Sign In  |  Register Now  Why Register?

 
 

 
Featured Images
Figure 1
Consider what would happen if a cable failure occurred, as in Figure 1, with the engine generator not grounded to its own grounding electrode

Figure 2
However, ground-fault currents may trip the normal source breaker when the load is connected to the engine generator set. See diagram in figure 2

Figure 3
As shown in figure 3, ground-fault sensing on the emergency side is often used for actuating an alarm circuit rather than tripping a breaker

Figure 4
Figure 4 illustrates a typical system with multiple three-pole transfer switches.
 
 


 

 
IAEI News>Issue Listing>July/August 1999 >Grounding of On-Site Electrical Power Systems
Grounding of On-Site Electrical Power Systems
This article applies to low-voltage power systems rated 600 volts and less, and explains types of grounding, fault protection, code requirements, and appropriate solutions. The interrelationship of ground, ground-fault sensing and transfer switching is discussed.

by Rene Castenschiold, P.E. and Gordon S. Johnson, P.E.         


Abstract-This paper is based on the new grounding chapter in the recently published third edition of On-Site Power Generation: A Reference Book. [1] It applies to low voltage power systems rated 600 volts and less, and explains types of grounding, fault protection, code requirements, and appropriate solutions. The interrelationship of grounding, ground-fault sensing and transfer switching is discussed. The importance of safety to personnel, protection of equipment and continuity of power to electrical loads is stressed.

For optimum safety of personnel, protection of equipment and continuity of power to electrical loads, proper grounding of on-site power systems is essential. If the on-site power is the sole source of power, then its grounding is relatively straight forward and follows the National Electrical Code Article 250. However, if the on-site power system serves an alternate source of power (i.e., emergency or standby power), then grounding of the system becomes more complex. Furthermore, portable and mobile generators have special grounding requirements.

Special consideration should be given to location of ground connections, means of minimizing circulating ground currents and providing proper ground-fault sensing. This paper discusses recommended practices for both system and equipment grounding without detracting from the ability of alternate power sources to provide reliable emergency power. It also provides some design guidelines in selecting transfer switching equipment, as necessary to meet code requirements and assure proper system grounding.

There are unique circumstances relating to emergency power systems that require special grounding considerations. In large building complexes, consideration should be given to possible power disruption within the facility and the need for area protection. At the same time, due consideration should be given to effects of multiple ground connections, proper sensing of ground faults and conformance to current code requirements.

Electrical power systems require two types of grounding; namely, system grounding and equipment grounding. As will be shown, each has its own function.

II. SYSTEM GROUNDING
System grounding pertains to the nature and location of an intentional interconnection between the electric system conductors and grounding electrode systems which provide an effective connection to ground (earth). In other words, it relates to how and where the grounded conductor is connected to earth.

Purpose of System Grounding: According to Section 250-2 of the National Electrical Code (NEC), system and circuit conductors are grounded to limit voltages due to lightning, line surges, or unintentional contact with higher voltage lines, and to stabilize the voltage to ground during normal operation. Systems are solidly grounded to facilitate overcurrent device operation in case of ground faults.

Power Systems: The following emergency power systems are commonly used to supply phase-to-neutral loads and should be solidly grounded:

120/240 volt, single-phase, three-wire system

208Y/120-volt, three-phase, four-wire wye system

480Y/277 volt, three-phase, four-wire wye system

600/347 volt, three-phase, four-wire wye system

240/120 volt, three-phase, four-wire delta system

Solidly Grounded Systems: To facilitate overcurrent device operation the equipment grounding conductors for solidly grounded systems are required to be bonded to the system grounded conductor at the service equipment and at the source of a separately derived system (standby or emergency power). This bond completes the ground-fault current return path from the equipment grounding conductors to the system grounded conductor. System grounding conductors and grounding electrodes are not intended to conduct the ground-fault current that is due to a ground-fault in equipment, raceways, and other enclosures. In solidly grounded systems, the ground-fault current flows through the equipment grounding path.

