| | |
 |
| Figure 1 |
| The term "furring strips" has been added to Section 300.4(D) |
|
| Figure 2 |
| The word "equipotential" was added to 680.26 to clarify the intended purpose of the bonding required by this section |
|
| Photo 1 |
| A new Part X to Article 430 provides rules for adjustable speed drives |
|
|
|

IIAEI
News>Issue Listing>September/October 2003>Proposed Code Changes for the 2005 NEC
| Proposed Code Changes for the 2005 NEC |
This article provides a preview of some of the more significant proposed changes to the 2005 NEC. This is a continuation of Part I provided in the July/August issue. |
|

This article is intended to
provide a preview of some of the more significant
proposed changes to the 2005 NEC. This is a
continuation of Part I provided in the July/August
issue. It is important to understand that this summary
is not intended to indicate that the Code is
going to be revised as provided in this article, only
that these are initial proposals that were acted on by
the code-making panels in the proposal stage of the
overall process. Part I reviewed various proposals from
Articles 80 through 230. This collection of significant
proposed changes provides a preview of proposed changes
starting in Article 240 and visiting other revisions
proposed to various other articles through to Chapter 8.
The second stage of the process includes opportunities
for public review and comment to the proposed changes.
It is important that the comments be submitted prior to
the closing date of October 31, 2003, at 5:00 p.m. EST.
The comment form is provided both in the printed copy of
the Report on Proposals (ROP) and on the NFPA
website at www.nfpa.org . Each comment submitted will be
acted on by the code-making panels in December in San
Diego, California, and then included in the Report
on Comments (ROC) when published.
The following provides a brief summary of the proposed
changes and includes the proposal number, the section,
and a short description of how each of these sections
would be revised as a result of initial panel action to
the proposals.
Proposal 10-22
New Exception to Section 240.4(C)
A new exception was added to this requirement that will
permit conductors to be protected by the next higher
standard overcurrent device rating (above the ampacity
of the conductors being protected) within the
limitations of four specific conditions.
1. The next higher standard overcurrent device rating
(above the ampacity of the conductors being protected)
does not exceed 6 percent above the ampacity of the
conductors being protected.
2. The ampacity of the conductors does not correspond
with the standard ampere rating of a fuse or a circuit
breaker without overload trip adjustments above its
rating (but that shall be permitted to have other trip
or rating adjustments).
3. The next higher standard rating selected does not
exceed 1600 amperes.
4. The overcurrent device has been listed for use with
the smaller conductors.
Devices rated 1600 amperes or less can be used to
protect conductors rated smaller than the rating of the
device if all four conditions are met. If any of the
conditions are not met, than the current requirements in
the general rule for devices rated over 800 amperes
shall be followed.
Proposal 10-24
Revision Section 240.4(E)
This section was revised by reorganizing the referenced
sections within the existing rule into a list format
that is consistent with the NEC Style Manual Section 3.3.2. This change does not have an impact on
any of the current sections referred to by this section
nor are there any added references. This list format is
a logical conversion where the result is more practical
for users of the Code.
Proposal 10-39
Revision 240.20(B)(1), (2), and (3)
This revision to subdivisions (1), (2), and (3) replaces
the word "approved" with the word
"identified." This change clarifies that
handle ties used on circuit breakers as permitted in
this section are required to be designed by the
manufacturer and used within those limitations. This
change will help prevent the use of nails, wire, or
other unacceptable methods of connecting single-pole
devices handles together to meet the requirements of
this section.
Proposal 10-57
Revision 240.21(C)
This revision changes the word "conductors" to
"each set of conductors feeding separate
loads" in the first sentence of the rule. This
change in wording provides clarification that multiple
sets of conductors can be tapped to a single transformer
secondary but each set must comply with all of the
requirements in 240.21(C)(1) through (6).
Proposal 10-72
Revision Section 240.24(B) Exception No. 2
This section was revised by adding the wording "in
other than dwelling units" within the exception.
This revision clarifies that guest rooms that meet the
definition of "dwelling unit" are required to
have the overcurrent protection devices for the
occupancy readily accessible to the occupant. Other than
dwelling units are only required to provide access to
the overcurrent devices to authorized management
personnel.
Proposal 10-82
New Section 240.93 Series Ratings
This proposal as accepted introduces a new section under
Part VIII Supervised Industrial Installations. This new
provision allows the use of series rated systems when
tested and selected under engineering supervision.
