|
| |
 |
| Photo
1 |
| Armor cutting tool |
|
| Photo
2 |
| MC cable pulled over sheave wheel |
|
| Photo 3 |
| Pulling MC cable through floor |
|
| Photo
4 |
| Horizontal support on trapeze |
|
| Photo 5 |
| Vertical MC cable support |
|
| Photo 6 |
| Interlocked armor MC cable bends not less than seven times the cable diameter |
|
| Photo
7 |
| MC cable fitting |
|
| Photo 8 |
| Parallel runs of jacketed MC cable entering gear |
|
| Table
1 |
|
| Table
2 |
|
| Photo
9 |
| Supporting MC cable every six feet |
|
| Photo
10 |
| Paying off large size MC cable |
|
|
|

IAEI
News>Issue Listing>September/October 2001>MC Cable Installations
The definitions in Article 334 identifies Type MC cable as a factory assembly of one or more insulated circuit conductors enclosed in an armor of interlocking metal tape, or smooth or corrugated metallic sheath. |
|

Type Metal Clad Cable (MC) is being
installed in virtually every type of building under
construction today including stadiums, schools, multi-family
housing, hotels, commercial retail and office, industrial
plants and warehouses along with many other facilities. This
article addresses the interlocked armor Type MC cable with
conductors No. 8 CU and No. 6 AL and larger for 600 volt
installations. Section 334-3 of the National Electrical
Code (NEC) (ANSI/NFPA 70 Standard) identifies uses
permitted to include services, feeders, branch circuits, wet
locations, and certain hazardous locations. Let’s review the
installation and inspection aspects of Type MC cable for
feeders and services.
MC cable is permitted in sizes 18 AWG
through 2000 kcmil for copper, 12 AWG through 2000 kcmil
aluminum, or copper-clad aluminum, and employs thermoset or
thermoplastic insulated conductors. Installation of MC cable
should be in accordance with Article 334 of NEC. The
definition in Article 334 identifies Type MC cable as a
factory assembly of one or more insulated circuit conductors
enclosed in an armor of interlocking metal tape, or smooth or
corrugated metallic sheath. The equipment grounding conductor
required within a cable with interlocked metal tape sheath may
be insulated or bare and may be sectioned. When sectioned, all
the sections must be identical. Any additional grounding
conductors are required to have green insulation. The sheath
of the smooth or corrugated tube Type MC cable or a
combination of the sheath and a supplemental bare or unstriped
green insulated conductor is suitable for use as the required
equipment grounding conductor. The required equipment
grounding conductor in conjunction with the cable armor and
connector (fitting) serve to satisfy the rule for a
low-impedance fault-return path to clear the overcurrent
protection device due to a ground fault.
Cable Preparation
Prior to pulling the MC cable, the installer prepares
the end by stripping the armor back to expose the conductor.
One method of stripping the armor is to cut a ring around the
cable with an armored cable cutter being careful to not cut
deep enough to damage the insulation on the conductors (see photo
1). Another method is to cut two adjacent ribs of the
armor utilizing a rotary cutter and slide the armor off the
conductors. Slide a basket grip over the conductor assembly
and then tape the basket, conductors and armor together. The
pulling force is to be applied to the conductors and not the
armor. The installer prepares the route of the cable pull by
placing sheave wheels or pulleys at adequate distances to pull
the cable without damage (see photo
2). Short distance pulls may not require wheels or pulleys
but only smooth surface with which to pull the cable over.
Pulling MC cable over hard edges such as angle iron can damage
the armor. UL 1569 Metal-Clad Cable testing requirements
include a tension test of the armor where a 150 lb. weight is
attached to the armor for five minutes. The armor must not
separate enough to expose the cable interior. The route of the
pull may include many turns, vertical and horizontal distances
but always pulls the cable by the conductors and not the armor
(see photo 3).
Cable Support
Section 334-10(a) of the NEC requires the cable
to be supported and secured at intervals not exceeding 6-ft.
(1.83 m). The supports may include strut, trapeze, and rack or
cable tray (see photo
4). Generally, the same support systems utilized for metal
conduit are used for MC cable except at distances of 6 ft
instead of 10 ft as required for conduit installations. The MC
cable can be secured by an assortment of clamps used for
conduit (see photo 5).
Section 334-10(b) Unsupported Cables states, "Type MC
cable shall not be required to be supported and secured where
the cable is fished, between access points, where concealed in
finished buildings or structures and supporting is
impracticable." An example is fishing MC cable down the
inside of an existing wall and supporting where accessible.
Bends in MC Cable
MC cable has no restrictions on the number of bends.
The bending requirement for interlocked armor Type MC cable is
"seven times the external diameter of the metallic
sheath" as stated in Section 334-11(b) of the NEC.
If you have a two-inch diameter MC cable the radius of the
curve of the inner edge of the bend shall not be less than 14
inches (see photo 6).