Solidly grounded systems exercise the greatest control of overvoltages but result in the highest magnitudes of ground-fault current. However, the inherent regulation of alternate source generators generally limits the available fault current. If line-to-neutral loads must be served, high resistance grounding of the generator neutral is not permitted because the neutral should never be used as a circuit conductor in systems that are grounded through a high resistance.

High Resistance Grounding: Where line-to-neutral loads need not be served, there is a growing trend toward high-resistance grounding of the neutral conductor. This is particularly true in industrial applications and where medium voltage generators are used for emergency power. High resistance grounding combines the advantages of ungrounded systems and solidly grounded systems. Fault current is limited to a value that will permit continued operation of the emergency power system until the normal power is restored. System overvoltages are held to acceptable levels and faults are easier to locate than on an ungrounded system. For these reasons, high resistance grounding is often used in process industries where an unscheduled outage can have serious consequences.

III. EQUIPMENT GROUNDING
It is important that all exposed metallic parts of electrical equipment be bonded to a grounding electrode. This includes metallic parts such as generator frames and engines of engine generator sets, mounting bases, electrical conduit and enclosures.

Purpose of Equipment Grounding: The purpose of equipment grounding is to assure the following functions:

1. To maintain a low potential difference between nearby metallic members and thereby protect people in the area from electric shock.

2. To facilitate the operation of circuit protective devices by providing low impedance conducting paths for ground-fault currents.

3. To provide an effective electrical conductor system over which ground-fault currents can flow without creating a fire or explosive hazard.

Equipment Grounding Paths: Only by providing adequate equipment grounding paths for metallic enclosures, frame of an engine generator set, etc., in a manner which assures adequate current-carrying capability, and an adequately low-value of ground-fault circuit impedance, can both electric shock hazard and fire hazard be avoided. Technical investigations have pointed out that it is important o have good electric junctions between sections of conduit or metal raceways that are used as equipment grounding paths, and to assure adequate cross-sectional area and conductivity of these grounding paths. Where systems are solidly grounded, equipment grounding conductors are bonded to the system grounded conductor and the grounding electrode conductor at the service equipment and at the source of a separately derived system in accordance with the requirements of Sections 250-30, 250-64 and 250-130 of the National Electrical Code (NEC).

The same network of equipment grounding paths is required for systems that are solidly grounded, high resistance grounded, or ungrounded. The equipment grounding paths in high-resistance grounded or ungrounded systems provide shock protection and a conducting path for phase-to-phase fault current if two ground faults occur simultaneously on different phase conductors.

Engine Generator Frame: The engine generator frame, automatic transfer switch enclosure, conduits and other exposed components of an emergency power systems should be permanently bonded together and connected to the grounded conductor of the service equipment providing normal power and/or the grounded conductor of the engine generator set. By means of grounding electrode conductors, these grounded conductors are connected to grounding electrodes at their respective locations.

The National Electrical Code permits the grounding electrode to be a metal underground water pipe which may be part of a municipal water piping system or a well on the premises. However, buried portion of a water pipe system less than 10 feet in length or that may include plastic or cement materials should not be used. For small emergency power systems where the ground currents are of relatively low magnitude, existing buried water pipe systems are usually preferred as electrodes because they are economical in first cost. Nevertheless, before reliance can be placed on any existing electrodes, it is essential that their resistance to earth be measured to insure that some unforeseen discontinuity has not seriously affected its suitability. Also, care should be exercised to insure that all parts which might become disconnected are effectively bonded with flexible bonding jumpers. Larger emergency power systems in industrial and commercial buildings often use the effectively/grounded metal frame of the building and concrete-encased metal below ground level as a grounding electrode. The concrete encasement of steel, in addition to contributing to low grounding resistance, serves to provide some measure of corrosion protection compared to direct contact with the earth. Due consideration must also be given to the ampacity of the equipment grounding path in order to handle the higher available ground-fault current.