Series rated combinations would now be allowable under
supervised engineering where combinations of line-side
overcurrent device and load-side circuit breaker are
tested and marked on the end use equipment. The
line-side device is to be selected under engineering
supervision, and the load-side device must be tested and
marked on the end use equipment by the manufacturer. The
line-side device must be field-marked as well as the end
use equipment.
Proposal 5-1
Entire Code – Change in Terminology
This proposed change would replace the term
"equipment grounding conductor" with the term
"equipment bonding conductor" where
appropriate throughout the sections in which it is used
within Article 250, and it was also proposed to all of
the code-making panels to address the term as used in
any article under the responsibility of each panel. The
proposed change in terminology is intended to work more
effectively with the recent changes that clarify
performance criteria and language in Article 250 that
differentiates between the "grounding" and
"bonding" and the performance aspects of each
term. This proposed change is directed at increased
understandability and usability of the Code requirements
related to these two separate functions grounding and
bonding.
Proposal 5-37
Title of Article 250
This change incorporates the words "and
bonding" into the title of Article 250. The title
of the article would now be Article 250 Grounding and
Bonding. There is no change to the wording of the scope
of the article, which already includes the words
"or bonding."
Proposal 5-74
Revision Section 250.28
This change draws a distinct differentiation and adds
new terminology within this section to clearly identify
the connection between the grounded conductor and the
equipment grounding conductor of separately derived
systems as a "system bonding jumper." Previous
editions of the Code have used the term
"bonding jumper" as in 250.30(A) which, by
definition, means something different than how it is
used in this section. The revision provides clarity and
increases understandability and application for users of
the Code. The term "service-entrance
conductors" from (D) has been removed and the words
"supply conductors" have been added to clarify
that the sizing requirements apply to the "supply
conductors" whether they are service-entrance
conductors or derived phase conductors of separately
derived systems. A new definition has also been accepted
to Article 100 that defines the new term "system
bonding jumper" used in this section.
Proposal 5-78
Revision and Reorganization of Section 250.30
This change reorganizes and restructures Section 250.30
for clarity and usability. It incorporates several
technical changes also to clarify the rules. The sizing
requirements for equipment bonding jumpers have been
clarified to reference 250.102(C), which resolves sizing
conflicts where the derived phase conductors are
installed as parallel secondary conductors. The methods
of connection for the grounding electrode conductor taps
to the common grounding electrode conductor have been
revised to be consistent with the methods permitted to
the same concept allowed under the provisions of
250.64(D) for services. A clarification has been
incorporated into Section 250.30(A)(7) to indicate that
any of the electrodes in 250.52(A) shall be permitted to
be used where structural metal building frame electrodes
or where a metal water pipe grounding electrode is not
available. The revisions to this section more clearly
address grounding electrode conductor(s) requirements
for individual separately derived systems and the common
grounding electrode conductor concept for multiple
separately derived systems as separate provisions.
Proposal 5-109
Revise Section 250.32
The words "two or more" and "from a
common service" have been removed from this
section. The title of the section has been revised to
include the words "feeder(s) or branch circuit(s)"
to clarify applicability of the requirement. The
revision clarifies that the grounding rules at separate
buildings or structures are required to apply regardless
of where the feeder(s) or branch circuit(s) supplying
them originates. A new sentence has also been added to
the Exception to read as follows: "For the purposes
of this section, a multiwire branch circuit shall be
considered a single branch circuit."
Proposal 5-244a
New Section 250.147
This change adds a new Section 250.147 to include
bonding requirements for switches in Article 250 that is
consistent with those in Article 404 for switches. This
added section is a logical placement for the
requirements for grounding of switches as it directly
follows the same requirements for bonding of grounding
type receptacles. The added requirement is also
consistent with the provisions currently contained in
404.9(B). Including the requirement in Article 250
improves usability and provides requirements within
Article 250.
Proposal 3-17
Section 300.4(D)
The term "furring strips" has been
incorporated into this section, clarifying that even
though they may not be framing members, that the
1-1/4" clearance from any edge subject to nail or
screw penetration must be maintained [see figure
1].
Proposal 3-67
Revision Section 300.11(A)(1)
Section 300.11(A)(1) has been revised to address
attaching additional wires for wiring method support to
the grid of a fire-rated ceiling assembly. An added
phrase, "and shall be permitted to be attached to
the assembly," now clarifies that additional wires
installed for wiring method support in a fire-rated
ceiling may be attached to the ceiling grid.
