions Used
In This Article
Listed below are some definitions of the vernacular of the
fire alarm systems to provide consistency throughout this
article.
Code – A code identifies the
type and when specific detection, protection, and
notification is required. This typically is based upon the
occupancy classification and the construction type.
Standard – A standard identifies
how a specific device or appliance shall be located within a
specific setting. Further categorizing would distinguish
between performance based and prescriptive based and is
beyond the scope of this article.
Initiating Devices – Smoke and
heat detectors, manual pull stations, duct detectors, water
flow switches and sprinkler valve supervisory devices.
Further categorizing would distinguish between alarm
initiating devices and supervisory initiating devices and is
beyond the scope of this article.
Notification Appliances – Horns,
Strobes, Horn/Strobes, Speaker, and Chimes. Speakers in any
combination are considered textual audible notification.
Shop Drawings – Shop drawings
are prepared by the specific trades and identify how the
entire system is put together. The shop drawings should
always contain product specification sheets, sometimes
called cut sheets. The shop drawings on the job site should
always be the approved set from the AHJ. Various codes and
standards delineate what is contained in the shop drawings.
Laying
the Foundation
The following is a review of the 1999 NFPA 72. The items
listed below are easily checked during an inspection and
corrected if needed.
1. Section 1-5.2.5.2: A smoke detector is
required over the fire alarm control panel and all remote
power supplies.
2. The fire alarm control panel requires
primary power from a dedicated branch circuit. The circuit
breaker and connection shall be mechanically protected. The
breaker shall be labeled "Fire Alarm Circuit
Control." Section 1-5.2.5.2
3. Section 1-5.2.5.3: The circuit breaker
shall have access limited to authorized personnel only. This
requirement allows the use of an approved circuit breaker
lock.
4. Section 1-5.5.1: The fire alarm
control panel shall be installed in a stable environment.
This includes a temperature range of 32°F to 120°F. A
humidity limit of 85 percent at 86°F. Always follow the
manufacturer's requirements.
5. Section 2-3.6.1.1: Smoke detectors
shall be installed within the following parameters:
Temperature between 32°F to 100°F.
Humidity limit of 93 percent.
Air velocity less that 300 ft/min.
6. Table A-2-3.6.1.2(a) lists various
types of contamination. These are important to consider when
determining locations for smoke detectors. These include but
not limited to showers, steam, cleaning fumes, exhaust
hoods, machining, oil mist, humidity, linen and bedding
handling, indoor fork lifts and the like. These always
should get a second look to help ensure proper detection.
7. Section 2-3.6.1.3. states,
"Detectors shall not be installed until after the
construction clean up of all trades is complete and final.
Shipping covers may be used and then left in place. It is
imperative that the AHJ knows when the covers were installed
and when they are removed.
8. Figure A-2-3.4.3.2. shows the proper
installation of smoke detectors under the computer
floor. Installing smoke detectors on the floor is not
permitted. The smoke detector is required to be installed in
the orientation for which it has been listed. Supporting the
back box with only one piece of conduit is not permitted.
9. Figure A-2-1.3.4(a) requires
termination of wire to maintain continuity for the
monitoring of integrity. Close attention of the termination
should always be checked. A simple test is to loosen the
terminal and lift only one wire. All other wires should
remain in place if the device is wired correctly. If the
wires are twisted together then more than one wire will come
off.
The following is a review of the 1999 NFPA
70, Section A of Article 760 is General Requirements and
Section C is Power Limited Fire Alarm. These are the two main
sections of Article 760. These items listed below are easily
checked during an inspection and corrected if needed.
1. Section 760-8: Fire alarm systems
require workman like manner.
2. Section 760-5: Fire alarm control
panels require access for service.
3. Table 760-61 indicates the type of
wire permitted for fire alarm systems. The substitutions are
also listed.
4. Section 760-52 requires mechanical
protection for fire alarm wire.