Another alternative is to use “made” electrodes such as driven electrodes, buried cables and plates. The type selected will depend upon the type of soil encountered and the available depth. Although the National Electrical Code permits up to 25 ohms resistance to ground for “made” electrodes, grounding electrodes for engine generator sets in industrial and commercial installations should be kept to a minimum and preferably below five ohms. Where the building steel is bonded to the ground grid system as well as most pipelines, it is not unusual to obtain an impedance as low as 0.1 to 0.2 ohms. Although the National Electrical Code requires only one electrode, sometimes more than one is necessary.

Another reason for positive grounding is that the radio frequency noise suppressors in some generators are connected to the engine generator frame. Inadequate frame grounding can result in interference to communication or audio equipment and improper operation of electronic governors. If the engine generator set is mounted on flexible or resilient pads, a flexible bonding jumper must be used.

Supplemental Equipment Bonding: Possibility of electrical shock can be reduced by additional supplemental equipment bonding between the conductive enclosures for conductors and equipment and adjacent conductive materials. This additional equipment bonding helps minimize any potential between exposed noncurrent-carrying metal parts of the electric system and adjacent grounded building steel when ground faults occur. The inductive reactance of the ground-fault circuit will normally prevent a significant amount of ground-fault current from flowing through the supplemental bonding connections.

Ground-fault current will flow through the path that provides the lowest ground-fault circuit impedance. The ground-fault current path that minimizes the inductive reactance of the ground-fault circuit is through the equipment grounding conductors that are required to run with or enclose the circuit conductors. Therefore, practically all of the ground-fault current will flow through the equipment grounding conductors, and the ground-fault current through the supplemental bonding connections will be no more than required to equalize the potential at the bonding locations.

IV. GROUND-FAULT SENSING AND PROTECTION
Providing reliable ground-fault protection in electrical systems having alternate emergency or standby power can be difficult unless adequate equipment is selected and properly coordinated. Multiple neutral-to-ground connections may prevent adequate sensing of ground fault currents and may also cause nuisance tripping of circuit breakers. To assure proper ground-fault protection, understanding the evolution of code requirements can be helpful.

National Electrical Code: Prior to 1971, most automatic transfer switches for three-phase four-wire systems had three poles with no provisions for switching the neutral conductor. The neutral conductor was grounded at both sources of power. When ground-fault protection of equipment became a requirement in 1971 (NEC Section 230-95), application problems began to appear in new emergency and standby power system installations. The problems dealt primarily with obtaining proper sensing of ground-fault currents because of multiple neutral-to-ground connections. Under some conditions, the ground-fault sensors would fail to detect fault currents. Under other conditions, unbalanced loads would cause ground-fault sensors to trip breakers, even though a ground fault or short-circuit did not exist.

Becoming aware of the above problems, the National Fire Protection Association (NFPA) decided to form a technical committee (including coauthors Rene Castenschiold and Gordon Johnson) to recommend changes to the NEC. At that time, the 1975 NEC included the following:

1. Section 230-95 stated, “Ground-fault protection of equipment shall be provided for solidly-grounded wye electrical services of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase for each service disconnecting means rated 1000 amperes or more.”

2. Section 250-5(d) stated, “A premises wiring system whose power is derived from generator, transformer, or converter windings and has no direct electrical connection to supply conductors originating in another supply system.”

3. Section 445-1 stated, “Generators and their associated wiring and equipment shall be considered to be separately derived systems and shall comply with the applicable provisions of Articles 230, 250, 700, and 750.

The technical committee made recommendations (not unanimously, however) which resulted in the following two changes in the 1978 NEC:

1. The definition for separately derived systems per Section 250-5(d) was changed by adding the phrase “including a solidly-grounded circuit conductor” and to read as follows: “A premises wiring system whose power is derived from generator, transformer, or converter windings and has no direct electrical connection, including a solidly grounded circuit conductor, to supply conductors originating in another supply system…”

(Note-this definition was removed from Article 250 in the 1999 NEC, but retained in Article 100.)

