|
| |
 |
| Figure
1 |
| Va |
|
| Figure 2 |
| Shows the flow of currents
in a 3-phase 4-wire distribution system serving motor
loads |
|
| Figure 3 |
| owever,
when SMPS loads are connected as shown in figure 3, each
phase wire carries both the 60 Hz fundamental current
that supplies power to the computer and the harmonic
currents that are there because of the way the SMPS
draws its current |
|
| Figure
4 |
| The electrical characteristics of this type
of circuit are such that it has a very high resistance
to the flow of 3rd harmonic current and a very low
resistance to the flow of the fundamental 60 Hz current.
Application of the HSS is shown in figure
4 |
|
| Figure 5 |
| A recent study showed
that, depending on transformer loading and the
distribution distance from the transformer, the energy
saved by eliminating 3rd harmonic currents ranged from a
minimum of 2.5 percent to a maximum of 8 percent of the
energy used to power computers.10
A graph from this study is shown as figure 5 shows. |
|
|
|

IAEI
News>Issue Listing>January/February 2003 >The 3rd Harmonic Blocking Filter:
A Well Established Approach to Harmonic Current Mitigation
| The 3rd Harmonic Blocking Filter:
A Well Established Approach to Harmonic Current Mitigation |
Despite thousands of successful applications of harmonic blocking technology worldwide, harmonics mitigation remains an elusive subject. |
|
| by Michael Z. Lowenstein, Ph.D. |

It has long been recognized that
harmonic currents, particularly the 3rd harmonic,
flowing in a wye distribution system serving multiple
computer loads, are detrimental to system operation.
Problems caused by these harmonic currents include
overheated transformers, switchgear and wiring; random
circuit breaker tripping; and reduced useable system
capacity. Conventional methods used to mitigate the
harmful effects of these harmonic currents include
k-rated or de-rated transformers, harmonic mitigating
transformers (zig-zag and phase shifting,) oversized
switchgear, double or triple neutrals, and other
"accommodation" techniques. However, it is
easier to prevent the flow of harmonic currents than to
treat them after they are flowing in the system. The
3rd-harmonic blocking filter is a well-established
device that prevents harmonic current flow.
Despite thousands of successful applications of harmonic
blocking technology world-wide, harmonics mitigation
remains an elusive subject, and questions continue to be
raised about how this technology works, is it safe, does
it meet code requirements, is it UL listed, what about
standards, etc. This paper will discuss the design and
operation of the 3rd harmonic blocking filter, with
special attention paid to code and regulation
requirements and electrical distribution system
benefits.
Harmonic currents
Harmonic currents are a direct result of the way in
which a switched-mode computer power supply (SMPS) draws
current from the system. The input circuit of an SMPS is
a bridge rectifier that changes the 120-volt AC input to
DC. A capacitor smoothes this DC to eliminate voltage
ripples and the resultant DC bus has a voltage of about
170 volts when the AC rms input is 120 volts. Although
the AC voltage is a sine wave, the rectifier draws its
current in spikes as shown in figure 1. These spikes
require that the AC supply system provide harmonic
currents, primarily 3rd, 5th and 7th. These harmonic
currents do not provide power to the SMPS, but they do
take up distribution system capacity. The principal
harmonic current is the 3rd (180 Hz) and the amplitude
of this current can be equal to or even greater than
that of the fundamental current. [Figures
1 and 2]
Harmonic current flow in a wye
distribution system
Figure 2 shows the flow of currents
in a 3-phase 4-wire distribution system serving motor
loads. One of the reasons this type of distribution
system is used is that when the loads on all three
phases are balanced, and only the 60 Hz fundamental
current is considered, the fundamental current cancels
in the neutral and the neutral current is zero. If the
loads are unbalanced, the neutral current is only the
unbalanced current. (Until 1990 the NEC permitted
downsized neutral wires since the neutral was not
considered to be a current-carrying conductor.) However,
when SMPS loads are connected as shown in figure 3, each
phase wire carries both the 60 Hz fundamental current
that supplies power to the computer and the harmonic
currents that are there because of the way the SMPS
draws its current. While most of the harmonic currents
cancel in the neutral wire, just as the 60 Hz currents
do, the 3rd harmonic current and other currents
divisible by three are additive in the neutral wire.
