
IAEI
News>Issue Listing>May/June 2002 >Molded-Case Circuit Breaker—Individual Pole Interrupting Capability
| Molded-Case Circuit Breaker—Individual Pole Interrupting Capability |
The fine print note to NEC 240.84 has aroused considerable controversy about whether such a statement will be helpful to users. |
|

The 2002 National Electrical Code (NEC) has
an added notation that can be confusing. The notion is a fine
print note (FPN) to 240.85 of the NEC that reads,
"Proper application of molded-case circuit breakers on
3-phase systems, other than solidly grounded WYE, particularly
on corner-grounded delta systems, considers the individual
pole interrupting capability." A FPN is non-mandatory
information according to 90.5 of the NEC. This
document will explore its meaning.
There was considerable controversy among
the NEC panel about whether such a statement will be
helpful to users. While there is no reason for special
attention for the generally applied distribution systems,
there can be reason for care in applying MCCBs in the
corner-grounded delta system.
MCCBs Provide Good
Protection
MCCBs have been safely applied in industrial systems with an
excellent record of performance since electricity became a
common source of energy for industry. UL 489, the Standard
for Safety for Molded-Case Circuit Breakers, Molded-Case
Switches and Circuit Breaker Enclosures was developed and
maintained to address the variety of systems in which MCCBs
may be used. It has always included individual pole
short-circuit tests, specifically to address the industrial
systems. These tests are applied rigorously in certification
of the products and annually throughout their production life.
The FPN is not an indication that installed systems should be
re-evaluated.
As we look around the world, we do not find
any other standard for MCCBs that addresses individual pole
short-circuit testing as comprehensively as does UL 489 and
its North American counterparts. IEC 60898 covering household
circuit breakers has recently added a requirement to test
individual poles at a current level of 500 amperes. IEC
60947-2 covering commercial and industrial circuit breakers
does not require any individual pole test on a general
application circuit breaker. However, Appendix H covering
special MCCBs for IT systems requires an individual pole test
at 1.2 times the instantaneous tripping current. Also,
Appendix C covering phased-earth systems (corner-grounded
systems) requires a test at 25 percent of the interrupting
rating.
The FPN does not address single-phase
systems because testing in all cases rigorously covers these
systems. Additionally, the FPN does not apply to 3-phase
systems that are used in residential and commercial
applications, because these systems are rigorously covered by
testing. These covered systems include the center-point
grounded 120/240 V, the 208Y/120 V and 480Y/277 V systems
among others. In fact, testing comprehensively covers all of
the systems identified in NEC 250.20(B).
Three Representative
Systems
The three systems that best illustrate the range of
all conditions are shown in figures
1, 2 and 3.
They are the solidly-grounded WYE, the corner-grounded delta
and the impedance-grounded WYE systems, respectively. Consider
how a short circuit can occur that would involve an individual
pole interruption and would not involve any other pole. If
another pole is involved, it is sharing the energy of
interruption so that a single-pole interruption is not
involved. When one pole is involved alone, the question is
whether the pole has been tested with the combination of both
voltage and current that it will see under a fault condition.
Solidly-grounded WYE
For the solidly-grounded WYE system, either a L-N
or a L-G fault would be detected and interrupted by a single
pole. The L-N and L-G voltages are both phase voltages as
opposed to being a L-L voltage. For a 480 V L-L system, the
phase voltage is 277 V. For a 208 V system, the phase voltage
is 120 V. The individual poles of a 3-phase MCCB are
effectively tested at the full current value of the
interrupting rating and at phase voltage when they interrupt
the 3-phase short circuit in the high available fault test of
UL 489. This combination of parameters occurs for the first
pole to clear. Without exception, MCCBs used in these systems
are fully capable of interrupting any short-circuit condition
up to the value of the interrupting rating.
Figure
1
Corner-grounded Delta
Now look at the corner-grounded delta system. A L-G
fault would be detected and interrupted by the single pole of
a MCCB. However, in this case the voltage is full L-L voltage.