2. Section 445-1 was changed by deleting the phrase requiring generators to be considered as separately derived systems. The section now reads as follows: “Generators and their associated wiring and equipment shall comply with the applicable provisions of Articles 230, 250, 700 and 750.”

Effects of the Above Changes: The net effect of the 1978 code changes was that an alternate power source, such as engine generator set, could no longer be interpreted as a separately derived system if its neutral conductor is directly connected with the neutral of the normal source of power.

An emergency source could now only be considered to be a separately derived system and have its neutral termination separately grounded when the associated transfer switch provided switching of the neutral conductor. In order to comply with the new definition for separately derived systems, grounding of the engine generator’s neutral conductor could therefore only be done by one of two methods.

1. Permanently ground the neutral conductor of the emergency source generator at only the grounding electrode of the incoming service for the normal utility source. There would be no switching of the neutral conductor, and the emergency source would not therefore be considered a separately derived system. It later became apparent that this method did not resolve all ground-fault sensing problems.

2. Permanently ground the neutral conductor of the emergency source generator at its location. This would require transfer switching of the neutral conductor, and the emergency source would be defined as a separately derived system.

Additional Code Changes: For emergency power systems the 1984 NEC added Section 700-7(e) requiring sensing and indication of ground-fault currents under certain conditions when the engine generator set(s) is feeding the load. In subsequent NEC editions this requirement is identified as 700-7(d). To accomplish this properly it is necessary for the emergency source to be a separately derived system. The 1993 NEC added Section 700-8 requiring a sign to identify all sources connected to a grounding electrode when it is remote from the engine generator set(s). Article 250 in the 1999 NEC was completely rewritten.

V. TRANSFER SWITCHING
There are three approaches to consider in meeting the current requirements of the National Electrical Code. For a three-phase 4-wire grounded system, they include (1) using a 3-pole transfer switch with the engine generator set considered as a non-separately derived source, (2) using a 4-pole transfer switch with the engine generator set considered as separately derived source, and (3) using a 3-pole transfer switch with overlapping neutral contacts with the engine generator set considered as a separately derived source. However, just meeting the minimal requirements of the code does not necessarily provide the degree of reliability needed for a good emergency power system. The system designer should consider the following:

An engine generator set is often remotely located from the grounded utility service entrance and the ground potentials of the two locations may not be the same. Good engineering practice requires the automatic transfer switch to be located as close to the load as possible to provide maximum protection against power failure due to cable or equipment failures within the facility (area protection). Thus, the distance of cable between incoming service and the transfer switch and then to the engine generator set may be substantial. Consider what would happen if a cable failure occurred, as in Figure 1, with the engine generator not grounded to its own grounding electrode. The load would be automatically transferred to an ungrounded emergency power system. This, in turn, could jeopardize emergency service continuity and possibly lead to additional failures. Concurrent failure of equipment or cable failure (break-down between line and equipment ground) after transfer to emergency may not be detected. Thus the generator frame may approach line potential, causing a substantial voltage difference between the generator frame and the grounded conductor (neutral).

Some local codes require ground-fault protection while the engine generators is operating. This may present a sensing problem if the neutral conductor of the generator is not connected to a grounding electrode at the generator site and proper isolation of neutrals is not provided. Furthermore, some local and state codes (Pennsylvania and Massachusetts) require area protection which may crate additional problems unless the neutral conductor of the generator is isolated and grounded at the generator location.

When the transfer switch is in the emergency position, other problems may occur if the engine generator set is not properly grounded. For example, a ground-fault condition could cause nuisance tripping of a normal source ground-fault circuit breaker even though load current is not flowing through the breaker. This would prevent automatic retransfer to the normal source and isolation of the fault condition. This would not be in accord with Section 230-95 of the National Electrical Code which since 1978 states, “Where ground-fault protection is provided for the service disconnecting means and interconnection is made with another supply system by a transfer device, means or devices may be needed to assure proper ground-fault sensing by the ground-fault protection equipment.” Furthermore, both the normal neutral conductor and the emergency neutral conductor would be simultaneously vulnerable to the same ground-fault current. Thus a single fault could jeopardize power to critical loads even though both utility and emergency power are available. Such a condition may be in violation of codes requiring independent wiring and separate emergency feeders.