Thus, if the 3rd harmonic current were 100 amps in each
phase, the 3rd harmonic current returning to the XO
transformer connection along the neutral wire would be
300 amps. While the code still permits downsized
neutrals if the system is not powering nonlinear loads,
this is the reason for language in NEC 310.15(B)(4)(b,
c) (2002) that requires neutral conductors to be
considered current-carrying conductors when nonlinear (SMPS)
loads are present. (Note that there is no code
requirement for double neutrals.)
System problems caused by 3rd
harmonic currents
The effect of current distortion on
the actual computer loads within a facility is minimal
since the distorted current is caused by operation of
these loads. However, the effect of current distortion
on distribution systems can be serious, primarily due to
the increased current flowing throughout the system. All
distribution systems are rms current limited, and the
more harmonic current flowing, the less room there is
for fundamental current. Since the harmonic current does
not deliver any power, its presence uses up system
capacity and reduces the number of loads that can be
powered. Harmonic currents also increase I2R
heat losses throughout the system. The 3rd harmonic
current flows in all phase wires and is additive in the
neutral wires. It is very possible for this extra
current to overload and overheat wires and associated
switchboards and panelboards.
Balanced 3rd harmonic currents cannot
flow out of a delta primary. Therefore, they circulate
in the primary of the transformer where they are
dissipated as heat (see figure
3). The current
circulating in the transformer delta primary winding
does not flow through the primary overcurrent protective
device but does contribute to the load on the primary
winding. Thus, the transformer primary winding can be
overloaded without operating the overcurrent protective
device.
inally, 3rd harmonic currents
flowing through the resistance of the electrical system
create 3rd harmonic voltage distortion. Phase-to-neutral
voltage distortion does not harm the computer power
supplies, since it is caused by operation of the
supplies. However, high neutral harmonic current flow
can lead to neutral-to-ground voltages (noise) that can
result in data loss and computer malfunction. The
further the computer is from the transformer, the higher
these neutral-to-ground voltages will be and the greater
the possibility for data loss.
Alternatives for harmonic
mitigation
Until introduction of the 3rd
harmonic blocking filter (often called a "harmonic
suppression system or "HSS"), methods used to
mitigate the effects of harmonic currents involved
"accommodation" of the currents after they
were in the system. A first step was to overbuild the
system to handle the extra current. Double-sized neutral
wires, oversized switchboards and panelboards and
transformers de-rated to less than their full capacity
are examples of system overbuilding. To reduce the
chance of transformer failure due to overheating,
special transformers, known as "k-rated," were
designed to be able to handle high harmonic loading,
including 3rd harmonic currents circulating in the delta
primary, without burning up. On a k-rated transformer,
neutral connection lugs are oversized and may be doubled
to handle two neutral wires. The transformer core
contains more iron to reduce flux density and multiple
wires are used in the windings to handle extra currents.
The resulting transformer will survive overheating when
subjected to high harmonic loading, but the harmonic
currents are still present in the system.
Another method of protecting
transformers from circulating 3rd harmonic currents
without replacing them with k-rated devices is to use a
"zig-zag" reactor. The zig-zag reactor
contains special windings connected so as to present a
low impedance to 3rd harmonic currents. When a zig-zag
reactor is connected between the phases and neutral of a
wye system, the 3rd harmonic currents are diverted
through the device. These currents no longer flow, from
the point where the zig-zag is connected in the system,
upstream to the transformer. From the point of
connection of the zig-zag back to the transformer, the
phase wires carry only 60 Hz current and harmonic
currents other than 3rd. However, the phase and neutral
wires from the zig-zag toward the loads still carry all
the harmonic currents, including the 3rd, and double
neutral wires are recommended. This device protects the
upstream wiring and transformer, but has no effect on
the loads or load wiring.