Terminating the
Conductors
Once the MC cable is supported and secured, the
installer will prepare to terminate the conductors. An
adequate length MC cable armor should be removed as described
earlier, again making sure not to damage the insulation on the
conductors, to terminate the conductors. Section 334-12
requires fittings used for connecting Type MC cable to boxes,
cabinets, or other equipment shall be listed and identified
for such use (see photo
7). The primary function of the fitting is to provide
mechanical connection between the cable and the enclosure and
ensure that the armor is properly grounded. There should be no
sharp edges in the fitting or on the armor which could damage
the insulation on the conductors. The installer should square
the end of the armor to provide a flush fit with the end stop
of the fitting. Selecting the correct size fitting requires
the installer to know the dimensions of the MC cable conductor
assembly and the armor diameter and the fitting dimensions of
the throat opening for the conductors and the clamping range
for securing the MC cable armor in the fitting. MC cable has a
polyester or paper wrap around the conductor assembly. The
fittings listed for MC cable by design may not require an
insulating bushing or may have a bushing included in the
fitting. The installer should note the instructions with the
fitting to determine if a bushing is included with the
fitting. The fitting manufacturer may have listed the fitting
as usable with Type AC or Type MC cable and thus a bushing is
included with the fitting. The bushing in this case may not be
required but the installer should verify with the fitting
manufacturer if the fitting was listed with or without the
bushing for Type MC cable (photo
7).
Parallel Runs
Section 334-23 states, "Type MC cable shall
provide an adequate path for equipment grounding as required
by Article 250." MC cable comes with an insulated or bare
equipment ground sized provide an adequate fault-current path
to protect the conductors in that individual cable. The
standard equipment ground supplied for the particular MC cable
probably is not sized for multiple runs of cable installed in
parallel. In photo 8,
ten sets of conductors are required to provide the ampacity
for the five circuits. Section 250-122(f) addresses the
requirement for properly sizing the equipment ground conductor
in each cable run in a parallel. Table 250-122 lists the
minimum equipment ground size for the overcurrent device
rating. Several years ago, manufacturers started supplying
four conductor 750 kcmil aluminum plus equipment ground with a
3/0 AWG aluminum equipment ground as standard stock material
instead of the previously supplied 1/0 AWG aluminum equipment
ground conductor. The 3/0 AWG aluminum equipment ground
enabled the installer to purchase stock 750 kcmil aluminum MC
cable and install two standard cables to supply 800 amp
equipment. Manufacturers of MC cable will provide cables with
larger equipment ground conductors when requested and at least
one provides stock sizes covering a range of overcurrent
devices (see table
1).
Vertical Runs
For long vertical runs, conductors must be supported to
prevent them from being pulled out of their connections by the
force of gravity. The conductor insulation must not be subject
to damage at bends. Cables installed vertically must not
exceed the requirements of Table 300-19(a) even though
supported every 6 feet without relieving the gravity and
weight of conductors (see table
2). Support is required to prevent the weight of the cable
from damaging conductor insulation and to prevent the
conductors from being pulled out of equipment terminals.
Section 300-19 states, "One cable support shall be
provided at the top of the vertical raceway or as close to the
top as practical." One method of supporting and securing
multi-conductor armored cables vertically is to install cables
with 90-degree offsets with a minimum horizontal distance of
two cable diameters. Remember interlocked armor Type MC cable
minimum bending radius is seven times the cable diameter.
Another method is to terminate the conductors such as in a
junction box and start a new section of cable to continue
vertically. Note the difference in distances allowed for
copper conductors and aluminum conductors, which reaffirms
that the supporting requirement is based on weight. In UL
1569, Type MC cable must meet the requirements for tightness
of armor on conductors. Cables containing No. 4 AWG or larger
conductors must not pull out of a ten foot sample cable
suspended vertically for one minute with a 30 lb. weight
attached to the conductor more than one-half inch (see photo
9).
As an inspector, sometimes it is very
difficult to identify the conductor type and size after
installation. With conduit and conductor installations you
must look for cut off pieces of conductor or conductor
remaining on reels as a source of information. The same
techniques are used with MC cable. MC cable information such
as cable and conductor type, size and voltage is shown either
on the marker tape included under the armor or on the
conductors.
Section 334-13 identifies ampacity of MC
cable to be in accordance with Section 310-15 or 310-60.
Generally the values in Table 310-16 will be applied to MC
cable if there are no more than 3 current carrying conductors
per cable. Derating is required when there are more than three
current carrying conductors per cable. Correction factors
apply for ambient temperature above 30ºC (86ºF).
The installation and inspection of
electrical components within an electrical system are critical
to the performance of the system. As inspectors witnessing
installations of Metal-Clad cable, note how the cables are
handled, pulling setup, support methods, armor stripping
techniques, locations installed, proper bending and correct
listed MC cable fitting. This article refers to 1999 NEC but there may be local amendments so always check with the
local authority having jurisdiction (see photo
10).
Larry Watkins is a
senior engineer for Distributor Products at Alcan Cable.
He has been involved in the wire and cable industry from
manufacturing to technical support and standards
committee work. He has been an associate member of IAEI
since 1993.
|
|
|