Proposal 3-94
Section 300.22(B) (C) & (D)
The panel rejected a new concept that would divide
air-handling spaces into:
1. Raised floor and ceiling cavity plenums
2. Ducts and plenums
"Plenum" cable would no longer be allowed
inside ducts and plenums, and a new "duct
cable" is being introduced in Articles 725, 760 and
other "low voltage" articles under the purview
of Panel 16. Panel 16 accepted the new concept, so the
Technical Correlating Committee and the two panels will
have to come to a consensus before or at the comments
stage. This revision would remove the term "other
spaces used for environmental air" from this
section and other articles and provide wording
consistent with that used in NFPA 90A-2002, The
Standard for Installation of Air-Conditioning and
Ventilating Systems. The Technical Correlating
Committee has assigned a task group to work
cooperatively with the panels and reach reasonable
consensus to address the proposals in consistent
fashion.
Proposal 6-31
Revise Section 310.15(B)(2)(a)
The proposed revision to this section adds a more
restrictive requirement to apply ampacity adjustment
factors where more than two NM cables containing two or
more current-carrying conductors each are bundled
together and pass through wood framing members where
fire-stopping or draft-stopping material is installed at
the penetration. The ampacity adjustment factors
specified in Table 310.15(B)(2)(a) would be required to
be applied to the current-carrying conductors installed
in this manner.
Proposal 6-33
Revise Section 310.15(B)(2)(a)
A new sentence has been added to the existing rule that
addresses adjustment factors where parallel conductors
are installed. The new sentence clarifies that each
current-carrying "wire" of a parallel set of
conductors is required to be counted as current-carrying
where application of correction factors is necessary.
Proposal 6-45
New Section 310.15(B)(2)(c)
A new section was added to this section and reads as
follows: "Installations Outdoors in Direct
Sunlight. Where feeders or branch-circuits are installed
in raceways outdoors on rooftops which are exposed to
direct sunlight, the ampacities of Tables 310.16 and
310.18 shall be derated by a factor corresponding to an
outdoor ambient temperature, plus 17 degrees C."
Proposal 9-14
New Section 312.21
This proposed change introduces a new section to Article
312 that requires repairing of plaster, drywall, etc.,
around cabinets and cut-out boxes as well as boxes and
fittings similar to the requirements for boxes currently
contained in Section 314.21.
Proposal 9-50
Revision Section 314.20
Current provisions of the Code for supporting
boxes allow screws to be used as a supporting means.
This revision would identify the hazard of screws with
coarse threads that pass through the interior of the box
which may damage the insulation of the conductors. This
revision clarifies that screws used to support boxes
need to be installed so that the threaded portions are
not exposed to the inside of the box or are protected
from the conductors.
Proposals to CMP-7 and CMP-8 to remove the
"uses permitted" section from each article as
appropriate.
Apparent problems resulting from list formats in the
cable wiring method articles and the raceway wiring
method articles have resulted in the Technical
Correlating Committee assigning a task group to review
the issues and conflicts associated between "uses
permitted" and "uses not permitted"
within the articles and provide a recommendation to
resolve these issues. The overall recommendation from
the Usability Task Group to the panels by proposals is
to remove the "uses permitted" section and
revise the "uses not permitted" section within
each article as appropriate. The result of these
revisions would leave only a "uses not
permitted" section within each article and remove
the task of having to be inclusive with a list of
"uses permitted" for each article. The result
basically would be any applications of these wiring
methods not specifically limited by the "uses not
permitted" section of wiring method article would
be acceptable for use.
Proposal 9-85
Revision Section 404.8 (B)
A new sentence has been added to this section stating,
"A multipole general use snap switch shall not be
permitted to be fed from more than a single circuit,
unless listed and marked as a two-circuit or
three-circuit switch. The voltage to the same single
circuit snap switch shall not exceed 300 volts."
The same hazard of circuits exceeding 300 volts fed to
the same device exists as does voltages in excess of 300
volts for adjacent devices.
Proposal 18-41
Revision Section 408.8(C)
This revision provides additional clarity and more
specifically addresses locations where receptacles are
not permitted at bathtub and shower locations. The
change prohibits receptacles from being installed within
a bathtub or shower stall as well as over those
locations.