A "zig-zag" transformer can
be used to replace the standard transformer in a system.
This device has the special windings of the zig-zag
reactor built into the transformer secondary so that the
3rd harmonic currents are cancelled in the secondary and
do not circulate in the primary winding. Again, the
phase and neutral wires from the transformer to the
loads still carry all the harmonic currents and double
neutral wires are recommended.
The 3rd harmonic blocking
filter (aka harmonic suppression system of "HSS)
The 3rd harmonic blocking filter uses
a different approach to mitigate harmonic currents in
the distribution system. Its application is based on the
same concept that is used in modern medicine,
"preventative action." Instead of treating the
symptoms of a disease, it is far better to keep the
disease from occurring. The HSS is designed to prevent
the flow of harmonic currents in the distribution
system, rather than treating or accommodating them after
they are there.
The HSS consists of a parallel
resistive/inductive/capacitive (RLC) network tuned to
the 3rd harmonic, or 180 Hz for a 60 Hz fundamental
frequency. The electrical characteristics of this type
of circuit are such that it has a very high resistance
to the flow of 3rd harmonic current and a very low
resistance to the flow of the fundamental 60 Hz current.
Application of the HSS is shown in figure
4.
The HSS is connected in series
between the neutral wire and the transformer XO. All
current that flows through the phase wires to the load
must return through the neutral. If 3rd harmonic current
cannot flow in the neutral, due to the high impedance of
the HSS, then no 3rd harmonic current can flow in the
phase wires. The damaging 3rd harmonic current is
blocked throughout the entire distribution system from
the transformer out to the furthest load. There is no
3rd harmonic current circulating in the delta
transformer primary because there is no 3rd harmonic
current available to circulate. The transformer is now
fully protected, by the primary circuit breaker, against
overloading. Phase wires have more capacity remaining to
carry useful load and double neutrals are not necessary.
The neutral, for code purposes, need no longer be
considered a current-carrying conductor. Overheating of
transformers, switchboards and panelboards, and wiring
is eliminated, increasing the lifetime of all system
components.
The HSS, the NEC and other regulations and concerns
In the reality of the commercial
marketplace competitors of a particular technology often
raise false concerns in an attempt to detract from the
benefits of that technology. As the HSS has been the
target of such actions, it is useful to examine the HSS
installation in terms of the Code and other
regulations. A number of issues will be discussed in
some detail.
Does the installation of the HSS
constitute a "resistance-grounded system?"
Resistance-grounded systems
employ an intentional resistance connection between the
electrical system neutral and ground."1
Such systems are usually used in medium and high voltage
distribution networks to limit ground-fault currents.
Impedance grounded systems are permitted in systems of
480–1000 volts, again to limit ground-fault currents. NEC
250.36 (2002). The impedance inserted is usually a
high value (100–10,000 ohms depending on the voltage
level) designed to limit the fault current due to a
phase-to-neutral short to a low figure, e.g., 10 amps. A
current sensor on the grounding resistor detects this
low current and shunt-trips the protecting breaker. The
installation of the HSS, with an AC impedance of 0.05
ohms or less, does not constitute an impedance ground,
does not significantly limit the
short-circuit current,
and is not in violation of this section of the Code.2,3
What about other grounding language
in the Code?
The following code references are to NEC 2002. Words in bold refer to the labels in figure
4.
Article 100 defines a separately
derived system and Section 250.20(D) establishes Section
250.30 as the controlling language. Section
250.30(A) defines exactly the manner in which the
HSS is applied to the electrical distribution system.
Conductors of interest include:
1. The grounded conductor (NEUTRAL), Section 250.26, Conductor to be grounded...,
as follows: (2) Single-phase, 3-wire: the neutral
conductor. and (5) Multi-phase systems in which
one phase is used as in (2) above: the neutral
conductor.
