|
|
Sign In | Register Now Why Register? |
||
|
|
|||
|
|
|||
|
IAEI News>Issue Listing>September/October 2001>Overcurrent Protection for Conductors
Requirements for overcurrent protection for conductors are found in Article 240, Overcurrent Protection, which is found in chapter two, Wiring and Protection, of the NEC. Electrical conductors are required to be protected against overcurrent in accordance with their ampacity ratings that are specified in Section 310-15. Chapter three covers wiring methods, and the conductors installed in conjunction with those wiring methods must follow the applicable requirements of Article 310, Conductors for General Wiring. Conductor
Ampacities An electrical conductor has two ampacity ratings: a long-time rating and a short-time rating. The long-time ratings for electrical conductors for general wiring are specified in the tables in Article 310. A conductor short-time rating is another way of referring to a conductor’s withstand rating. The short time ratings for conductors are not given in the NEC, but should be given consideration as part of electrical design. Section 110-10 requires OCP devices to be selected and coordinated to clear faults without extensive damage. See also 310-10. An insulated conductor has a five-second withstand rating of approximately 1 ampere for every 42.25 circular mil area of conductor. For more detailed information on the short circuit withstand capabilities of conductors refer to chapter 11 of IAEI’s Soares Book on Grounding. This article will focus on protection of conductors in accordance with their long-time ampacity ratings. These are the ampacities specified in the tables in Article 310.1 These ampacities are the values of current that the conductor can carry without causing damage or degradation of the conductor. Conductors that are not provided with properly sized overcurrent protective devices are subject to over heating and insulation failures which ultimately lead to ground fault and short circuits in the wiring system. The Code on
Overcurrent Protection of Conductors A look at Table 310-16 and the title of the table reveals that the ampacity values given in the table are based on two conditions. First, the ambient temperature the conductors are installed in is based on 86°F (30°C) and not more than three current-carrying conductors are installed in the same raceway, cable, or earth. If either of these conditions in the title of Table 310-16 varies, some adjustment based on the conditions of use will have to be made. It is important to properly protect the conductor at the adjusted ampacity if correction factors have to be applied. Section 310-15(b)(2) requires an ampacity correction factor when the number of current-carrying conductors in a raceway or cable exceeds three or where single conductors or multiconductor cables are stacked or bundled together without maintaining spacing in distances longer than 610 mm (24 in.). The adjustment factor percentages are given in Table 310-15(b)(2)(a). Neutrals are current-carrying conductors. The amount of current a neutral carries is based on the unbalanced return current of the ungrounded conductors of the common multiwire branch circuit. Neutrals must be counted as current-carrying conductors if either conditions of 310-15(b)(4)(b) or (c) are applicable to the circuit. Many neutral conductors of individual circuits as well as multiwire branch circuits these days are often counted as current-carrying because of the large amounts of nonlinear loads (see sidebar) containing harmonic currents imposed on the return neutral of the circuit. Electronic equipment, electronic/electric-discharge lighting, adjustable-speed drive systems, and similar equipment are examples of the types of equipment that could be nonlinear loads. So several factors come into play when determining a final conductor ampacity for any given electrical circuit, and each must be considered and factored into the protection of the conductor (see photo 2). Next Higher Rated
Overcurrent Device Where the overcurrent protective device for the conductor exceeds 800 amperes, the ampacity of the conductors is required to be equal to or greater than the rating of the overcurrent device as defined in Section 240-6. The main reason for the limitation on devices rated at over 800 amperes is simply that the standard rated devices over 800 amperes start increasing in increments greater than 100 ampere increments. In fact, at 3000 amperes the increments for standard rated devices start increasing by 1000 amperes each up to 6000 amperes. Two things are very important when working Section 240-3 with Section 240-6. Make sure that (1) the conductor has enough ampacity for the load to be served, and (2) the next standard size device still properly protects the conductor after adjustment factors have been applied to it (see photo 3). Location of the
