IAEI News>Issue Listing>November/December 2002 >Understanding the Zone Area Classification Method in the NEC
The division classification method has been used in the United States since being incorporated into NEC 1920 to cover electrical and electronic equipment and wiring in extra-hazardous areas where fire or explosion hazards may exist from flammable and combustible liquids, vapors, or gases. The use of the term extra-hazardous locations implied that an electrical installation was already a hazardous installation but where used in areas, rooms, or compartments with some chemicals, it was more hazardous than usual. In NEC 1931, the term classifications was added to the NEC along with Class I, Class II, and III. The term extra-hazardous has been dropped from the NEC. These areas are now called hazardous (classified) locations which differentiates the hazardous chemical areas with electrical equipment from hazardous health areas. The NEC 1996 was the first edition to address the new hazardous (classified) method of zone classification. The NEC 1996 identified the newly introduced zone classification method as Class I, Zone 0, 1, and 2 and provided a basis to build upon in subsequent editions of the NEC. This new method of protection was based primarily upon the international method of zone protection and covered only limited concepts of the international technique. Definitions for this new method of zone protection were provided in a new Article 505 but contained limited information and application techniques. The NEC 1996 tied the division type of hazardous location articles together with the new zone type of protection techniques but the information was rather difficult to find since the new zone protection text was inserted into various places within the general hazardous locations articles. Even though the bulk of the information was in Article 505, it was necessary to extract some of the zone classification information from Articles 500 and 501 primarily covering Class I, Division 1 and 2 hazardous (classified) locations. In NEC 1999, all references to the zone concept of hazardous (classified) locations were removed from Article 500 for general hazardous location concepts and from most of Article 501 for Class I, Division 1 and 2 installations. A fine print note was left in 500-1 to provide the user with direction to Article 505 containing the bulk of the information on the zone concept of area classification. This single article concept for zone applications provided a more user-friendly method to access pertinent information where applying the zone concept. Article 505 provides information on equipment and wiring methods that are permitted in a Zone 0, Zone 1, and Zone 2 classified area. All other applicable rules would apply to these installations, except as amended by Article 505 or amended by those requirements in Article 504 dealing with intrinsically safe installations. The zone concept was further enhanced in NEC 2002 by changing the basic layout of Article 505 to fit the new numbering sequence required by the NEC Style Manual. All definitions were moved to 505.2; 505.3 covers other applicable rules located in other articles; and 505.4 provides general information pertaining to zone installations. This was done to provide consistency of section numbering with other similar articles. Further changes to Article 505 made it completely independent of Articles 500 and 501. Section 505.15 for wiring methods in a zone area was expanded to match its counterpart in 501.4 for wiring methods in a Class I, Division 1 and 2 area. Section 505.16 was inserted to cover the sealing requirements for zone methods rather than just referring back to 501.5 as was done in the previous Codes. Location and General Requirements for Article 505 Each area should be considered individually in determining the classification and care should be taken to not over-classify, as well as to not under-classify. Electrical equipment should be installed and connected in an area that is outside the hazardous (classified) location; however, where this not possible or practical, then special electrical equipment must be installed in the hazardous (classified) location. All of the factors that are normally associated with division area classification would apply to a zone classification, such as temperature, density or molecular weight of the substance, air circulation, quantity, pressure, and so forth. Highly oxygenated areas are outside the scope of both the zone classification and the division classification systems. These areas have had the ignition and burning characteristics of materials changed by exceeding the normal volume of oxygen of air that is mixed with the flammable gas or vapor. Where highly oxygenated areas are encountered, the user should refer to the specialized documents that deal with these types of areas and comply with the requirements for installation of electrical equipment in those areas. Areas where pyrophoric materials are present or handled are also outside the scope of both the zone classification and the division classification systems. Pyrophoric materials can be ignited just by introducing the material to air. Where these chemicals are used, installation of special electrical equipment is usually not necessary. However, care should be taken since there may be other combustible chemicals in the area that may require special electrical equipment. Since much of the electrical equipment built for the European and other world markets incorporate metric measurement and sizing, it may be necessary to provide adapters to convert from the standard NPT threads that are used in the United States to the metric threaded entries or fittings provided with the equipment. If equipment with metric threads is provided for use in the United States, the NEC requires that metric to NPT adapters be included with the equipment or be marked to identify the threaded entries as metric threads. NPT threads provide a ¾ inch per foot taper. Most standard conduit threading equipment available in the United States uses NPT thread. By conforming to a standard threaded system and providing a standard to metric adapter, electrical equipment with metric threads can be readily and safely adapted. Good electrical and mechanical continuity of conduit connections by the proper threaded adaptor to the enclosure can prevent sparking between the fitting, the conduit, and the enclosure during an electrical fault. The proper fitting can also ensure the integrity of the explosionproof or flameproof path by permitting the venting and subsequent cooling of the hot flaming gases after an explosion occurs within the enclosure. Definitions of Zone