Three Pole Transfer Switching: Using three pole transfer switches is the least expensive approach and requires less space. However, ground-fault currents may trip the normal source breaker when the load is connected to the engine generator set. See diagram in figure 2. Furthermore, use of 3-pole transfer switches does not provide area protection within the facility and this could lead to an ungrounded power system in the event of cable failure. See diagram in figure 1. Finally, with the neutral conductor connected to the incoming normal service, it is difficult to provide ground-fault sensing on the emergency side as required to meet Section 700-7(d) of the National Electrical Code.

Four Pole Transfer Switching: A better solution is to use a four pole transfer switch which provides complete isolation of service and generator neutral conductors. This eliminates possible improper ground-fault sensing and nuisance tripping caused by multiple neutral-to-ground connections. When this is done the generator will comply with the current National Electrical Code definition of a separately derived system. With the neutrals thus isolated, ground-fault protection with conventional sensors can be added to the generator output.

Four pole transfer switches have been satisfactorily applied on applications where the loads are passive and relatively balanced. However, unbalanced loads may cause abnormal voltages for as long as 10 to 15 milliseconds when the neutral conductor is momentarily opened during transfer of the load. Transfer switches are frequently called upon to operate during total load unbalance caused by a single phasing condition. Inductive loads may cause additional high transient voltages in the microsecond range. Furthermore, it should be remembered that the contacts of the fourth switch pole do interrupt neutral currents and are, therefore, subject to arcing and contact erosion. However, contact erosion of the fourth pole can be minimized if the fourth pole is designed to open last (after the three other poles interrupt the load current) and make first without contact bounce. In any event, a good maintenance program must reaffirm at intervals the integrity of the fourth pole as a current-carrying member with sufficiently low impedance.

Both the National Electrical Code and Underwriters Laboratories, Inc., recognize the use of four pole transfer switches for 3-phase, 4-wire systems. In some European countries, including Germany and France, it is mandatory to use 4-pole switching devices.

Overlapping Neutral Contacts: Another method for isolating the normal and emergency source neutrals is for a 3-pole automatic transfer switch to include overlapping neutral transfer contacts. This feature provides the necessary isolation between neutrals and at the same time minimizes abnormal switching voltages. By means of overlapping contacts, the only time the neutrals of the normal and emergency power sources are connected together is during transfer and retransfer. With a sole-switch, this duration can be less than the operating time of the ground-fault sensor which is usually set anywhere from 6 to 24 cycles (100 to 400 milliseconds).

Figure 3 shows a typical system utilizing a three-pole transfer switch with overlapping neutral transfer contacts for isolating the neutral conductors. Note that there is no possible flow of fault current through the neutral conductor that would detract from or effectively reduce ground-fault detection. Furthermore, there is no possible flow of unbalanced current through the generator neutral to alter the response level of the ground-fault sensor and possibly cause nuisance breaker tripping. As with four pole transfer switches, conventional ground-fault sensing can be readily added to the emergency side. As shown in figure 3, ground-fault sensing on the emergency side is often used for actuating an alarm circuit rather than tripping a breaker, such as required per Section 700-7(d) of the National Electrical Code.

With overlapping neutral transfer contacts, the load neutral is always connected to one source of power. In that there is no momentary opening of the neutral conductor when the transfer switch operates, abnormal and transient voltages are kept to a minimum. Another advantage is that, there is no erosion of the overlapping contacts due to arcing, thus assuring current-carrying integrity and no increase in impedance of the neutral circuit. It should be noted that a 3-pole transfer switch with over lapping neutral contacts should not be specified as a 4-pole switch, according to Underwriters Laboratories Standard UL-1008 and the National Electrical Code. [4] [2]

Selecting Transfer Switching Equipment: For three-phase, four-wire systems involving one transfer switch and one engine generator set, response to the questions in Table 1 serve as a guide in selecting the type of transfer switch needed for a particular application.

