
IAEI
News>Issue Listing>May/June 2002 >Other Code—Math Behind Extreme Wind Loading
Other Code
Math Behind Extreme Wind Loading |
In the last IAEI News (March/April 2002), I shared with you the details of the new extreme wind loading requirements of the 2002 National Electrical Safety Code (NESC). For structures sixty feet tall and shorter, the extreme wind loading only applies to the structure. For structures taller than sixty feet, the extreme wind loading applies to the structure and all the supported facilities. To understand the impact of the 2002 revision, lets crank through an example calculation. |
|

In the last IAEI News (March/April
2002), I shared with you the details of the new extreme wind
loading requirements of the 2002 National Electrical Safety
Code (NESC). For structures sixty feet tall and
shorter, the extreme wind loading only applies to the
structure. For structures taller than sixty feet, the extreme
wind loading applies to the structure and all the supported
facilities. To understand the impact of the 2002 revision,
lets crank through an example calculation.
Consider the following example shown in the
photograph:

Structures: 80-foot southern yellow
pine poles set 10 feet in the ground
All spans are 200'.
Supported Facilities:
1-7 No. 5 AW static wire at 70', conductor
diameter 0.546"
1-795-30/19 ACSR 138 kV phase wire at 60',
conductor diameter 1.140"
1-795-30/19 ACSR 138 kV phase wire at 54',
conductor diameter 1.140"
1-795-30/19 ACSR 138 kV phase wire at 48',
conductor diameter 1.140"
3-477 AAC 12 kV phase wires at 38',
conductor diameter 0.793"
1-1/0 AAAC neutral wire at 28', conductor
diameter 0.398"
1-1.5" diameter communications cable
at 25'
1-1.5" diameter communications cable
at 24'
1-0.5" diameter communications cable
at 23'
1-3" diameter communications cable at
21'
Question
What is the minimum pole class (diameter)
necessary to withstand the 2002 NESC extreme wind loading?
To determine the minimum pole class, we
will calculate the total moment on the pole at the ground-line
by multiplying the wind load on the pole and all supported
facilities by the height of attachment of those facilities.
The calculation will be done for the worst-case condition,
when the wind is blowing perpendicular to the line. For this
example, assume the line will be constructed on the East coast
in an area where the Basic Wind speed per Figure 250-2(b),
page 167, is 115 miles per hour. The first step is to
calculate the wind load on the pole.
Wind Load on the Pole
Because the pole diameter changes over its
length, we will look at the wind load on each one-foot segment
of the pole, starting at the top. To do this calculation, we
must assume a particular pole class, calculate the moment, and
then check to see if the class we assumed is adequate. The
minimum dimensions of wood poles are given in ANSI Standard
O5.1 Specifications and Dimensions for Wood Poles. Minimum
pole circumferences are given by wood type at the top of the
pole and six feet from the butt. Dimensions at other locations
can be determined by interpolation. For an 80-foot class H1
pole, the minimum diameter at the top is 9.23 inches and the
minimum diameter at the ground line, i.e., 10 feet from the
butt, is 17.66 inches. For wind load calculations, we have to
use maximum dimensions so we multiply the minimums by 1.2 as
suggested by section 6.2.2, page 7, of the ANSI O5.1 standard.
From Rule 250C, page 161, for cylindrical structures and
attachments:
load in pounds = 0.00256 x (wind speed)2 x
kz x GRF x Area
The velocity pressure exposure coefficients
kz for structures are given in Table 250-2, page 163, as a
function of the height of the structure above ground. The gust
response factors GRF for structures are given in Table 250-3
as a function of height of the structure above ground. The
velocity pressure exposure coefficients kz for conductors are
given in Table 250-2 as a function of the height of attachment
of the conductor on the structure. The gust response factors
GRF for conductors are given in Table 250-3 as a function of
height of attachment on the structure and conductor span
length (see table 1).
Wind Load on the
Conductors
To calculate the wind load on the
conductors, we use the same equation for load in pounds except
kz and GRF are different for conductors and the Area A is the
cross-sectional area of the conductor for half the span in
each direction. The moment for each conductor is the load
multiplied times the height of attachment for that conductor.
For the 7 No. 5 AW static wire, the height of attachment is
70'. From Table 250-2, kz is 1.20 for a conductor 70 feet
above ground. From Table 250-3, GRF is 0.86 for a conductor
70' above ground and spans shorter than 250'. Since the spans
are all 200 feet, the conductor area in square feet is the
conductor length in feet multiplied by the conductor diameter
in feet. The conductor diameter in feet is 0.546" / 12 =
0.0455. The conductor area A is then 200 x 0.0455 = 9.1 square
feet.
Wind load in pounds
= 0.00256 x (115)2 x kz x GRF x A
= 0.00256 x 13,225 x 1.20 x 0.86 x 9.1
= 317.9
The moment on the pole at the ground-line
due to the extreme wind load on the static wire is
317.9 x 70' = 22,253 foot-pounds
We then calculate the moments due to the
other conductors and add them all. At 38', we have three 477
AAC conductors. Calculate the moment for one conductor and
then multiply the answer by three. The total moment due to
extreme wind on all the conductors is 221,764 foot-pounds
compared to 90,462 for the structure. The large communications
cables contribute 77,661 foot-pounds even though they are
close to the ground. The total moment is 312,226 foot-pounds.
Safety Factors
Rule 260B1, page 175, states that
"Structures shall be designed to withstand the
appropriate loads multiplied by the overload factors in
Section 25 without exceeding their strength multiplied by the
strength factors of Section 26." The safety factor is the
overload factor divided by the strength factor. Table 253-2,
page 174, gives us the overload factor of 1.33 for use with
250C loads (extreme wind loads). The corresponding strength
factor of 1.0 is given in Table 261-1B, page 182. The safety
factor is 1.33 / 1.0 = 1.33. The calculated moments must be
multiplied by the safety before comparison to the pole
strength.
Total moment with safety factor
= 312,226 x 1.33 = 415,260 foot-pounds.
Pole Strength
The pole strength or ultimate moment at the
ground-line for a southern yellow pine pole is 2.111
multiplied by the cube of the pole circumference in inches.
The minimum circumference at the
ground-line
= ( total moment / 2.111)1/3
= (415,260 / 2.111)1/3
= 58.16"
The minimum diameter
= circumference / 3.1416
= 58.16 / 3.1416
= 18.51"
The minimum diameter for an 80-foot H1
class pole at ground line is 18.11". It looks like we
need an H2 pole (19.05"). Since we assumed an H1 pole for
the wind loading on the pole calculation, we will have to
recalculate for a H2 pole to be sure we are OK.
If you have general questions about the
NESC®, please call me at 302-454-4910 or e-mail me at dave.young@conectiv.com.
National Electrical Safety Code® and NESC®
are registered trademarks of the Institute of Electrical and
Electronics Engineers.
Dave Young is a senior engineer with Conectiv Power
Delivery of Wilmington, Delaware, where he has been working
with and teaching the NESC for over 30 years. He is a member
of the NESC Interpretations Subcommittee and an alternate on
the NESC Overhead Lines Clearances Subcommittee 4. Dave is
also vice-chairman of the Delmarva Division of the Chesapeake
Chapter of the IAEI.
|