Sign In  |  Register Now  Why Register?

 
 

 
Featured Images
No images.


 

 
IAEI News>Issue Listing>September/October 1998>UL Question Corner    
UL Question Corner
I've noticed that the color, size, and visibility of exit signs varies greatly. Do UL requirements permit these variances? 
The “UL Question Corner” answers questions of general interest that are sent in from authorized government inspectors and we believe will have interest for many inspectors.
by Underwriters Laboratories


Question
I've noticed that the color, size, and visibility of exit signs varies greatly. Do UL requirements permit these variances?       

Answer:  UL listed exit signs must meet the requirements outlined in UL 924, the Standard for Emergency Lighting and Power Equipment. These fixtures are intended for installation in accordance with the National Electrical Code, ANSI/NFPA 70, and the Life Safety Code, ANSI/NFPA 101. Some of the listing requirements are as follows. 

Color — Typical exit sign letters are red, but UL also lists signs with green lettering. The requirement for a specific color may be included in state or local codes, but UL has no color requirements. 

Letter Size—UL 924 requires that exit sign letters be at least 6 inches high. The 6-inch tall letters must be 2 inches wide (except for the 1): the stroke width must be 3/4 inch, and the spacing between the letters 3/8 inch. For larger signs, the letters must increase in size proportionally, to make them legible from a distance.

Luminance— The luminance specified in UL 924 and NFPA 101 is 0.06 ft. lamberts. This is based on research conducted by UL and industry in the mid-1970s that compared the visibility of internally illuminated signs and signs with self-contained energy sources.

Viewing Distance—All exit signs are evaluated for a viewing distance of 100 feet, based on the requirements in NFPA 101. In UL924, there are two tests that determine compliance with these viewing distance requirements—UL's analytical luminance visibility test conducted on a photometer and a 100-foot observation visibility test. An exception to this rule allows manufacturers to request that their self-luminous or electroluminescent exit signs be tested at 50, 75, or 100 feet. UL would require these signs to be marked with the legible viewing distance.

Self-luminous Materials—Self-luminous signs are powered continuously by a self-contained energy source, other than a battery. An example is radioactive tritium gas. Because this gas has a limited life expectancy, UL requires a replacement date to be marked on the sign. This date must be visible after installation.

Photoluminescent Materials—Since photoluminescent materials require exposure to light for activation of their luminescent properties and have a limited life expectancy, they may be used only in combination with other methods of illumination.

Floor Proximity Egress Path Marking Systems—These path marking systems are intended for indoor installation in low level locations on floors, or on walls at or near the floor, to provide a clearly marked path of escape during emergency situations. Photoluminescent materials may be evaluated for their suitability as a floor proximity marking system in accordance with UL 1994, the Standard for Low Level Marking and Lighting Systems.

Exit Fixture Retrofit Kits—Exit fixture retrofit kits consist of parts and/or subassemblies intended for field installation in listed exit fixtures. They are intended to convert the light source of an exit fixture, i.e. incandescent to fluorescent.

The names of listed exit sign manufacturers appear in the product category Exit Fixtures (FWBO) in the Electrical Construction Materials Directory (Green Book). The guide card listing information also appears in the General Information Directory (white book). Exit fixtures are evaluated for installation at or near a ceiling or above a door, unless marked for use at floor level. Exit fixtures that are suitable for use at floor level have been subjected to additional tests for mechanical abuse. Exit fixtures should not be confused with "exit markers," which are products that are UL classified for use in listed floor proximity egress path marking systems.


Question
For outlet boxes that support ceiling suspended fans, does UL consider out-of-balance fans?

Answer: Section 422-18(a) of the 1996 National Electrical Code permits "listed" ceiling fans that do not exceed 35 lbs. to be supported by outlet boxes identified for such use. Ceiling fans exceeding 35 lbs. are required to be supported independently of the outlet box, in accordance with Section 422-18(b).

Requirements for ceiling-suspended fan support for metallic outlet boxes are located in UL 514A, the Standard for Metallic Outlet Boxes. For nonmetallic boxes, the requirements can be found in UL 514C, the standard for Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers. Both of these standards specifically include testing of the boxes using out-of-balance fans.

For the ceiling-suspended fan support test, a ceiling fan (weighing or ballasted to weigh 35 pounds) is installed in accordance with the manufacturer's installation instructions. Samples are tested in both the horizontal position and at an incline of 30 degrees. A 40 gm (1.4 oz) weight (imbalance) is placed on a single fan blade and a rigid-metal pipe is connected to position the lower edge of the fan blade 12 inches from the ceiling. The fan is operated at a specified speed for 24 hours to simulate an unbalanced fan and then the outlet box is examined for damage. Next, one of the fan mounting screws is loosened two full turns, and the fan is operated for an additional 24 hours.

A UL listed outlet box intended to support a ceiling-suspended fan is required to be marked "Acceptable for Fan Support."


The special UL meetings for government inspectors provide us an excellent opportunity to ask questions of UL engineers and to clarify UL requirements. The "UL Question Corner" answers questions of general interest that are sent in from authorized governmental inspectors and we believe will have interest for many inspectors.

Please send us questions you may have that are of general interest, and we will have UL engineers answer them in a future issue. If space does not permit answering all questions received, we’ll see that you get an answer by letter. Send your questions to:

UL Question Corner - IAEI News
PO Box 830848
Richardson, TX 75083-084

 

 

 
Multi-Occupancy Buildings
 

 

 

 

 

Home  | Join | Advertising | Seminars | Contact Us | Privacy Statement | Legal Notices
Copyright © 1997-2008 IAEI. All Rights Reserved.

 

 

 

Current Issue Home Page Issue Listing Series Focus on the Code Reprints Contacts Subscribe