Classification For Zone 0 locations, it is recommended that electrical equipment be located in an area outside the Zone 0 location. This is not always feasible since measurement equipment and other electrical equipment may be necessary for the function and monitoring of the system. In a Zone 0 location, intrinsically safe apparatus and the associated intrinsically safe circuit are the only wiring methods and protection technique that are permitted to be installed. Zone 1 Locations The normal classification for Zone 1 locations does not take into consideration catastrophic leaks. It does, however, consider small leaks from valves, pump packing glands, and other similar leakage considered common for equipment handling hazardous materials. Zone 2 Locations A Zone 2 location is one where the liquids, gases, or vapors are handled, processed, or used in an area but are normally confined within closed piping or containers that can only leak as a result of a rupture or some other abnormal condition. Positive mechanical ventilation is often used to prevent the buildup of ignitable concentrations of gases or vapors and, thus, to reclassify or declassify the area. Should the ventilation system break down, an ignitable concentration could require classification as a Zone 2 location. An area that is adjacent to a Class I, Zone 1 location from which ignitable concentrations of flammable gases or vapors could migrate would be a Zone 2 location, unless positive mechanical ventilation has been provided and there are safeguards to ensure against ventilation failure. Protection Techniques for Zone
Locations Underwriters Laboratories Inc. (UL) has further adapted these IEC documents with minor changes into a multi-part American National Standards Institute (ANSI) document, ANSI/UL 2279-2001, the Standard for Electrical Equipment for Use in Class I, Zone 0, 1, and 2 Hazardous (Classified) Locations. This UL standard is used for testing and listing of electrical equipment for use in zone classified areas and provides the manufacturer and the user with a detailed description of the particular protection techniques that can be used for these areas. Section 505.4(B), fine print notes provides standard references for important information involving hazardous locations. Each protection technique permitted in a zone installation is covered in 505.8 and in fine print notes that immediately follow many of these protection techniques.
Special Precaution with Zone
Equipment and Area Classification If abnormally low temperatures are encountered at the installation, such as below -20°C (-4°F), special equipment may need to be installed. If these low temperatures are encountered, it should be noted that many liquids are well below their flash points and are no longer a hazardous concentration issue; however, low temperature may also adversely affect the equipment operation, unless the equipment has been designed to operate in extremely low temperatures. For Class I, Zone 0, 1, and 2 areas, NEC 1996, 1999, and 2002 require classification of areas, selection of equipment, and selection of wiring methods to be handled under the supervision of a qualified, registered professional engineer. The use of a qualified, registered professional engineer for these systems should help ensure a degree of accountability for the installation and will remain a requirement until a significant number of trained personnel familiar with the equipment design and installation are available. Care should be taken where an installation that has both division and zone locations exists at the same facility. There may be some applications where the zone system is located adjacent to an existing division area, and this may require different area classification methods for the same plant or facility. This dual classification of a facility is acceptable; however, there are certain cautions that the user must observe. Class I, Zone 0 and Zone 1 locations must not abut or overlap any Class I, Division 1 or 2 locations. It is permissible to have Class I, Division 2 and Class I, Zone 2 areas that are adjacent to each other. Dual classification permits these two different classification methods with their different wiring methods to exist at a single facility but to provide a clear line of delineation between the two different systems. A user could reclassify a Class I, Division 1 or Division 2 area as a Class I, Zone 0, Zone 1 or Zone 2 area provided all of the reclassified space is classified using a single flammable gas or vapor source. Grouping and Classification of
Areas Based on the Chemicals Used These group classifications are subdivided into Groups IIC, IIB, and IIA according to the nature of the gas or vapor and the type of protection technique. Protection techniques, such as increased safety "e", encapsulation "m", purged and pressurized "p", and powder filled "q" equipment, are not dependent upon the ignition properties of the gases in the group. Their inherent designs will preclude the gases or vapors from entering the enclosures or being ignited by an arcing or hot electrical part. Group IIC is an atmosphere containing acetylene, hydrogen, or flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed with air that may burn or explode when ignited, having either an MESG less than or equal to 0.50 mm or an MIC ratio less than or equal to 0.45. Group IIB is an atmosphere containing acetaldehyde, ethylene, or flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed with air that may burn or explode when ignited, having either an MESG greater than 