|
| |
 |
| Figure
1 |
| Listing marks and SCGFP marks |
|
| Figure 2 |
| Neon transformers and power supplies are permitted above suspended ceilings where not supported by the ceiling grid system and appropriate access is provided to the transformer or supply |
|
| Figure
3 |
| Adequate working space at remote neon transformers and power supplies is required |
|
| Figure
4 |
| Connections of primary branch-circuit equipment grounding conductor and secondary circuit bonding conductor at transformer enclosure |
|
| Figure
5 |
| Transformer terminals indicating specific connection terminals for the grounded (neutral) conductor and the ungrounded (hot) conductor |
|
| Figure
6 |
| Transformer checklist diagram from Neon Lighting, page 230 |
|
|
|

IAEI
News>Issue Listing>September/October 2003>Installing and Inspecting Neon Transformers
| Installing and Inspecting Neon Transformers |
Neon signs and field-installed skeleton tubing installations require a transformer or power supply to step up the voltage to a high level that will cause ignition of connected neon tubing. |
|

Neon signs and field-installed
skeleton tubing installations require a transformer or
power supply to step up the voltage to a high level that
will cause ignition of connected neon tubing. This
transformer can be considered the "heart beat"
of the neon sign or outline lighting system. Recent
articles in the IAEI News have been written to
provide information relative to neon signs and neon
installations. This article will visit some of the
general requirements one must be aware of to properly
install or inspect a neon transformer or power supply.
Keep in mind that installation conditions can vary from
site to site. There are some important factors and
concerns involved with this type of installation that
require close attention. High voltages require increased
focus on insulation, spacing, and types of wiring
methods and products used. Specified minimum clearances
for high voltage conductors must be maintained.
Listing and Marking
Requirements
A good starting point is the identification and listing
marks required on the transformer or power supply. These
marks help give an indication that the products have
been evaluated by an electrical testing laboratory and
can assist in determining if the product is being used
properly. Neon transformers and power supplies are
required to be listed and suitable for an intended use.
If the transformer or supply is remote, it will be
field-installed, and the secondary wiring to the sign
copy will also have to be field-installed. Conformance
assessment and approval responsibility of the
field-installed transformer and secondary wiring rests
with the authority having jurisdiction. This applies not
only to field-installed systems but also to listed
section signs. If the sign is a listed section sign,
verify that each section of the copy (sign) and related
power supply or transformer(s) bears a listed section
sign mark. Listed section signs, what is covered under
that listing, and the field wiring inspection were
reviewed in detail in the May/June issue of the IAEI
News. [Figure
1]
Location of the transformer installation can have an
impact on the type of transformer enclosure required.
Transformers installed in wet locations, such as on a
roof, or on the inside of a parapet wall of a building
must be suitable for those locations or be installed in
suitable enclosures that provide adequate environmental
protection [NEC 600.21(C)]. There are
transformers and listed transformer enclosures
specifically for this purpose. Transformers and power
supplies generally are required to have
secondary-circuit ground-fault protection and they must
be so marked. This is a marking requirement of the Code and the applicable product standard [UL 2161;
600.23(F)]. Other important markings on the transformer
are the input and output (secondary) voltages and the
current ratings.
Location and
Accessibility
Locating the transformer or power supply is an inherent
part of effective design using ingenuity. The location
of the transformers is critical in the tube loading and
selection process. The Code addresses this
generally in requiring the transformer to be as near to
the lamps as practicable to keep the secondary
conductors as short as possible [600.21(B)]. Maximum
lengths are specified in the Code for neon
secondary circuits, which will be covered in the next
article in this series.
Another important aspect of the location is
accessibility. The transformer must be accessible for
the installer, the inspector, and service personnel.
Unlike the general requirement for standard building
power transformers, which are required to be readily
accessible, the neon transformer or power supply only
has to be accessible. Definitions can help one establish
the key difference between the two terms. Basically, the
neon transformer can be located in areas where it could
be accessed by ladders or other portable means. Service
and repair personnel see the benefits of properly
located transformers and power supplies and endure the
hardships of installations that do not provide proper
access or adequate working spaces for this type of
equipment.
The NEC includes requirements for adequate
working space about electrical equipment that is likely
to require examination, adjustment, servicing, or
maintenance while energized. Minimum working space is
generally 750 mm (30 in.) in width, and not less than
900 mm (3 ft) from the front of the equipment enclosure.
It is interesting to note that within Article 600
specific working space is required to be provided at
each ballast, transformer, or power supply or its
enclosure where it is not installed in a sign. Minimum
space to be provided is not less than 900 mm (3 ft) x
900 mm (3 ft) x 900 mm (3 ft). Where located in attics
or soffits, an access opening or door at least 900 mm (3
ft) x 600 mm (2 ft) is required to gain access (see figure
3). This is often the case in storefronts and above
show windows where the neon or sign is installed to the
front or fascia of the building. Sometimes a single
access door to these spaces is acceptable, but where the
transformers or power supplies are remote from the
access opening, suitable passageway and walkways are
required. This requirement of the Code is far
easier to comply with in new construction than in
existing buildings, but keep in mind the NEC does
not differentiate here. Electrical safety and safety of
the worker is important here [NEC 600.21(D) and
(E)].