2. The GROUNDING ELECTRODE, Section
250.30(A)(4), Grounding Electrode, (1) an effectively
grounded structural metal member of the structure
3. The grounding electrode conductor
(GEC), Section 250.30(B)(2), A grounding
electrode conductor shall be used to connect the
equipment grounding conductors, the service equipment
enclosure, and, where the system is grounded, the
grounded service conductor to the grounding electrode…
4. The equipment grounding conductor
(EGC), Section 250.110, …exposed
non-current-carrying metal parts…shall be grounded …
5. The bonding jumper, Section 250.30
(A)(1) refers to Section 250.28, For a grounded
system, an unspliced main bonding jumper shall be used
to connect the equipment grounding conductor(s) …to
the grounded conductor of the system…
6. Equipment bonding jumper (EBJ), Section 250.30(A5), Where a bonding jumper is run
with the derived phase conductors from the source of a
separately derived system…
In figure 4, it can be seen that the NEUTRAL is directly connected inside the filter to the EGCs.
The connections are with, "…listed pressure
connectors…", NEC 250.70. The connections
are all made within the filter enclosure directly at a, "…bus
bar…," Section 250.30(A)(3)(b), which serves
as the main bonding jumper. The GEC is
also connected to the same point and goes from that
point directly, "shall be installed in one
continuous length without a splice or joint…" ,
NEC 250.64(C), to a GROUNDING ELECTRODE in
accordance with 250.30(A)(4). Further, the
transformer enclosure is correctly connected to the NEUTRAL by the EGC, NEC 250.118, as are all enclosures
and conduit in the distribution system. The Code requires transformer enclosure grounding, for safety, NEC
450.10, and as explained above, the HSS and its
associated transformer connections follow exactly NEC definitions and language. The HSS was designed to meet NEC requirements. Consultation with a number of NEC board members, who are experts on grounding, has
confirmed HSS code compliance. Any suggestion that the
HSS installation does not meet NEC requirements
is simply not valid.
What about "arcing" faults
due to phase-to-neutral shorts?
The purpose of grounding requirements
in the NEC is to ensure that health and safety
are not compromised. Adjacent pieces of equipment that
can be energized must be tied together to a common
ground so that dangerous potentials do not exist between
equipment cabinets. Proper grounding must ensure that
protective devices will operate correctly under fault
conditions. The impedance of the HSS is less than 0.05
ohms, and decreases with increasing HSS kVA rating.
Under short-circuit conditions, the current flowing
through the HSS is more than sufficient to trip the
phase breakers. It should be noted that the inductive
elements of the HSS, which carry the current under fault
conditions, are UL listed components and have been
tested to carry full rated current for the size of the
system in which they are used.
What about UL?
In most jurisdictions, it is
impossible to sell or install electrical equipment that
has not been inspected by a qualified third party
testing laboratory. Therefore, before the neutral
blocking filter could be offered on the market, it was
submitted to UL for testing. All neutral blocking
filters are UL listed.4
What about voltage distortion?
Voltage distortion caused by harmonic
current flow is a natural result of harmonic currents
flowing through the impedance of a system. In commercial
facilities, where multiple computers are powered, the
computers often draw enough 3rd harmonic current through
the supply wires to generate as much as 10 percent
voltage distortion. (The further the load is from the
transformer, the higher this distortion.) While this
might seem to be cause for concern, the truth is that
this distortion is caused by operation of the SMPSs and
certainly does not interfere with their operation. When
the HSS is installed at the transformer, 3rd harmonic
currents no longer flow in the phase wires. However, the
high 180 Hz impedance of the device, results in
phase-to-neutral 3rd harmonic voltage equal to, or
sometimes higher than, the natural voltage distortion.
Again, this does not interfere with the SMPS operation.
What about high voltage distortion damaging the
rectifiers or capacitors in the SMPS?
It has already been mentioned that
the SMPS during its operation causes 3rd harmonic
voltage distortion. Research studies have been conducted
to thoroughly investigate the effect of voltage
distortion on the power supplies. Contrary to any
suggestion that reduced peak voltage would increase
power supply losses, a definitive study has determined
that addition of 10 percent 3rd harmonic voltage
distortion to the 60 Hz wave actually increased the
efficiency of the power supply by as much as 6.1
percent.5
Further, a computer modeling study carried out at a
major university, found that installation of the HSS
reduced the strain on rectifiers and would be expected
to lead to increased lifetime for the SMPS components.6
Neither of these studies is compatible with the
suggestion that use of the HSS could lead to equipment
failure. There has never been any study that shows that
erratic or subtle malfunctions are caused by powering
SMPSs with distorted voltage. If anything, erratic
operation can be caused by neutral-to-ground voltages.