Table 1

Questions                                        Yes                   No

a. Is the application for emergency power per Section 700 of the National Electrical Code?

b. Is the incoming service of the normal source rated 1000 amperes or more?

c. Is the service a solidly-grounded wye that is rated more than 150 volts to ground?

d. If the engine generator set is located remote from the normal incoming service, is area protection required?

e. Is sensing and alarm indication of a ground fault on the emergency or standby source required?

 

If the response to the first three questions (a, b, and c) are all “yes,” it is necessary to use a 4-pole transfer switch or a 3-pole transfer switch with overlapping neutral contacts in order to satisfy the requirements of the 1999 National Electrical Code. If the answer is “no” to any one of these questions, then proceed with questions d and e.

If the response is “yes” to either question d or e, use a 4-pole transfer switch or a 3-pole transfer switch with overlapping neutral contacts in order to satisfy the requirements of the National Electrical Code. If the answer is “no” to both questions, a less expensive 3-pole transfer switch without overlapping neutral contacts can be used. Then the neutral terminal of the generator should be grounded at the incoming service of the normal source.

Although the above questions apply to three phase four wire systems, the same approach can be taken for single phase three wire systems to determine the transfer switching equipment. However, most single phase systems are 400 amperes or less, and therefore can be satisfied with 2 pole transfer switches. It should be kept in mind that the above selection approach only applies to applications with one engine generator set and one transfer switch.

VI. OTHER CONSIDERATIONS
Because of the variety of emergency and standby power systems, it is not always feasible to provide fixed recommended practices. Each installation should be evaluated and designed to satisfy specific load, customer and code requirements. Examples of other special conditions are as follows:

Multiple Transfer Switches: Multiple transfer switches, located close to the loads, are often used rather than one transfer switch for the entire load. In such cases, consideration should be given to the possibility of cable or equipment failure possibly causing an emergency or standby power system to become ungrounded. This is particularly important if a solidly interconnected neutral conductor is grounded at the service equipment only.

Under such conditions, there is a possibility of tripping the ground-fault circuits when on ground fault exists. Figure 4 illustrates a typical system with multiple three-pole transfer switches. When power is supplied from the normal source of the load through a transfer switch the neutral current will divide between two neutral conductors. Some of the current will return by the normal return path. The remainder of the current will flow to the neutral terminal of the engine generator and through the neutral conductor of the other transfer switch to the normal source. This can cause tripping of either ground-fault circuit breaker even when no ground-fault exists. The problem can be corrected by the use of the three-pole transfer switches with overlapping neutral or four-pole transfer switches.

Multiple Engine-Generator Sets: When multiple engine-generator sets are connected in parallel and serve as a common source of power, each generator neutral is usually connected to a common neutral bus within the paralleling switchgear which, in turn, is grounded. The associated switchgear containing the neutral bus should be located in the vicinity of the generator sets. A single system-grounding conductor between the neutral bus and ground simplifies the addition of ground-fault sensing equipment.

It may be argued when individual grounding resistors are used, circulation of harmonic currents between paralleled generators is not a problem, since the resistance limits the circulating current to negligible values. However, if third harmonics are suppressed in the engine-generator sets, circulating currents are usually not a problem.

Engine generator sets which are physically separated and used for isolated loads may necessitate additional neutral-to-ground connections. By using multiple four-pole transfer switches or three-pole switches with overlapping neutral contacts, proper isolation and ground-fault sensing can be obtained.

Lightning Protection: Protection from power failures caused by lightning storms is a prime purpose for providing emergency power systems. It, therefore, seems only logical that the emergency power system be properly protected against lightning. Particular concern should be given to buildings housing emergency power equipment that are constructed of minimal nonconducting materials. When engine generator sets are installed on roof tops, additional consideration may have to be given to the installation of surge arrestors and grounded metallic masts.