Another popular location for remote neon transformers
and power supplies is above suspended ceilings. The
ceiling grid cannot be depended upon for support, which
means transformers and power supplies must be securely
fastened to the structure in another fashion. Cord- and
plug-connected transformers or power supplies are not
permitted above suspended ceilings (see figure 2).
Grounding and Bonding
Understanding grounding and bonding is essential to safe
neon installations. Grounding the equipment as required
establishes a reference to earth on the metal equipment
associated with the sign or outline lighting system.
This is accomplished when the equipment grounding
conductor with the branch circuit is connected to the
transformer or power supply. All metal parts associated
with the neon sign or outline lighting must also be
bonded together and connected back to the transformer
enclosure where the equipment grounding conductor of the
branch circuit is connected. This accomplishes two
tasks. It puts all metallic parts associated with the
sign at the same potential and bonds the metallic parts
and components to the equipment grounding conductor of
the branch circuit feeding the transformer. This, in
turn, puts the bonded metal parts at earth potential
(ground reference). Ungrounded metal parts or metal
parts that are not bonded and are located in close
proximities to high voltage secondary circuits can start
to rise in potential owing to capacitance coupling
effects. This can lead to potential shock hazards and
fire hazards that can result from tracking, etc. A
properly grounded and bonded system minimizes these
potential hazards and enhances overall electrical
safety. [Figure
4]
Proper Loading
The Code addresses the loading of neon
transformers in a general nature only. This is left as a
primary responsibility of the installer to ensure that
the design of the system is such that the right amount
of tubing is being supplied by the appropriate
transformer or power supply. Basically the length of
tubing, the diameter and type of gas used have to be
married to the appropriate transformer so that a
continuous overcurrent beyond the design loading of the
transformer will not result. Transformer manufacturers
can provide the tube footage charts for use in design of
these systems. Once again, this should be done in the
design and planning stages of a neon system installation
[NEC 600.41(A)]. There are occasions where the
inspector should verify that the proper transformer is
being used. A good indication that transformers are
underloaded or overloaded is a pattern of service
callbacks to keep replacing transformers that continue
to fail.
Connections to
Transformer
Connections are important parts of any electrical
installation. Generally, if failure is going to happen,
it usually starts at connection points or terminations.
It is rare for failures to start in the middle of a
conductor between terminals, but that is is not to say
it cannot happen. When the transformer is installed one
of the last steps prior to testing the system is
checking the connections at the transformer. Primary
branch-circuit connections and secondary connections are
required. In transformers within integral enclosures,
there are usually separate compartments for primary and
secondary connections. The integrity of the terminal
connections is important. Try to avoid loose connections
or connections with devices not intended for such use as
they will eventually spawn failure in the system. Where
the transformer is field-installed with a suitable
enclosure, both secondary and primary conductors are in
the same enclosure and attention must be focused on the
minimum spacing required between them. A minimum spacing
of 38 mm (1 ˝ in.) between each secondary conductor and
all other objects including the branch-circuit
conductors is required [NEC 600.32(E)]. Another
item to verify is the minimum length of insulation on
the conductor where it emerges from the raceway into the
enclosure. In damp and wet locations a minimum distance
of 100 mm (4 in.) is necessary, and a minimum of 65 mm
(2 ˝ in.), in dry locations. Suitable secondary
conductors should be used. Another important point to
verify is that proper polarity is maintained for the
primary connection to the transformer as many of the
secondary-circuit ground-fault protection units are
polarity sensitive (see figure
5). Many are marked to indicate the terminal
specifically for the grounded conductor, and some
transformers are also sensitive to being connected to a
multiwire branch circuit. A multiwire branch circuit is
one that includes two or three circuits that share a
common neutral conductor (see the definition of
multiwire branch circuit in Article 100). It is
important to follow the manufacturer’s installation
instructions and recommendations.
As with any electrical installation, there are unique
situations or conditions that will be encountered in the
field that are not specifically addressed in this
article. General requirements and more common elements
for field-installed transformers and electronic power
supplies have been provided. Also included in this
article is a helpful diagram and checklist for these
types of installations derived from Neon Lighting,
IAEI’s new book. [Figure
6] The checklist serves as a basis for installers
and inspectors and might not be totally inclusive.
Safe electric signs, neon, and outline lighting systems
are the desire of the installer and the inspector.
Working together and effective communication are the
keys to attaining safe neon installations. Education is
the key to understanding these systems and installations
and to becoming more capable of properly applying Code rules to them. The next article in this series provides
a review of the secondary conductor installations and
wiring methods from the transformer output hubs to the
tubing electrodes.
Michael J. Johnston is IAEI’s
director of education and an IAEI principal member on
CMP-5. Johnston was formerly employed as an electrical
field inspections supervisor for the city of Phoenix,
Arizona. He is fully certified in many areas. He is a
member of the IBEW. He achieved both journeyman E-2 and
master electrician E-1 licenses in the state of
Connecticut. Additionally, he holds all IAEI
certifications. He also holds ICBO Electrical
Inspections Certification. He is a member of the UL
Electrical Council.
|
|
|