What about neutral-to-ground voltage?
When 3rd harmonic currents flow in
neutral wires, but not in the safety ground wires, the
result is a voltage generated between the neutral and
ground. When the combined 3rd harmonic currents from the
phases flow in the neutral, this voltage can reach more
than 10 volts. This voltage can interfere with data
transmission in shielded wires and can result in lost
data or data corruption. By preventing the flow of 3rd
harmonic currents in any neutral wires out to the
furthest load, the HSS completely eliminates 3rd
harmonic neutral-to-ground voltage, thereby increasing
the reliability of data transmission.
What about computer ride through?
Reduction in peak voltage, whether
caused by the operation of the SMPS or by installation
of an HSS, reduces voltage-out ride through time. Ride
through time is why facilities install uninterruptible
power supplies (UPSs) on their critical computer loads.
Most facilities that install HSS also have large UPSs
and generators for support. Some use small UPSs at
critical loads. The switching time for small UPSs is
between 10 and 50 milliseconds. A published study showed
that a computer would function for about 175
milliseconds on complete input voltage loss if the input
rms voltage were 120 volts, (the peak voltage would be
about 170 volts.)7 HSS flat
topping has never reduced the peak voltage below 150
volts, which would result in a ride through time of no
less than 136 milliseconds. Since the majority of
complete power outages last for longer than 200
milliseconds, the computer supply will not ride through
the outage either with or without the HSS. That is the
reason for the UPS, and it is clear that, even in the
worst case, with an HSS the computer would operate long
enough for the UPS to take over. The same study showed
that computers would operate indefinitely with an input
voltage of only 50 percent of the rated voltage—60
volts. It should be clear that the HSS does not affect
computer ride through in the real operating world.
What about IEEE 519?
There is a mistaken belief that IEEE
519 regulates harmonic voltage distortion levels
everywhere in a distribution system. In reality, this
document was developed to limit current and voltage
distortion at the utility connection to multiple
customers, called the Point of Common Coupling (PCC)8
It was developed to deal with 3-phase industrial systems
and was never intended to apply, and does not apply, to
phase-to-neutral voltage distortion at the secondary of
a transformer that is internal to a facility. (As has
been discussed above, phase-to-neutral voltage
distortion has no negative effects on operation of
computer power supplies.) Any references to IEEE 519
with regard to voltage distortion and the HSS are an
incorrect application of this standard.
Benefits of the HSS
Now that issues with the HSS and any
code, regulation, or operation factors have been
discussed, it is useful to examine in some detail the
benefits of installing this technology to mitigate
harmonic currents. Four areas will be discussed: 1)
enhanced life safety; 2) increased system capacity; 3)
greater reliability; 4) energy and operating cost
savings.
Enhanced life safety
Third harmonic currents flowing in
the system can overload transformers, switchgear, and
wiring. With neutral currents greater than the phase
currents, facilities, and particularly older facilities,
are at risk from overheated wiring leading to fires.
Transformers with high 3rd harmonic currents circulating
in the primary, and unprotected against overloading, can
fail or catch fire. One study found that 33 percent of
telecommunication fires were caused by failures of power
systems or components.9
By eliminating 3rd harmonic currents from the
transformer to the furthest outlet, the HSS eliminates
the risk of over-current caused fires.
Increased system capacity
All electrical distribution systems
are rms current limited. Harmonic currents carried by
transformers, switchgear, and wiring use up system
capacity that could be used to carry 60 Hz currents that
do work. By eliminating 3rd harmonic currents throughout
the entire distribution system, the HSS provides the
facility with more useful capacity without requiring
that the electrical system be upsized.