Article 300, Wiring Methods, and Article
250, Grounding, are referenced in Article 760.
That
Just Doesn’t Look Right!
The electrical inspector has the opportunity to examine the
initial installation of the fire alarm system: locations of
the back boxes, type of wire used, and how they are installed
require inspection. This is the time to question coverage,
environmental conditions, installation methods, location, and
type of detection.
The bulleted list below is only a brief
outline. Further details will be found in NFPA 72, chapter 2.
Smoke Detectors
• Smoke detectors cover a circular area
with a radius of 21'. This is based upon a manufacture listing
of 30 feet, a smooth, and flat ceiling
• May be mounted on the wall or ceiling
• Room temperature between 32°F to
100°F
• Room air velocity less that 300 ft/sec
• Room humidity less than 93 percent
Smoke detectors respond to a specific
concentration of smoke. Several factors affect how smoke may
concentrate and include such factors as: air movement or lack
of movement, stratification of smoke, ability for smoke to
bank down, heat source to produce hot or cold smoke, and
others.
Heat Detectors
• Heat detectors cover a circular area
with a radius of 35'. This is based upon a manufacture listing
of 50 feet, a smooth, flat ceiling less than 10' high. Ceiling
height, ceiling construction and slope of the ceiling are all
factors to be considered for the proper placement of heat
detectors. These design factors are beyond the scope of this
article. Always question something if you are not sure. You
are never too old to get free information.
Horn/Strobe and Strobe Only
• Wall mounted 80" to 96." Use
Table 4-4.4.1.1(a)
• Ceiling mounted permitted. Use Table
4-4.4.1.1(b)
• Sleeping rooms (hotel, motel, and
apartment). Use Table 4-4.4.3.2
110 cd strobe light – minimum of 24"
from the ceiling.
177 cd strobe light – within 24"
from the ceiling.
• A 15cd within 15" from the end of
a corridor. Use Table 4-4.4.2.1
Horn Only
• Wall mounted – minimum of 90"
from the floor and 6" from the ceiling. 4-3.5.1
May I Please See
the Fire Alarm System Shop Drawings!
Rough Wire Inspection
A rough wire inspection is a perfect
opportunity to examine the framework of the fire alarm system.
Compare the shop drawing design to the actual field locations.
You will be surprised at the number of discrepancies. There is
nothing wrong with changes as long as they have been reviewed
through the proper channels. Always record any concern you may
have, even if it is small. Several small items should raise a
flag!
Some questions to ask: Are the locations
proper? What type of wire is used? Are the back boxes properly
secured and does the wire have strain relief? Are the smoke
detectors mounted on the wall and ceiling? Are there any air
diffusers within three feet of the smoke or heat detector? Are
the ceilings flat, peaked or a shed style? Is the ceiling
smooth, joist, or beam construction? How will the
environmental conditions affect the detection?
Photo
1.
Photo 2.
Photo 3.
Photo 4.
Photo 5.
Final
Inspection
All of the wires, back boxes and potential mistakes are
now concealed in the floors, walls and ceiling. Similar
questions need to be asked during the final inspection. Have
any devices or appliances been added or deleted that were not
on the "approved" shop drawings? Have any devices or
appliances been installed without back boxes or with the wrong
wire? The wrong wire can include type and size. The shop
drawings will indicate this specific information. Are devices
and appliances that are listed for indoor use only installed
outside or installed in a humid/wet room? Are wall mounted
appliances installed on the ceiling?
Compare all notes that have been made
during the rough wire and final inspection. This will serve as
a reminder to check items you identified.
A lot of these questions may be difficult
for one to understand and beyond the scope of an inspection.
Asking another inspector for a second opinion or "set of
eyes" may broaden the knowledge base, giving one the
opportunity to provide more service to the contractor,
building owner and the general public.
Working
Together for the Same Purpose
I would like to end this article with a brief reminder about
our purpose for inspections, why we inspect and whose lives
are at risk.