It is 480 V in a 480 V system or 208 V in a 208 V system. This
voltage exceeds the phase voltage seen by the individual pole
in the 3-phase test at the interrupting rating. In UL 489
testing, there is a single pole test at full L-L voltage.
While it is at the highest voltage rating of the MCCB, it is
at a limited test current that may be below the current that
could flow in a L-G fault on this system. Two-pole MCCBs
specifically intended for use in these systems are marked
"1F-3F" as indicated in NEC 240-85. In both
cases, 2-pole or 3-pole, it would be well for the engineer
designing a corner- grounded system to verify that the tested
current is not lower than the current that can flow in a fault
or to select a MCCB rated for application on the
corner-grounded system.
Figure
2
Impedance-grounded
WYE
Next look at the impedance-grounded WYE system. A
L-N fault would be covered by test, the same as it is for the
solidly-grounded WYE system. With respect to a L-G fault, the
impedance would limit such a fault to a very low level of
several amperes. Therefore, a MCCB is well rated and tested to
interrupt a fault seen by an individual pole. However, if
multiple, simultaneous faults are considered, there is a
condition that may deserve attention. A L-G fault on one phase
on the load side of the MCCB plus a simultaneous L-G fault on
a different phase on the supply side of the MCCB would result
in the condition shown in figure 4. In this case, full L-L
voltage appears across the pole. The probability of such a
condition becoming a problem for interruption by the MCCB is
very low considering:
• Two simultaneous faults must occur.
• The impedance of L-G faults is such
that the current is limited.
• Arcing is likely at one or both fault
points, which would considerably limit short-circuit
current.
• Arcing would most likely propagate to
other phases due to ionized gases such that more than one
pole would be involved.
• Actual fault path will involve
another pole of an overcurrent protective device in many
cases.
Note: Circuit breakers can react very
rapidly to these types of arcing faults to clear the circuit.
As the arcing fault current is increasing through one pole,
the fault will most likely propagate to the other phases due
to ionized gases. At the same time as the pole under fault
trips, it is causing all poles of the circuit breaker to open
simultaneously due to common trip. This circuit breaker
feature will invariably allow the circuit breaker to clear the
fault successfully while limiting the arcing current to levels
well below the circuit breaker’s interrupting capability.
Figure
3
In addition to these points, NEC 250.36 limits the application of impedance-grounded systems
and requires ground detection systems to support early repair
of the first fault thereby reducing the potential for
occurrence of a second simultaneous fault. MCCBs can be safely
applied in these systems. Depending on the specific protection
needs and the anticipated maintenance of the facility, the
design engineer may wish to verify the single pole test values
against the system. Here, the straight voltage rating
expressed as 600, 480 or 240 V should be used. The slash
voltage ratings such as 600Y/346 and 480Y/277 are not intended
for impedance-grounded systems.
Systems such as the impedance-grounded WYE
system are utilized primarily in the process industries
specifically to avoid having manufacturing processes
interrupted by the occurrence of a single ground fault. To
gain the value of the system, facilities using them must
detect and repair any ground fault within a short time of its
occurrence. The occurrence of a second ground fault anywhere
in the system on a different phase will cause overcurrent
devices to open and result in an outage.
Figure
4
The three systems addressed above represent
all but a small percentage of installations. In addition is
the ungrounded delta system, the analysis of which is the same
as for the impedance-grounded WYE system from the MCCB
standpoint. There is also the center-point grounded delta
system used in residential and commercial applications, which
is comprehensively covered by testing.
Apply MCCBs with
Confidence
Molded-case circuit breakers are rigorously tested
overcurrent protective devices that can be applied with
confidence for protection of residential, commercial and
industrial systems. System designers applying MCCBs in
industrial systems should be aware of short-circuit conditions
related to single pole capabilities on corner-grounded delta
systems. Where impedance-grounded systems are used, system
designers must comply with NEC 250.36. Here, experience
has shown that the standard circuit breaker with the straight
voltage rating is suitable, especially when the first fault to
ground is corrected rapidly. The FPN does not have to be
confusing.
Molded-case members of National
Electrical Manufacturers Association.
|