Greater reliability
The major cause of failure for
transformers and equipment is overheating. Random
breaker tripping due to harmonic heating is well known.
The elimination of 3rd harmonic currents reduces heat in
all parts of the distribution system, thereby reducing
the likelihood that system components will fail or trip
off due to excessive temperatures. The elimination of
high neutral currents lowers neutral-to-ground voltages
and reduces the likelihood that data errors will occur.
Energy and Operating Cost Savings
Excessive heat in electrical
distribution systems means wasted energy. The heat is
due to I2R
losses in all system components, and appears directly in
energy bills as increased kW hour charges. Installation
of the HSS eliminates this wasted energy and leads to a
direct reduction in energy costs. A recent study showed
that, depending on transformer loading and the
distribution distance from the transformer, the energy
saved by eliminating 3rd harmonic currents ranged from a
minimum of 2.5 percent to a maximum of 8 percent of the
energy used to power computers.10
A graph from this study is shown as figure 5 shows. In addition to the direct waste of energy
caused by harmonic currents, there is a secondary
effect. Air conditioners must be powered to remove this
excess heat. Reducing extra operation of air
conditioners, necessary because of harmonic generated
heat, can add another 1–3 percent to the energy saved
by an HSS. The bottom line is that the installation of
an HSS can pay for itself in two to three years.
Conclusions
The harmonic suppression system is a
well established technology. It has been on the market
for more than 10 years without a single documented case
of damage to equipment in any facility. It has been
embraced by a wide variety of users, including major
computer manufacturers, banks, stock exchanges,
educational institutions, insurance companies, broadcast
facilities…in short any group that uses multiple
computers. The capacity and energy savings are well
documented and life safety and reliability issues need
no longer be of concern to users. It would be
unfortunate if some were deterred from using this
innovative and effective technology by undocumented
allegations and suggestions of "potential"
problems that are never realized in the real world.
References
1. Recommended Practice for Electric
Power Distribution for Industrial Plants, section 7.2.2,
The Red Book, IEEE141-1993.
2. Private correspondence, Lanny McMahill, Electrical Inspections Supervisor, City of Phoenix, November
17, 2001.
3. Private correspondence, Mike Holt,
Consultant, 2001.
4. UL file # E190931
5. "Energy Use of Personal
Computers," PQTN Brief # 20, EPRI Power Electronics Application Center,
(1994.)
6. "Neutralizer Harmonic Blocking
Device Study," Alexander E. Emanuel, Worcester Polytechnic
Institute (2001.)
7. "Low Voltage Ride-Through
Performance of a Personal Computer Power Supply," PQTN
Brief # 11, EPRI Power Electronics Application Center, (1993.)
8. Chapter 11, IEEE Recommended
Practices and Requirements for Harmonic Control in Electrical
Power Systems, IEEE Std 519-1992, IEEE (1993.)
9. "Target: Telco Fires," Workplace
Protection, Fall Issue (2001.)
10. "Power Savings," Harmonics
Limited EAB2 (2002.)
Dr. Lowenstein holds an A.B. in
chemistry from Oberlin College, and an M.S. and Ph.D. in
physical and analytical chemistry and physics from
Arizona State University. He spent 13 years as a college
chemistry professor and 8 years as a national program
manager for the Solar Energy Research Institute. His
experience with harmonics includes 15 years designing
filters for 3-phase industrial drives. In 1989 he
founded Harmonics Limited, a company devoted to solving
harmonic problems caused by multiple computer loads.
He has served as a lecturer at the University of
Wisconsin, Milwaukee, teaching courses in power quality
and non-linear loads. He has presented invited lectures
and seminars at national meetings for numerous
organizations with concerns about power quality and
harmonics.
Dr. Lowenstein is a member of The IEEE Industrial
Applications Society, The Power Engineering Society, and
the Standards Society. He serves on SCC 22, the power
quality Standards Coordination Committee, the body with
coordination responsibility for all IEEE power quality
standards, and is involved in the revision of IEE519
currently underway.
|
|
|