Proposal 18-61
Revision Section 410.15(B)
This proposed change recognizes nonmetallic poles for
the support of luminaires (lighting fixtures) such as
parking lot luminaires. Nonmetallic poles, such as
concrete poles, are becoming more common and this
revision expands the requirement to beyond those poles
of only the metallic types.
Proposal 17-24
Revision Section 422.31(B)
This revision provides a sentence to this section that
places additional restrictions on the provision for the
lockable means for the switch or circuit breaker used as
the disconnection means. The proposed change requires
the lockable means to be permanently installed on or at
the switch or circuit breaker which is also consistent
with similar provisions for motor disconnecting means in
430.102(B) Exception.
Proposal 11-7
Article 430 Change in Terminology
The term "full load amperes (FLA)" has been
changed to the term "full load current (FLC)"
to be consistent with the definition of ampacity in
Article 100. It is more appropriate that the term
current be used when describing loads, including motor
loads.
Proposal 11-16
New Part X
to Article 430
A new Part X has been added to Article 430 and is titled
"Adjustable Speed Drives." The revision
establishes a specific part of Article 430 to address
key installation rules for motor adjustable speed
drives. Existing provisions for adjustable speed drives
currently contained in 430.2 and 430.22 Exception No. 2
were relocated under this new part and other
installation requirements have been added as well.
Proposal 11-65
Revise Section 430.102(B)
The last sentence of 430.102(B) has been deleted. The
words "to be in sight from the motor and driven
machinery location" in the first sentence of the
exception have also been deleted. This revision
clarifies that a disconnect would not be required at the
motor if the conditions of either (a) or (b) of the
exception have been met. This revision is not intended
to eliminate the disconnect required within sight from
the motor and driven machinery location generally, as
currently required by the 2002 NEC.
Proposal 14-108(a)
New Article 506
This proposed new article would provide an alternative
method of addressing electrical installations in
atmospheres where fire and explosion hazards may exist
due to flammable dusts, fibers, and flyings. This
article would be an alternative to the requirements
presently contained in Articles 500, 502, and 503 for
electrical installations in these environments.
Proposal 14-111
Revision Section 511.3
This section has been rearranged for a more logical
order so that all requirements related to unclassified locations within commercial repair garages are located
in 511.3(A) and all requirements related to the classified locations are located in 511.3(B). Previously some
of the text in this section was located in exceptions
and some was located in Article 514.
Proposal 14-122
Revision Section 514.8
This proposed change eliminates the text that indicates
the space within the earth, below a classified area is a
Class I, Division I location. The definition of a Class
I location in Article 500 states that an ignitible
concentration of fuel and air must be present for a
classified location to exist. Raceways installed under
the classified location must continue to include a seal
where the raceway emerges from below grade. The space in
the earth below the classified location is unclassified
where the space does not include enough oxygen to reach
ignitible concentrations.
Proposal 15-42
Revise Section 517.30(C)(3)
The proposed revisions to this section would now permit
Types AC and MC cables for wiring methods for the
emergency system where normally a nonflexible wiring
method is required for mechanical protection. This
alternative wiring method in cable form is now permitted
to be installed in existing installations where it is
impractical to install a nonflexible metal raceway.
Proposal 19-7a
New Definition in Section 547.2
The term "site-isolating device" is unique to
Article 547 and is now defined as "a disconnecting
means installed at the distribution point for the
purposes of isolation, system maintenance, emergency
disconnection, or connection of optional standby
systems." Section 547.9(A)(1) in the 2002 NEC described the purpose of this device and was, in fact, a
definition of the term. This revision creates a
definition and places it in 547.2 to conform to NEC Style Manual requirements.
Proposal 19-12a
Revision Section 547.9
This revision incorporates various technical changes and
issues raised in proposals 19-14, 19-16, 19-17, 19-18,
19-19, 19-21, and 19-23. One key revision is the
site-isolating device is required to be pole-mounted.
Where the device is readily accessible at grade level it
must meet all of the provisions for service equipment,
including overcurrent protection and short-circuit
current ratings.
Proposal 19-154
The phrase "other than luminaires (fixtures)"
has been added to 604.6(A)(3) and a new Section
604.3(F). The proposed change clarifies that the
provisions of this section limiting length and size of
the flexible cords utilized in manufactured wiring
systems are not applicable to luminaires (fixtures).