Overcurrent Device in the Circuit This requirement in the Code works well for conductors that originate from a panelboard or a switchboard where the overcurrent protection is an integral part of the device that is directly connected to the bus of the equipment and then properly fused (see photo 4). Tap Conductors The 1999 NEC made two clarifications relative to tap conductors that work to clarify any gray areas or confusion that may have been previously associated with tap conductors. The first revision to the Code addressing tap conductors shows up in Section 240-3(e). Here the term "tap conductor" is defined as "a conductor, other than a service conductor that has overcurrent protection ahead of its point of supply, that exceeds the value permitted for similar conductors that are protected as described elsewhere in" Section 240-3. Section 240-3(e) permits tap conductors to be protected against overcurrent in accordance with Sections 210-19(d), 240-21, 364-11, 364-12, and 430-53(d). The second and very important clarification that was made in the 1999 NEC was that it is not permitted to tap a conductor that is already functioning as a tap conductor. This is commonly referred to as "tapping a tap." The Code never has permitted tapping a tap conductor; it was just one of those gray areas that needed clarification. The clarification was made in Section 240-21. Here, the last sentence of this section states: "No conductor supplied under the provisions of (a) through (g) shall supply another conductor under those provisions, except through an overcurrent protective device meeting the requirements of Section 240-3."3 This revision did two things: it clarified that tapping a tap is not permitted, and it also clarified that service conductors do not fall under the requirements for tap conductors, just feeders and branch-circuit conductors. Service-entrance conductors fall under the requirements of Part G of Article 230. It should be understood that when a tap conductor is permitted by the Code, it allows the conductor to be connected to the source, either a feeder or a transformer or other source, and installed without any overcurrent protection for any of the lengths specified in Section 240-21 based on which tap rule is being applied. The Code recognizes the need for this length of unprotected conductor and has specific rules in place that provide equal and effective means of protecting the sacrificed conductor. Most of the tap rules in Section 240-21 require that the tap conductors terminate in a single overcurrent device or set of fuses that will limit the load to the ampacity of the tap conductors. Other requirements for tap conductors may include a length limitation, protection from physical damage, and sizing requirements. Each specific tap rule found in Section 240-21 must be applied specifically to the conditions of use. Remember that the Code is allowing the sacrifice and installation of unprotected conductors for a given length. All of the requirements in each of the tap rules must be followed based on the particular tap conductor requirements. Tap rules will be covered in detail in upcoming issues of the IAEI News (see figure 2). Overcurrent
Protection of Equipment For motors and air-conditioning equipment, the overcurrent protection requirements are specified in those particular articles. Overcurrent protection for equipment will be covered in another article in coming issues of the News. Summary When applying any of the tap rules in Section 240-21 for tap conductors, be sure that all conditions of the tap rule have been complied with upon completion of the installation or inspection. Conductors are required to be protected in accordance with their allowable ampacities and equipment is also required to be protected against overcurrent. Overcurrent protection for switchboards and panelboards is specified in Section 384-16, and for transformers, see Sections 450-3(a) and (b) and Tables 450-3(a) and (b). There are many other types of equipment, such as motors and HVAC equipment, that have specific requirements for overcurrent protection covered by the rules in the NEC. It is important to work these Code sections in harmony with one another to achieve all of the minimum required overcurrent protection anticipated by following the rules in the Code. Various local jurisdictions may amend or supplement the National Electrical Code. Always consult the local authority having jurisdiction if there are doubts or questions regarding the minimum electrical code requirements in that area. 1 Article 310, NFPA 70, National Electrical Code, 1999 Edition, (Quincy, MA: National Fire Protection Association, Inc.), p. 70-116-140. 2 Article 100, NFPA 70, National Electrical Code, 1999 Edition, (Quincy, MA: National Fire Protection Association, Inc.), p. 70-23. 3 240-3, NFPA 70, National Electrical Code, 1999 Edition (Quincy, MA: National Fire Protection Association, Inc.), p. 70-71. Michael J. Johnston is IAEI’s director of education, technical editor and an IAEI principal member on CMP-5. Johnston was formerly employed as an electrical field inspections supervisor for the city of Phoenix, Arizona. He is a member of the IBEW. Additionally, he holds all IAEI certifications. He also holds ICC Electrical Inspections Certification. He is a member of the UL Electrical Council.
|
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home
| Join | Advertising | Seminars | Contact
Us | Privacy
Statement | Legal
Notices |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||