One of the best training sessions I have
had was a ride-along with a city electrical inspector. We can
read and study codes and standards all day long but to get
hands-on training from these craftsmen is second to none. I
cannot encourage you enough to spend time in the field with
inspectors of other related trades. Joining your local chapter
of the IAEI will provide you a tremendous opportunity to
discuss field problems.
A new tenant was moving in and wanted to
remodel. The fire alarm contractor suggested that the owner
retain the existing fire alarm system and simply add
components where required. Unfortunately, for the owner, this
meant using equipment and wire of unknown condition. There was
no documentation of any testing and inspection of the fire
alarm system. The wires were pulled down during demolition and
therefore became severely nicked, crimped and in some places
bare copper conductors exposed. The fire alarm panel was laid
on the floor for safe keeping (see photo
6).
It was the electrical inspector who forced
the issue of removing all existing fire alarm wire. The fire
alarm contractor installed new equipment, including new wire.
The symbiotic relationship between NFPA 70 and NFPA 72 can
only lead to a similar relationship between inspection
disciplines.
Photo
7.
Photo 8.
Our Role as an
Inspector
As the AHJ, we are ultimately providing life safety to the
citizens we serve. The Life Safety Triangle graphically
represents our relationship to the building owner, the fire
alarm contractor and the citizens we serve. This is a check
and balance of the fire codes, standards and their respective
intents (see photo
9).
AHJ – To enforce the various fire
codes and standards that have been tried, tested and proven.
To provide an independent, knowledgeable, third party
verification that the various fire codes, standards and
respective intents have been met.
Fire Alarm Contractor – To provide
the building owner with the fire alarm system, defined by the
code and standard, that will help ensure the life safety of
the building occupants.
Building Owner – To provide for the
life safety of the building occupants. The building owner
relies on the AHJ to help ensure that the fire alarm
contractor has designed, installed and is properly testing the
fire alarms system.
Electrical Contractor Sentenced to 5-Year
Jail Term for Fatal Fire.4
In what has been described as the first
case of its kind in the nation, a 49-year-old East Haven,
Connecticut, electrician has been convicted of manslaughter
and sentenced to five years probation after his prison term.
According to a report in The
Providence Sunday Journal, a jury convicted Richard E.
Salz of second-degree manslaughter in the death of Burton
Gorman III, 12, who died of smoke inhalation during a fire
at his grandparent’s home in East Haven. The fire was
linked to a baseboard-heating unit Salz has installed in the
basement. Testimony showed that Salz had committed numerous electrical
code violations, ignored manufacturers’ instructions for
installation, and failed to get a permit for the job.
The prosecutor in the case said that Salz
did not merely "make a mistake," but that he was
guilty of "flagrant, reprehensible, egregious
work," according to the account.
According to newspaper reports, national
trade organizations and a publication that follows the
electrical industry said the case marks the first time an
electrician has been held criminally liable for a death
arising from work performed by the electrician.
As indicated earlier, fire codes have been
written with the blood of peoples lives. Let us use the pen of
pro activity and the ink of sound decisions as we enforce the
codes and standards that effect you and me.
1. National Electrical
Code, 1999 Edition, National Fire Protection Association,
One Batterymarch Park, Quincy, Massachusetts 02269.
2. National Fire Alarm
Code, 1999 Edition, National Fire Protection Association, One
Batterymarch Park, Quincy, Massachusetts 02269.
3. "News &
People," NFPA Journal, National Fire Protection
Association, 1 Batterymarch Park, Quincy, Massachusetts,
02269, March/April 1991, Volume 85/Number 2, page 22. (Bold
and Italics added for emphasis)
Mark Campbell, CET is the vice
president of engineering for Global Fire and Safety, an
installation design and consulting fire alarm company.
He has been involved with training, installation, plan
review, and third party consulting on fire alarm codes
and standards for over 17 years. He has worked in both
the private and public sector including 11 years with
the West Metro Fire Rescue.
|