Subsection F permits cord-connected electric-discharge
luminaires (fixtures) to be installed in accordance with
the requirements of Section 410.30(C).
Proposal 18-107
Changes to Article 600
This proposal combines revisions and new requirements
into Article 600. A new definition of "section
sign" would now be included in 600.2. A reference
is made to signs installed in hazardous (classified)
locations and a requirement to comply with the
applicable provisions and requirements of Chapter 5.
Additional language was accepted to provide
clarification that secondary wiring is required to meet
the requirements of Article 600, Part II. Another
proposal has also been submitted to revise and expand
the applicability of Part II of Article 600 from being
limited to just field-installed skeleton tubing
installations. See proposal 18-117 for more information.
Proposal 17-115
Revision Section 680.26
The title of Section 680.26 has been revised from
"680.26 Bonding" to "680.26 Equipotential
Bonding." The revision also inserts the word "equipotential"
into 680.26(A); the proposed revisions to this section
are intended to clarify the purpose of the bonding
required by this section is to "eliminate voltage
gradients in the pool area as prescribed" [see figure
2].
Proposal 17-154
New Article 682
This proposal introduces a new Article 682 to the NEC.
The title of the article would be "Natural and
Artificially Made Bodies of Water." The article
would initially be comprised of three parts as follows:
Part I – General
Part II – Installation
Part III – Grounding and Bonding
This proposed new article is the result of the work of a
CMP-17 task group to address the concerns for
requirements that cover electrical installations
associated with other bodies of water outside of the
scope of Article 680.
Proposal 16-9
New Definitions 770.2
Six proposed definitions of terms used in NFPA 90A have
been added to this section.
New terms are: air duct, ceiling cavity plenum, raised
floor plenum, duct distribution plenum, apparatus casing
plenum, and air-handling plenum.
Proposal 16-12
Revision Section 770.3
The proposed changes reflect a change in terminology
used to describe "other spaces used for
environmental air" to "other air-handling
spaces." The proposed revision recognizes Types
OFNP and OFCP cables for use in plenums, including
ceiling cavity plenums and raised floor plenums.
This proposal is consistent with several similar
proposals (see list of Code Sections below) to
revise the wording in each of the respective articles to
a common format.
Panel 3 - 300.22, 725.3, 760.3, 770.3, 725.61,
725.71, 760.30, 760.31, 760.61, 760.71, 770.51, and
770.53 (Panel 3 rejected initially).
Panel 16 – 800.8, 820.3, 830.3, 800.51, 800.52,
800.53, 820.51, 820.51, 820.52, 820.53, 830.5, 830.54,
830.55, and 830.58 (Panel 16 accepted initially).
Panel 8 – 392.4 (Panel 8 accepted initially).
Panel 15 – 518.4 (Panel 15 accepted initially).
Panel 12 – 640.3 (Panel 19 accepted initially).
Panel 19 – 604.4 (Panel 19 accepted initially).
These proposals have the objective of clarifying the
language used in the NEC and coordinating with
the language used in NFPA 90A-2002, The Standard for
Installation of Air-Conditioning and Ventilating
Systems. These proposals would remove the term
"other spaces used for environmental air-handling
purposes" and replace it with the following terms
as appropriate: ceiling cavity plenum, raised floor
plenum, air-handling plenum, etc. There are six
definitions of terms used to describe these spaces
proposed in proposal 16-9.
Proposal 16-70
Reorganization Articles 800, 820, and 830
These revisions reflect the work of a task group under
guidance from the TCC to reorganize these articles in a
more logical layout that is consistent and parallel
between the articles and is in concert with the
requirements of the NEC Style Manual.
The organization of the restructured article as proposed
is shown below:
Part I – GeneralPart II – Wires and Cables Outside
and Entering BuildingsPart III – ProtectionPart IV – Grounding MethodsPart V – Wires and Cables Within
Buildings
Part VI – Listing Requirements.
Michael J. Johnston
is IAEI’s director of education and an IAEI principal
member on CMP-5. Johnston was formerly employed as an
electrical field inspections supervisor for the city of
Phoenix, Arizona. He is fully certified in many areas.
He is a member of the IBEW. He achieved both journeyman
E-2 and master electrician E-1 licenses in the state of
Connecticut. Additionally, he holds all IAEI
certifications. He also holds ICBO Electrical
Inspections Certification. He is a member of the UL
Electrical Council.
|
|
|