0.50 mm and less than or equal to 0.90 mm or an MIC ratio greater than 0.45 and less than or equal to 0.80. Group IIA is an atmosphere containing acetone, ammonia, ethyl alcohol, gasoline, methane, propane, or flammable gas, flammable liquid-produced vapor, or combustible liquid-produced vapor mixed with air that may burn or explode when ignited, having either an MESG greater than 0.90 mm or an MIC ratio greater than 0.80. Equipment can be listed for the specific gas or vapor, specific mixtures of gases or vapors, or any specific combination of gases or vapors. This permits electrical equipment to be designed, tested, and listed based upon a specific anticipated usage. For example, electrical equipment that has been tested as a Group IIB would normally be required for ethylene-based chemical atmospheres but may also have been tested for hydrogen-based chemicals. This permits the equipment to be marked with a IIB marking instead of having to be subjected to the more rigid tests for acetylene, as would normally be required if a IIC equipment listing is used. Listing, Marking, and
Documentation Zone equipment must be marked to indicate the class and the particular zone for which it has been listed. Zone equipment marked for use in the United States will have an "AEx" marking to indicate that the equipment has been listed in accordance with United States nationally recognized testing and listing standards. Many European and other countries permit manufacturer’s self-certification of electrical equipment for suitability of the equipment for environmental conditions, wire bending spaces, electrical insulation, in other words, the ordinary electrical equipment requirements. These countries do, however, require the equipment used in a zone location be third party certified for the hazardous location into which the equipment will be installed. The "AEx" mark and the testing lab mark should indicate to all persons involved in the installation that the electrical equipment has been tested and listed by a third party certification organization based on U.S. standards for the particular protection techniques plus the aforementioned ordinary electrical equipment requirements for shock and fire hazards. Temperature and Classification
of Zone Equipment Equipment designed be used in an ambient temperature below -20°C or above +40°C must have the ambient temperature range marked on the equipment. This is necessary since the ambient temperature at which it has been designed may affect the operating temperature of the equipment. These extremely low or high ambient temperatures may also affect the amounts of gases or vapors present. Low temperatures may also produce higher explosion pressures in flameproof or explosionproof equipment. Equipment suitable for use in an ambient temperature exceeding 40°C (104°F) must be marked with both the maximum ambient temperature in which it may be operated and the operating range of the equipment at that elevated temperature. Extremely high ambient temperatures may elevate the gas or vapor close to the autoignition temperature of the gas or vapor. It is critical that the autoignition temperature of a gas or vapor is not exceeded by contact with extremely hot electrical equipment. Electrical equipment that is not of the heat producing type or that operates at no greater than 100°C (212°F) is not required to have a marked temperature range or a marked operating temperature. Many hazardous chemicals have a much higher autoignition temperature than 100°C, but even if dealing with a chemical that has a low autoignition temperature, the electrical equipment is just one of many items that could be located in the area and be a concern for causing possible ignition of the material. Conclusion Ed Briesch is a senior staff engineer with Underwriters Laboratories and has been involved with Hazardous Locations equipment and installations for over 30 years. He is a principle member of NEC CMP-14 and the NFPA Technical Committee on Electrical Equipment in Chemical Atmospheres. He is also a member of several IEC, ASTM, IEEE and ISA technical committees related to explosion protected equipment. Ed has a BSChE from the Illinois Institute of Technology and is a Registered Professional Engineer in the State of Illinois. Mark C. Ode, staff engineering associate at the Underwriters Laboratories Inc. in the Research Triangle Park, North Carolina Regulatory Services Department, was a senior electrical specialist for the National Fire Protection Association. He is a former staff liaison and secretary to the NFPA Electrical Equipment in Chemical Atmospheres Committee. He was the executive secretary for the NFPA Electrical Section and editor of the Electrical Section news bulletin, Current Flashes. Prior to joining NFPA, Mr. Ode worked for over 27 years as a licensed electrician and a licensed electrical contractor. He is a licensed electrician in the State of Massachusetts. He has taught the National Electrical Code throughout the United States. He also taught the NEC for 10 years at Maricopa County Community College in Phoenix, Arizona. He is certified for electrical inspection for one and two family dwellings, general electrical installations, and for electrical plan review by the International Association of Electrical Inspectors (IAEI), and is certified as a general electrical inspector by the International Conference of Building Officials (ICBO). He is certified as an electrical instructor for the States of Wyoming, New Jersey, North Carolina, Michigan, and Massachusetts, as well as others. He was Vice-President of Field Operations for an engineering firm for two years and was President of Ode Electric for 15 years. He is an electrical code columnist for Electrical Contractor magazine. He was a principle member of NEC Panel 20 for the 1990 NEC and an alternate member of NEC Panel 3 for the 2002 NEC. He is a principle member of CMP 4, an alternate member of CMP 1, and an alternate on the NEC Technical Correlating Committee for the 2005 NEC. He has been a member of IAEI since September 15, 1975.
|
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||