Since lightning currents (direct or through arresters) may flow through various equipment ground components, the connection to earth is a most important part of the equipment ground system. Arrester grounds which are normally secured by driven ground rods near the arrester should not exceed 5 ohms.

A grounding reactor is sometimes preferred in medium voltage applications where the feeders from the generators are exposed to lightning surges (overhead power line). For the low frequencies (50 and 60 Hz), the reactor forms a low impedance to ground. For the lightning and switching surges, which are high frequency, the reactor forms a higher impedance thus limiting the current without allowing the high overvoltages associated with an ungrounded system. However, it should be kept in mind that the neutral cannot be used as a circuit conductor where the system is grounded through an impedance. Damage to structures and equipment due to surge effects is a subject in itself, and protection against this type of damage is not within the scope of this paper. For additional information and references, see Chapter 3 of IEEE Standard 142-1991 (Green Book). [3]

Mobile Engine Generator Sets: Though somewhat more difficult, proper grounding of mobile engine generator sets is extremely important. The mobility of such equipment often precludes the installation of a predesigned ground mat such as might be employed as a fixed installation. The portable equipment must be designed and grounded to permit personnel to approach (and touch) the apparatus without risk of dangerous electric shock.

Providing sensitive fast operating ground-fault protection with mobile engine generator sets provides additional protection. Switching devices or connectors should not be installed in the grounding conductor which may be subject to loss of conductivity. Grounding of the engine generator frame and vehicle chassis should be positive and thoroughly tested prior to engine starting.

Plate electrodes are sometimes used for grounding mobile engine generator sets. In addition to the minimum requirements of Section 250-52(d) of the 1999 National Electrical Code, the following conditions are recommended: [5]

1. 1.5 square feet of the plate surface should be below the surface and a linear distance of at least one (1) foot is common to earth and air above the earth.

2. The electrode should be located within a distance of no more than three (3) feet from the exterior surface of the generator set.

3. The electrode should be exposed to rain or moisture at least to the same degree as is the housing or exterior metal surfaces of the generator set.

Connection to the plate electrode would be in addition to a solid connection to the equipment grounding conductor of the facility or building to which the mobile power is being served. There is no restriction on the number of grounding electrodes conductors or electrodes that may be used. The more the better from a safety standpoint.

Small Portable Generator Sets: Grounding small portable generator sets presents a different problem. It is often impractical at construction and similar sites to ground the generator set. Section 305.6(a) Exception 1 of the National Electrical Code permits leaving such sets ungrounded as long as the only loads are connected to receptacles mounted on the generator set. The code does require that such sets have GFCI (ground-fault circuit interrupters) for personnel protection either on the receptacles or the extension cord, and as with all electrical equipment an equipment ground system be used. An exception (Section 305.6(a) Exception No. 1) to the GFCI requirement is allowed for 120 volt two wire sets, not over 5 kW, that has both its electrical connectors insulated from ground.

Generator Sets Mounted in Vehicles: Section 250-34(b) of the National Electrical Code does permit the frame of a vehicle to serve as the grounding electrode for a system supplied by a generator located on a vehicle, provided that:

1. The frame of the generator is bonded to the vehicle frame, and

2. The generator supplies only equipment located on the vehicle and/or cord-and-plug-connected equipment through receptacles mounted on the generator, and

3. The noncurrent-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the generator frame, and

4. The system complies with all other provisions of Article 250 of the National Electrical Code.

Using the frame of a vehicle as the grounding electrode is practical when the generator is the sole source of power, particularly if other grounding means are not readily available. However, if the generator serves as an alternate source of power (i.e., emergency or standby power), then grounding as explained above for mobile engine generator sets may be more appropriate. This would assure solid grounding of the generator frame to equipment grounding conductors of the facility or building to which the mobile power is being served. Furthermore, ground-fault sensing and whether or not the generator set is to be considered as a separately derived source are factors to consider. In either case, it is important that the frame of the generator is bonded to the vehicle frame.

Upgrading Transfer Switching Equipment: Upgrading older transfer switch equipment to present codes and standards can be a real challenge, particularly for larger and more complex industrial and commercial facilities. Awareness that three-pole transfer switches may not always provide complete isolation and proper ground-fault sensing has not been too apparent in the past. With more emergency and standby power systems being updated, the concern regarding safety and product liability should not be treated too lightly. This concern provides another reason for upgraded installations to include adequate grounding and preferably new transfer switches that provide switching of the neutral conductor. Regardless of whether or not ground-fault sensing is required, proper switching of the neutral conductor is good engineering practice because of the system isolation, improved grounding and the extra safety it can provide. [6]

There are a number of factors that should be considered when grounding on-site power systems. Simply conforming to minimum code requirements will not necessarily assure the degree of reliability required for such systems. Thorough consideration should be given to protecting against power disruption within the building or facility, and providing adequate ground-fault protection. Techniques for both equipment grounding and system grounding should be such as to provide optimum safety and assure maximum continuity of power to essential loads. This includes proper grounding and ground-fault sensing when the transfer switch is in the emergency position as well as the normal position. Grounding instructions provided by the manufacturer of the equipment should be followed.

As a general rule, most applications requiring ground-fault sensing, area protection, multiple transfer switches, or multiple engine generator sets, the on-site power should be considered as a separately derived system. In such cases the neutral of the engine generator set is grounded at its location.

It is not intended for the scope of this paper to cover in detail all aspects of grounding on-site power systems. Those requiring more detailed information may find the following list of references helpful.

REFERENCES
[1] EGSA On-Site Power Generation: A Reference Book. Third Edition. Electrical Generating Systems Association, Coral Springs, FL (edited by coauthor Gordon Johnson)

[2] National Electrical Code, NFPA No. 70-1999. National Fire Protection Association, Quincy, MA

[3] IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems (Green Book), Standard 142-1991, Institute of Electrical and Electronic Engineers, New York, NY (chaired by coauthor Gordon Johnson)

[4] Standard for Automatic Transfer Switches, UL 1008, Underwriters Laboratories, Melville, NY

[5] Grounding of Alternate Power Sources, by R. Castenschiold. IEEE Conference Record. Industry Applications Society Annual Meeting, October 1997. Institute of Electrical and Electronic Engineers, New York, NY

[6] Factors to Consider When Upgrading Transfer Switching to Present Codes and Standards, by R. Castenschiold and I. F. Hogrebe. IEEE Transactions Industry Applications, Vol. 29, No. 3, May/June 1993; Institute of Electrical and Electronic Engineers, New York, NY

BIBLIOGRAPHY
[B1] IEEE Recommended Practice for Emergency and Standby Power Systems (Orange Book), Standard 446-1995, Institute of Electrical and Electronic Engineers, New York, NY

[B2] IAEI Soares Book on Grounding, 6th Edition, by J.P. Simmons, International Association of Electrical Inspectors, Richardson, TX

[B3] More About Standby Generator Grounding, GFP, and Currents that Go Bump in the Night by Hugh O. Nash, Jr., IEEE Transactions Industry Applications, Vol. 33, No. 3., May/June 1997, Institute of Electrical and Electronics Engineers, New York, NY

[B4] National Electrical Grounding Research Project, by T. Lindsey, IAEI News, May/June 1998, International Association of Electrical Inspectors, Richardson, TX


Rene Castenschiold, P.E., Life Fellow, IEEE
LCR Consulting Engineers, P A
Green Village, NJ 07935

Gordon S. Johnson, P.E., Life Fellow, IEEE
306 7th Street S
Dundee, FL 3383

 

 

 
Air Conditioning and Heat Pump Equipment
 

 

 

 

 

Home  | Join | Advertising | Seminars | Contact Us | Privacy Statement | Legal Notices
Copyright © 1997-2008 IAEI. All Rights Reserved.

 

 

 

Current Issue Home Page Issue Listing Series Focus on the Code Reprints Contacts Subscribe